SERVICE MANUAL KING SERIES ASH-18AK, ASH-24AK
1 Summary and features 18 Outdoor unit: Model ASH-18AK ASH-24AK 24 Outdoor unit: Remarks 1Ph 220~240V 50Hz R410a
22 Technical specifications ASH-24AK ASH-18AK Model . . COOLING Function Rated Voltage Rated Frequency HEATING COOLING HEATING 220-240V~ 220-240V~ 50Hz 50Hz 18000 19500 22000 23200 Power Input (W) 1640 1670 2120 2120 Rated Input (W) 2500 2550 3000 3000 Rated Current (A) 10.9 11.1 13 13 Total Capacity (Btu/h) Air Flow Volume (m3/h) (H/M/L)** Dehumidifying Volume (l/h) EER / C.O.P (W/W) Energy Class Model of Indoor Unit Fan Motor Speed (r/min) (H/M/L) .
Model of Outdoor Unit Com pres s or Manufacturer/trademark Com pres s or Model Com pres s or Type L.R.A.
3 Part name Air in Front Panel Manual switch Indoor unit Filter Guide louver Air out Indicator light Wrapping Tape Wall Pipe Remote control window Wireless remote control Heat Cooling Run Air in Connection pipe Outdoor unit Drainage hose Air out
4 Outline and installation dimension Outline and installation dimensions of indoor unit H Air inlet D W Tube exit Wall-Mounting Plate: Rear View 18/24 Ceiling Left Right Wall-Mounting Plate Model ASH-18AK ASH-24AK W(㎜) H(㎜) D(㎜) 1020 228 310
Outline and installation dimensions of outdoor unit ASH-18AK 913 342 680 378 Unit:mm 550 Bolt Nut Wrench
ASH-24AK 378 700 950 572 Unit:mm over over over over Bolt Nut Wrench
5 Electrical circuit diagram ASH-18AK ASH-24AK These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
6 Manual of functions of remote controller and operation method Manual 1 of functions of remote controller 6.1.1 Temperature parameter The room setting temperature(Tpreset) The room ambient temperature (Tamb) 6.1.2Basic Functions Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least. For the first energization, the compressor will be started without 3-minute lag.
Tpreset +2℃ Cooling Tamb Dry Tpreset -2℃ 6 min. 4 min. Stop 6 min. 4 min. Compressor Outdoor fan Indoor fan low speed Run Stop 6.1.2.2.3 Protection Antifreeze Protection Upon meeting the cooling condition, if it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped,and the indoor fan will run at low speed.
3.Other controls 1. Memory function Memory contents: Mode, up and down swing, Light, Setting temp., Setting fan speed, Ordinary setting Fahrenheit/Centigrade, after powered off, and powered on, it will run at the memory contents. If no timer setting function in last remote control order, the system will memorize the last remote control order, the system will memorize the last remote control order and work with last remote control setting.
(6) Turbo function The turbo function is available in Cool and Heat modes. (7) Dry function Dry function is available in Cool and Dehumidifying modes. (8) Auto fan speed control In this mode, indoor fan can run with Hig, Mid, Low speeds.
Manual 2 of functions of remote controller This manual is applicable to ASH-18AK, 24AK models, the centigrade is used for the following function manual, if there will be the Fahrenheit degree, that will be TF= TCX1.8+32. 1.
DRY Modes When Tamb. Tpreset 2 , the unit will run under DRY cooling mode, in which case the compressor and outdoor fan will be started and the indoor fan will run at low speed. When Tpreset 2 Tamb. Tpreset 2 , the unit will run under Dry mode, in which case the indoor fan will keep run at low speed, the compressor and outdoor fan will be stopped after 6mins. After 4 minutes, the compressor and outdoor fan will be restarted. The dehumidifying process is so repeated in cycle. When Tamb.
If it is detected that the evaporator tube temperature is too high, the outdoor fan will be stopped. When the tube temperature resumes to normal,the outdoor fan will be restarted. Noise Silencing Protection If the unit is stopped by pressing ON/OFF, the reversal valve will be stopped after 2-minute l ag; or 2 minutes wi l l be delayed upon mode switching. Over current product The overcurrent protection is the same with the the over current protection under cool mode.
1hr. 2hrs. 2hrs. above Tpreset Tpreset Tpreset temp. Tpreset Turbo function The turbo function is available in Cool and Heat modes. Dry function Dry function is available in Cool and Dehumidifying modes. Auto fan speed control In this mode, indoor fan can run with Hig, Mid, Low speeds.
(18/24) Disassembly procedures for indoor unit Operating Procedures / Photos 1. Disassemble the front panel, Filter, Electric box cover Front Pane Screw Protect board Open the front panel ,Push the filter upwards to unloose the clasp, and then pull out the two filters. Screw off the screws fixing the electric box cover remove the cover out. Electric box cover Filter 2. Disassemble the guide louver Bend the guide louver so that the movable lock of guide louver is released to remove the guide louver.
Operating Procedures / Photos 4. Disassemble the electric box cover Screw off the screws fixing the electric box cover and then open the cover, next unscrew the screws fixing the toggle switch on the cover, at last remove the cover out. Electric box cover 5. Disassemble water tray Loosen the clasp of the front and rear of water tray sub-assy and lift them up, pull out of the connection wire of swing motor, then can take out the water tray sub-assy.
Operating Procedures / Photos 6. Disassembling the evaporator Screw Screw off 5 screws fixing the left and right side of the evaporator, then elevate left side the evaporator to remove it backward. CAUTION: When repair, Carefully take out the evaporator and pay attention to protect the connecting pipe. Screw off one screw which fix the connection board clamp. Take down the connection board clamp. Screws 7.
(18) Disassembly Procedures for Outdoor Unit Operating Procedures / Photos 1. Disassemble Handle and Top Cover Top Cover Unscrew the screw fixing the handle, then push it downwards to take it out. Unscrew the screws fixing the top cover, and then lift the top cover to remove it. Screws Handle Screw 2. Disassemble Rear Grill Unscrew the screws fixing the rear grill to re- Rear Grill move it. Screws 3.
Operating Procedures / Photos 4. Disassemble Front plate Unscrew the screws fixing the cabinet to remove it. Front side plate 5. Disassembel Right side plate Unscrew the 9 screws of the right side plate, then take down the right side plate. Right side plate 5. Disassemble Electric Box Sub-assy unscrew the screw of electric box, pull out the Screw lead out insert of compressor, four-way valve and motor, then take down the electric box.
Operating Procedures / Photos 7. Disassemble Gas and Liquid Valves Unsolder the pipeline connecting with valves ( to prevent soldering gun from burning out the chassis).Unscrew 2 bolts fixing gas valve ,and then unsolder the weld spot between pipeline and gas valve to remove gas valve. Unscrew the 2 bolts fixing liquid valve, and then unsolder the weld spots between pipeline and liquid valve to remove liquid valve.
Operating Procedures / Photos 10. Disassemble Four-way Valve Only for cooling and heating unit Unscrew the fixing nut of the four-way valve coil and remove the coil. Wrap the four-way valve with wet cotton and unsolder the 4 weld spots connecting the four-way valve to take it out. Welding Weld spots Four-way Valve process should be as quick as possible and keep wrapping cotton wet all the time. Be sure not to burn out the lead-out wire of compressor. 11.
(24) Disassembly Procedures for Outdoor Unit Operating Procedures / Photos 1. Disassemble Top Cover and Front Side Plate Unscrew the screws fixing the top cover, and then lift the top cover to remove it. Unscrew the 3 screws fixing the front side plate to remove it. Top Cover Screws Front Side Plate 2. Disassemble Rear Grill Unscrew the 4 screws fixing the rear grill to remove it. Rear Grill 3. Disassemble Cabinet Unscrew the screws fixing the cabinet to remove it.
Operating Procedures / Photos 4. Disassemble Electric Box Sub-assy Unscrew the 2 screws fixing electric box to pull out the connection line between fan motor, compressor,four-way valve, and then lift the elec- Electric box tric box to take it out. Screws 5. Disassemble Right side plate Unscrew the screw of the right side plate, then take down the right side plate. Right side plate 6.
Operating Procedures / Photos 7. Disassemble Axial Flow Fan Unscrew the nut fixing the fan with a spanner to take out the fan. Axial Flow Fan Nut 8. Disassemble Outdoor Motor Unscrew the screws fixing the motor support, and then lift it upwards to remove it. Unscrew the screws fixing the motor and pull out the connection line between it and electric box to remove it. Motor Terminal Screw of Motor Motor Support Screws 9.
Operating Procedures / Photos 10. Disassemble Capillary Unsolder the weld spots of capillary,valve and outlet tube of condenser to remove the capillary. Prevent welding slag from blocking the capillary. Capillary 11. Disassemble Compressor Unsolder the pipeline connecting the compressor, and then unscrew the 3 foot-nuts fixing conpressor to remove it.
PARTS GUIDE KING SERIES ASH-18AK, ASH-24AK
(18/24) Exploded View of Components and Parts of Indoor unit
Parts List for ASH-18AK Indoor unit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Description Parts No.
Parts List for ASH-24AK Indoor unit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Description Parts No.
(18) Exploded View of Components and Parts of outdoor unit
Parts List for ASH-18AK Outdoor unit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23.1 23.2 23.3 24 25 26 27 28 Description Parts No. ASH-18AK Outdoor unit Small Handle 26235401 Axial Flow Fan 10333426 Fan Motor 15013070 Motor Support 01703059 Condenser Assy 01113033 Condenser Clamp 01175202 Top Cover 01255001 Rear Grill 014730371 Electrical Box 01403835 Capacitor CBB61 3.
(24) Exploded View of Components and Parts of outdoor unit
Parts List for ASH-24AK Outdoor unit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24.1 24.2 24.3 25 26 27 28 Description Parts No. ASH-24AK Outdoor unit Panel Grille 22414102 Front Plate 01433017 Axial Flow Fan φ472X165 10338731 Fan Motor 15015421 Motor Support 01703027 Condenser Assy 01113034 Top Cover 01255262 Mesh Enclosure 01473028 Electric Box Cover Plate 01413047 Electric Box Sub-Assy 01403248 Capacitor CBB65 50uF/450V φ50X120 33000001 Capacitor CBB61 3.
9 Failure and analysis Note: When replacing the controller, make sure insert the wire jumper into the new controller, otherwise, the running indicator off 3s, blink 15 times, (the dual eight will display C5) but cannot turn on the unit. The breaker trips at once when it Measure insulation resistance to ground to see if there is any leakage. is set to "ON". Trip of breaker or blow of fuse The circuit or the part of the air conditioner has malfunction.
Improper set of temperature Adjust set temperature If cooling (heating) load is proper Check the forecasted load of cooling (heating) The refrigerant has leakage or is insufficient Malfunction of refrigerant flow Leakage between the high pressure and the low pressure inside the compressor Malfunction of four-way valve Poor COOL(HEAT) operation Local block of capillary Blockage of cooling system Heat insulation for the connection pipes of the indoor unit and the outdoor unit is bad.
The indoor fan motor is burned or breaks or has the heat protector malfunction. The fan does not run when it is set to supply air. In the cooling and heating mode, the compressor runs, but the outdoor fan does not run. The compressor is too hot and leads to the action of the protector. The built-in heat protector of the motor breaks frequently because the motor is abnormal. Replace the fan motor Wrong connection Make the correction connection based on the circuit drawing.
Drainage pipe blocked or broken Change drainage pipe Water leakage Wrap of refrigerant pipe joint is not close enough. Re-wrap and make it tight. Fan of indoor unit contacts other parts. Adjust fan location. Foreign object in indoor unit Take out the foreign object. Compressor shakes too much. Abnormal sound and shake Adjust support washer of compressor, and tighten loosen screws. Touch of pipeline of outdoor unit Separate the touching pipeline. Touch of inner plates 1. Tighten connect screw.
PG motor locked protection H6: Probable reasons: 1. Air vents were blocked which may cause the fan speed is too slow; 2. Fan blade locked; 3. Motor locked; 4. Fan motor capacitor damaged; 5. Motor damaged (ordors, winding, open circuit or shortcircuit are not normal, when testing the winding, pls distinguish whether the motor body cause temperature is too high so that bring on the thermal protector starts up) 6.