Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Temperature Sensor Locations
3-way
regulating valve
controlling air
off temperature
Water Temp. Sensor ensures the water inlet
temperature is above the dew point.
Room Temp. &
Humidity Sensor
Server Air Off /
Coil On Sensor
No. 1
Server Air Off /
Coil On Sensor
No. 2
Server Air Off /
Coil On Sensor
No. 3
Server Air Off /
Coil On Sensor
No. 4
Sever Air Off / Coil On
sensors monitor the
temperature / heat
generated from the
server and regulates the
fans to maintain a
constant temperature.
Room Temp. & Humidity
Sensor is used to
calculate the dew point
of the air in the room.
Air Off Temp.
Sensor No. 1
Air Off Temp.
Sensor No. 2
Air Off Temp.
Sensor No. 3
Air Off Temp.
Sensor No. 4