Measurement Guide

Specifying Non-Powered Foundation Vents
Automatic Foundation Vents (non-powered) open and close automatically using a heat/cold sensitive coil. The
louvers open completely at approximately 70°F and completely close at approximately 40°F. These vents self-
adjust all year.
To Specify:
Whenever possible, foundation vents should be placed on all sides of the foundation. This will create an
intake/exhaust system that delivers a steady flow of air. One vent should be installed for each 8 to 10 feet of
foundation wall.
Most building codes require 1 square foot of open ventilation area for every 150 square feet of crawlspace.
Generally, Automatic Foundation Vents have 50 inches of net free area per vent. Therefore, install one vent for
every 50 square feet of crawlspace.
For crawlspaces with polyethylene installed on 80-90% of the floor, the ventilation requirement changes to 1
square foot of ventilation for every 500 square feet of crawlspace with a minimum of 4 vents installed to
provide cross ventilation. For crawlspaces with polyethylene, install at least one vent for every 500 square feet
of crawlspace.
Specifying Powered Foundation Vents
Powered foundation vents are designed for foundations that require a higher rate of airflow and for areas that
are difficult to vent. Depending on the fan model the vent can move large amounts of air per hour. Designed to
run continuously on low speed, they draw minimal electricity. Air Vent recommends power foundation vents be
fitted with a thermostat and a humidistat to control the operation of the vent.
To Specify:
To determine the correct number of powered foundation vents use the following formula:
1) Multiply the square feet of crawlspace by the height in feet. This gives the number of cubic feet in the
crawlspace.
2) Multiply the cubic feet in the crawlspace by the number of air changes per hour desired (4 to 6 is the
recommendation). This gives the total number of cubic feet of air that has to be moved per hour to
produce the desired number of air changes.
3) Divide this number by 7,200 or 11,160 (depending on which model foundation vent is being used) to
obtain the number of powered foundation vents needed.
4) Install non-powered foundation vents on one side of the crawlspace to provide intake air for the powered
foundation vents.

Summary of content (1 pages)