Operating instructions

IM-P623-04 ST Issue 5
7
Body design conditions
HP80 and 100 PN250, Class 1500
to ANSI B 16.34
HP150 and 210 PN420, Class 2500 to ANSI B 16.34
PMA
Maximum
HP80 and 100 258 bar g @ 93
°C (3741 psi g @ 199°F)
allowable pressure
HP150 and 210 431 bar g @ 93
°C (6249 psi g @ 199°F)
Maximum
HP80 500°C @ 126 bar g (932°F @ 1827 psi g)
TMA
allowable temperature
HP100 570°C @ 57 bar g (1058°F @ 827 psi g)
HP150 and HP210 570°C @ 97 bar g (1058°F @ 1407 psi g)
Minimum allowable temperature
HP80 -14
°C (6.8°F)
HP100, 150 and 210 -22°C (-7.6°F)
HP80 80 bar g @ 500°C (1160 psi g @ 932°F)
PMO
Maximum
HP100 100 bar g @ 530
°C (1450 psi g @ 986°F)
operating pressure
HP150 150 bar g @ 537
°C (2175 psi g @ 999°F)
HP210 210 bar g @ 525°C (3045 psi g @ 977°F)
Maximum
HP80 500°C @ 126 bar g (932°F @ 1827 psi g)
TMO
operating temperature
HP100 570°C @ 57 bar g (1058°F @ 827 psi g)
HP150 and HP210 570°C @ 97 bar g (1058°F @ 1407 psi g)
Minimum
inlet pressure
HP80 20 bar g (290 psi g)
for satisfactory operation is:
HP100, 150 and 210 25 bar g (363 psi g)
Minimum operating temperature 0°C (32°F)
PMX Backpressure for correct operation must not exceed 90% of the upstream pressure
Designed for a maximum cold
HP80 and HP100 388 bar g (5626 psi g)
hydraulic test pressure of:
HP150 and HP210 646 bar g (9367 psi g)
The product must not be used in this region.
The product should not be used in this region or beyond its operating range as damage
to the internals may occur.
A - B Flanged PN63 and PN100.
A - C Flanged ANSI 600.
A - D Flanged ANSI 900 and ANSI 1500 ( socket weld and butt weld HP80 and HP100).
A - E Flanged ANSI 2500
(socket weld and butt weld HP150 and HP210).