LogiCool™ OnRak IT Cooling Technical, Installation, Operational and Maintenance Manual
LogiCool™ OnRak IT Cooling About Airedale Products & Customer Services Active Cabinet Exhaust Warranty, Commissioning & Maintenance As standard, Airedale guarantees all non consumable parts only for a period of 18 months, variations tailored to suit product and application are also available; please contact Airedale for full terms and details.
IT Cooling LogiCool™ OnRak Warranty Warranty All AIAC products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an AIAC engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
LogiCool™ OnRak IT Cooling Health and Safety Active CabinetTheExhaust information contained in this manual is critical to the correct operation and IMPORTANT maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/electrical equipment, care must be taken if you are to obtain the best results.
IT Cooling LogiCool™ OnRak CONTENTS About Airedale Products & Customer Services ...................................................................... 2 Warranty ..................................................................................................................................... 3 Health and Safety ....................................................................................................................... 4 Personal Protective Equipment ..........................................
LogiCool™ OnRak IT Cooling Specifier’s Guide Indoor Unit Nomenclature Active Cabinet ExhaustLOR Example: LOR 60 80 42U C 028 033 0 Introduction 60 42U - C 033 - 0 LogiCool OnRak Case width in centimetres Unit height in U Separator Chilled water cooling Nominal cooling capacity in kW Separator 230V / 1Ph / 50Hz / 60Hz The OnRak is a compact rear door heat exchanger designed to manage discharge temperatures from a server rack into the aisle space.
IT Cooling LogiCool™ OnRak Standard Features 0-10V 2 or 3 way chilled water valve Advanced Airetronix controls Water temperature sensor Tri coloured LED (Alarm status) for easy fault detection Rack mounted temperature / humidity sensor Leak detection Bleed and drain valves LOR 8042U-C038-0 EC fan node LOR 8042U-C032-0 EC axial fans LOR 6042U-C0 33-0 Standard Features LOR 6042U-C0 28-0 The OnRak unit comes with a series of standard features.
LogiCool™ OnRak Rack Mounted Temperature/ Humidity Sensor IT Cooling Rack mounted temperature and Humidity sensor shall be supplied as standard. This shall be supplied loose for onsite fitment in a customer rack. Active CabinetLeak Exhaust Leak Detection detection for the water system, able to report alarm status to the BMS system shall be provided. The unit shall then be shut down before any damage occurs. The leak detection tape shall be fitted within the drip tray of the coil.
IT Cooling LogiCool™ OnRak Optional Features Lon BMS connection pCOWeb BacNet protocol Programming smart key Threaded pipe connections Quick coupling water connections Flexible hoses of alternative lengths Isolating solenoid valves Dual power supply Uninterrupted Power Supply Static Transfer Switch Room mounted temperature / humidity sensor Rack Pressure Management Features available Display Options 1. 2. 3. 4.
LogiCool™ OnRak Lon BMS Connection IT Cooling The Airedale controllers, using special serial cards, shall be integrated into LonWorks® networks. The RS485 and the FTT10 standards shall be supported by the LonWorks® serial cards.
IT Cooling Dual Power Supply LogiCool™ OnRak Dual supply for redundancy and backup in the event of mains supply failure shall be provided. The dual power supply switch ensures that the OnRak always has an incoming power supply. For the dual power supplies to operate effectively, the incoming power supplies must have the same voltage and frequency and be within 120° Phase Angle.
LogiCool™ OnRak IT Cooling Technical Data Active Cabinet Exhaust IMPORTANT The following information is for general guidance; refer to the certified drawings provided for installation. CAUTION ALL work MUST be carried out by technically trained competent personnel. The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work. A fused and isolated electrical supply of the appropriate rating should be installed.
IT Cooling LogiCool™ OnRak Cooling Performance LOR 6042U-C028-0 (N+1 configuration, Fans at 75%) 36 34 32 Cooling Performance (kW) 30 28 26 45°C SDT 24 22 40°C SDT 20 18 16 35°C SDT 14 12 10 11 12 13 14 15 16 17 18 19 Water Inlet Temperature °C (based on 6°C T) (1) At the design chilled water temperature project a line until it intersects with the Server Discharge Temperature (SDT), read off the cooling performance. (e.g. 14°C projected up to 35°C SDT Line, reading across to 17.3kW.
LogiCool™ OnRak IT Cooling Cooling Performance LOR 6042U-C033-0 (N Configuration, Fans at 100%) Active Cabinet Exhaust 36 34 32 28 Cooling Performance kW Cooling Performance (kW) 30 45°C SDT 26 24 22 40°C SDT 20 18 35°C SDT 16 14 12 10 11 12 13 14 15 16 17 18 19 20 21 Water Inlet Temperature °C (basedon on 6°C Water Inlet Temperature °C (based 6°CT) T) (1) At the design chilled water temperature project a line until it intersects with the Server discharge temperature (SDT), read off
IT Cooling LogiCool™ OnRak Cooling Performance LOR 8042U-C032-0 (N+1 configuration, Fans at 75%) 36 34 32 30 Cooling Performance kW Cooling Performance (kW) 28 45°C SDT 26 24 40°C SDT 22 20 18 35°C SDT 16 14 12 10 11 12 13 14 15 16 17 18 19 Water Inlet Temperature °C (based on T) 6°C T) Water Inlet Temperature °C (based on 6°C (1) At the design chilled water temperature project a line until it intersects with the Server discharge temperature (SDT), read off the capacity.
LogiCool™ OnRak IT Cooling Cooling Performance LOR 8042U-C038-0 (N Configuration, Fans at 100%) 42 Active Cabinet Exhaust 40 38 34 45°C SDT 32 Cooling Performance kW Cooling Performance (kW) 36 30 28 26 40°C SDT 24 22 20 35°C SDT 18 16 14 12 10 11 12 13 14 15 16 17 18 19 20 21 Water Inlet Temperature °C (based on 6°C T) Water Inlet Temperature °C (based on 6°C T) (1) At the design chilled water temperature project a line until it intersects with the Server discharge temperature (SD
IT Cooling LogiCool™ OnRak Ethylene Glycol Correction Factors Calculation of Design Volumetric Flow Rate (l/s) The maximum design volumetric flow rate can be calculated using the following equation: = V Q x Cp x ΔT Where: Q T Cp Calculation of Indoor Unit Pressure Drop (Ps) = = = = Cooling Capacity (kW). Temperature Difference between Water/Glycol Entering/ Leaving (°C). Density of Glycol/Water mixture at design condition. Refer to table below. Specific heat capacity at design condition.
LogiCool™ OnRak IT Cooling Mechanical Data Active Cabinet Exhaust mm kg Dimensions - H x W x D Weight - Machine – Operating Construction Material/ Colour Nominal Air flow Fan redundancy Gross Total cooling Capacity Fan gains EER LOR6042U-C028-0 2030 x 600 x203 65 75 m³/s (1) 1.4 N+1 28.1 161 175 kW W LOR6042U-C033-0 LOR8042U-C032-0 2030 x 600 x 203 2032 x 800 x 213 65 75 96 110 Sheet steel, epoxy baked powder paint RAL 7021 (Black Grey) 1.8 1.4 N N+1 33.4 32.
IT Cooling LogiCool™ OnRak Dimensional Data LOR 600 LOR 800 mm mm A 600 800 Dimensions B C 210 2030 213 2032 D 90 103 E 110 110 Component Masses Door Mating frame Fans mm kg kg kg LOR 600 LOR 800 65 28 5 5 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
LogiCool™ OnRak IT Cooling Sound Measurement Method Active Cabinet Exhaust Measurement of Sound Data All sound data quoted has been measured in the third-octave band limited values, using a real time analyser calibrated sound intensity meter in accordance with BS EN ISO9614 Part 1: 1995. All sound power levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1: 1995.
IT Cooling LogiCool™ OnRak Pipework Schematics Scheme 1 3 way chilled water valve Bypass balancing valve Normally closed solenoid valves Threaded pipe connections Scheme 2 3 way chilled water valve Bypass balancing valve Normally closed solenoid valves Quick connector IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
LogiCool™ OnRak IT Cooling Pipework Schematics Scheme 3 Active Cabinet Exhaust 2 way chilled water valve Normally closed solenoid valves Threaded connections Scheme 4 22 2 way chilled water valve Normally closed solenoid valves Quick connector IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
IT Cooling LogiCool™ OnRak Installation IMPORTANT If the unit is dropped, it should immediately be checked for damage and reported to Airedale. Positioning The mating frame is attached to the customers rack. An air tight seal must be placed between the mating frame and the data enclosure. The OnRak is then lifted onto the hinges and as it’s closed will produce an air tight seal. CAUTION Airedale will accept no responsibility for mishandling during the positioning of the equipment.
LogiCool™ OnRak Fitting Hinges IT Cooling The OnRak needs to be lifted vertically to ensure that the assembly fits onto the hinges. must be taken whilst locating the lift-off hinges together prior to lowering into place. Active CabinetCareExhaust Illustrations for guidance only Data Rack Feet 24 The data rack feet must be used prior to the unit being mounted to the rack. This takes the weight off the castors.
IT Cooling Rack Support Wheel LogiCool™ OnRak A support wheel is provided for fitment under the Onrak door. This is to be at the same level as the door rack feet. The wheel is to be fitted ensuring that it has free movement.
LogiCool™ OnRak IT Cooling Door Latch Mechanism Active Cabinet Exhaust CAUTION 26 Ensure that the door latch mechanism does not snag on the sheet metal. Distortion of the door can occur if the latch is forced IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
IT Cooling Floor Cut Outs LogiCool™ OnRak To enable the flexible pipework installation the following minimum cut out is required in the floor tile below the unit. Contact your grommet supplier for exact sizes. This ensures that the pipework does not get obstructed causing additional strain on the fittings. Floor Tile Cut Out Dimension (Minimum) Mating Frame Cut Out IMPORTANT Ensure that the mating frame and floor is sealed for correct unit operation.
LogiCool™ OnRak Water Connections IT Cooling Two flexible, stainless steel braided hoses connect the coil to the chilled water supply. flexibility of the hoses allows the OnRak door to be easily opened for accessing Active CabinetThe Exhaust hardware within the server cabinet, without the need to disconnect services or disrupt cooling.. Outlet Inlet Unobtrusive pipework Additional pipework components are then installed under the server room floor.
IT Cooling LogiCool™ OnRak Flexible Water Connection Pipework Sweep The stainless steel braided must be installed so that the hose has unobtrusive movement in either fully opened or closed positions Plan View Side View Recommended Dimensions X = Floor Void Depth Y = 500mm Z = 110mm Minimum recommended hose length X + 1m (Hoses available as standard in 1.5m and 3m lengths) IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
LogiCool™ OnRak IT Cooling Compression Fittings The recommended method of using compression fitting is as follows:- Active Cabinet Exhaust 1 2 Nip nut slightly to secure olive onto pipe. Apply small amount of oil to top of olive. 4 3 Insert into fitting (remove any excess sealant with a cloth). Undo and remove pipe from fitting. Apply small amount of pipe sealant to leading edge of olive that will be inserted into fitting. 5 6 Mark two alignment marks on fitting.
IT Cooling Chilled Water Valve (3 Way) LogiCool™ OnRak The chilled water valve has an indication of flow on the stem. The actuator is securely attached to the top of the valve so that when there is a demand for cooling the valve opens allowing water to flow through the coil. No demand, the water goes through the bypass (0 VDC no demand, 10 VDC 100% demand).
LogiCool™ OnRak Chilled Water Valve (2 Way) IT Cooling The chilled water valve has an indication of flow on the stem. actuator is securely attached to the top of the valve so that when there is a demand Active CabinetThe Exhaust for cooling the valve opens allowing water to flow through the coil. No demand, the water is shut off allowing no water to enter the coil (0 VDC no demand, 10 VDC 100% demand).
IT Cooling Solenoid Valve LogiCool™ OnRak The solenoid valve can be installed in any position, vertical with coil upwards preferred. Mass 1kG a 105 CAUTION b 85 c 106 f 71 g 46 l 28 s 42 The solenoid valve electrical connection must be a maximum of 3m away from the customer terminal box. This is to ensure EMC Compatibility. Coil Water Connections Swivel pipework connection to coil Coil connections are brazed at Airedale. Full pressure testing to 20Barg is carried out prior to unit despatch.
LogiCool™ OnRak Customer Terminal Box IT Cooling The customer terminal box is attached to the coil guard during shipment. Carefully remove this and feed the box through the hole in the mating frame. This must be done after the door is fitted to the mating frame. Active Cabinet Exhaust Dual Power Supply The dual power supply can be either fitted into a rack or fitted in the floor void under the server rack. The following procedures apply.
IT Cooling IMPORTANT LED Indicators LogiCool™ OnRak Attach the earth strap to the rear of the power supply unit. Locate the Dual power supply between the cable support guides of the server rack. Secure the unit with screws supplied by your rack manufacturer. Attach the incoming fused power supplies. Fit power supply retaining clips. Attach the outgoing power supply to the customer terminal box. Do not route the outgoing cable through the area occupied by the pipework.
LogiCool™ OnRak Under Floor Dual Power Supply IT Cooling The under floor Dual Power supply is located under the floor void. The supply is to be mounted securely. Provision is made for fixing to the floor or associated supports. Attach relevant earth bonding to the power supply. Active Cabinet Exhaust Attach the incoming fused power supplies. (The Primary supply for this supply is always “A”.) Fit power supply retaining clips. Attach the outgoing power supply to the customer terminal box.
IT Cooling Uninterrupted Power Supply LogiCool™ OnRak The UPS shall fit within the server cabinet and shall be the same dimension as 1U/ 2U rack. Various capacities are available. Installation of the UPS is rack mounted. Full information of the installation is supplied with the UPS. The UPS can be personalised to the application (response times etc) through a computer. This connection can be either RS232 or USB.
LogiCool™ OnRak Rack Pressure Management IT Cooling The rack pressure management comes in two parts for onsite fitment. Part one A static pressure ring (-ve negative pressure) is fitted behind the coil guard. An airflow tube comes out from the controller and is then routed around the drip tray.
IT Cooling Rack Sealing LogiCool™ OnRak The rack must be sealed so that air does not bypass the servers. The racks must not have any ventilation holes such as a perforated roof. Any space within the server racks that are redundant must be sealed with blanking panel (usually supplied in 1U and 2U). Figure 1 Wrong Cabinet not sealed CAUTION OnRak OnRak The heat leaving the servers must be sensed by the OnRak to ensure correct operation.
LogiCool™ OnRak IT Cooling Interconnecting Wiring L1 N1 PE Mains incoming supply 230V/1PH/50Hz 509 500 509 500 Flow solenoid valve Common Return solenoid valve Common 824 500 502 Signal to chilled water valve Common 24VAC 827 828 502 500 SCR Air on temperature Air on humidity 24VAC Common Screened cable terminated at controller.
IT Cooling LogiCool™ OnRak Automatic Fan Disconnect This type of connector removes the requirement for manual disconnection of the fan wiring, as removing the fan automatically and fully disconnects power from the fan. Plug (Fan side) Socket (Unit side) IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
LogiCool™ OnRak IT Cooling Controls Active Cabinet Exhaust Addressing the Display Keypad The address of the display keypad can be configured only after having connected the power supply, using the RJ11 connection cable.
IT Cooling LogiCool™ OnRak 1 4 2 5 3 6 When more than one alarm is active the ALARM button will illuminate red. 1. ALARM Pressing the ALARM button once will indicate information regarding any active alarms. Pressing the ALARM button twice will reset any active alarms. Prg 2. PRG Pressing the PRG button will select the main navigation menu. Esc 3. ESC Pressing the ESC button will return the user to the main display screen showing unit status. Pressing the UP button can either: 4.
LogiCool™ OnRak IT Cooling Extra Functions Buttons UP + DOWN+Exhaust Allow users to change display address. Active Cabinet + + ENTER + + Esc + Prg + + ALARM + ENTER Allows access to controller system information. ALARM + UP Allows access to change controller address (only when display address is zero) ESC + ENTER Allows the user to switch between the preinstalled languages PRG + ENTER Temporary displays the address of the controller. ENTER + UP Change unit on remote display keypad.
IT Cooling LogiCool™ OnRak Enabling the Unit Prg To turn the unit on press the option and press key to enter the program menu. Using the and keys select the Unit On/Off : When is pressed the above screen will be shown. To turn the unit on simply press the screen will change: key again and the Esc Once the screen has changed to the above, press the key which will return back to the main screen. IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
LogiCool™ OnRak IT Cooling Dew Point Control Active Cabinet Exhaust The pCO controller within the OnRak unit can calculate the dew point within a room by monitoring the temperature and humidity of that room and then performing a calculation to provide a dew point value. The pCO controller uses a signal received from the temperature/humidity sensor which is wired into the controller.
IT Cooling LogiCool™ OnRak Temperature Sensor Locations Air Off Temp. Sensor No. 1 Server Air Off / Coil On Sensor No. 1 Air Off Temp. Sensor No. 2 Server Air Off / Coil On Sensor No. 2 Air Off Temp. Sensor No. 3 Room Temp. & Humidity Sensor Server Air Off / Coil On Sensor No. 3 Air Off Temp. Sensor No. 4 Server Air Off / Coil On Sensor No.
LogiCool™ OnRak IT Cooling Modes of Operation Active Cabinet Exhaust Temperature Neutral Mode Server Air Off Temperature Sensors regulate the fan speed to maintain a constant cabinet temperature of 40°C Air Off Temp. Sensor No. 1 Heat lost to air Server Air Off Sensor No. 1 Air Off Temp. Sensor No. 2 Server Air Off Sensor No. 2 Air In Sensor AIR OFF 20˚C Air Off Temp. Sensor No. 3 Server Air Off Sensor No. 3 AIR IN 20˚C Air Off Temp. Sensor No.
IT Cooling LogiCool™ OnRak Load Neutral Mode Server Air Off Temperature Sensors regulate the fan speed to maintain a constant cabinet temperature of 40°C Heat lost to air Server Air Off Sensor No. 1 Remote Room Air Temperature Sensor ROOM AIR TEMP 20˚C Server Air Off Sensor No. 2 AIR OFF 18˚C Air Off Temperature is used to maintain the Room Air Temperature by modulating the 3-way valve to adjust the flow of water through the coil Server Air Off Sensor No. 3 Server Air Off Sensor No.
LogiCool™ OnRak IT Cooling Rack Pressure Management The fans will operate to maintain the “air off” temperature as long as the pressure remains within the normal operating range. However, if the pressure within the server space changes beyond the high or low differential set-points, the fans prioritise pressure control to bring the server pressure back within limits, at which point normal temperature control resumes.
IT Cooling LogiCool™ OnRak Commissioning Procedure General To be read in conjunction with the commissioning sheets provided. CAUTION Please ensure all documents have been completed correctly and returned to Airedale technical support to validate warranty. CAUTION All work MUST be carried out by Technically Trained and competent personnel. The equipment contains live electrical and moving parts, Isolate prior to maintenance or repair work.
LogiCool™ OnRak IT Cooling Commissioning Procedure Active Cabinet Exhaust Fan Removal Alarm Check alarm state when a fan goes offline. Differential Pressure The differential pressure switch should cause the OnRak fans to increase / decrease when the server fans are active. One of the fans can be removed to allow the differential pressure to be recognised if the server load is low.
IT Cooling LogiCool™ OnRak Maintenance Changing EC Fans The fans are designed as plug and play “hot swap” enabling the fans to be changed without the need to disconnect the power from the entire unit. Removing the 4 security fixings enable the fan to be removed The unit has automatic disconnect sockets to the fan motors. The remaining fans will increase speed to compensate for the fan being serviced (only in N+1 configuration) CAUTION The unit will remain live up to the fan disconnect socket.
LogiCool™ OnRak IT Cooling Operational Maintenance checks Active Cabinet Exhaust Owners Responsibility To ensure that the unit can be maintained correctly the following requirements are required. Maintain a safe working environment around the unit, free from obstructions and debris. The unit shall follow the following maintenance regime as a minimum. The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work.
IT Cooling LogiCool™ OnRak Troubleshooting FAULT POSSIBLE CAUSE REMEDY/ACTION Unit will not start No power Check power supply to the controller. Wired incorrectly Check wire connections in accordance with wiring diagram on control panel. Loose wires Check all wires, connections, terminals etc. Power supply failure Check power supply at circuit breaker. Wiring to motor Check voltage at motor terminals.
LogiCool™ OnRak Active Cabinet Exhaust 56 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
IT Cooling LogiCool™ OnRak IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.
Head Office: Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY United Kingdom Tel: Fax: e-mail: website: PART NO: (TM E) V1.1.0 V1.3.0 V1.4.0 V1.5.0 V1.6.0 ISSUE 12/2009 11/2010 12/2010 02/2011 05/2011 09/2012 02_2013 +44 (0) 113 239 1000 +44 (0) 113 250 7219 enquiries@airedale.com www.airedale.