.COVER Upflow – Precision Air Conditioning 8kW - 101kW TECHNICAL MANUAL
-V Precision Air Conditioning AB OUT AIR ED AL E About Airedale Products & Customer Services WARRANTY All AIAC products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an AIAC engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
Precision Air Conditioning -V CONTENT S Contents INDOOR UNIT 4 General Description ................................................................................................................4 Unit Identification.................................................................................................................... 4 Introduction ............................................................................................................................ 4 Standard Features ..............
Precision Air Conditioning -V Indoor Un it General Description GENERAL UNIT IDENTIFICATION ALPHACOOL PRECISION AIR CONDITIONING RANGE V Upflow Configuration 9 - 95 Model Size (Expressed as Nominal Cooling in kW) A Air Cooled Remote Condensing Unit X Air Cooled Remote Condenser CW Chilled Water D Dual Circuit AT Example INTRODUCTION Controls V31AD-AT Designed to provide environmental Precision air conditioning tolerances within the conditioned space, such as Telecommunication Facilities, C
Precision Air Conditioning -V General Description STANDARD FEATURES Unit cabinets are manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide a durable finish. Standard unit colour is Light Grey (RAL 7035). Internal strength and rigidity is provided by a welded space frame constructed of channel profile folded steel. Cabinets are lined internally with fire resistant 20mm foam (UL94 V0) for thermal and acoustic insulation.
-V Precision Air Conditioning General Description GENERAL STANDARD FEATURES Chilled Water Coil (CW Models) Large surface area coil(s) ideally positioned to optimise airflow and heat transfer, manufactured from refrigeration quality copper tubes with mechanically bonded aluminium fins. Fins are coated with a non-stick acrylic film (hydrophilic) which provides additional corrosion protection and efficient surface water removal for improved performance.
Precision Air Conditioning -V General Description STANDARD FEATURES An adjustable differential pressure switch activates a visual alarm at the status panel and breaks the power supply in the event of a fan or motor failure. Compressor Compressor(s) are mounted on the base via the use of vibration isolators. Each compressor is designed for use with R407C refrigerant.
-V Precision Air Conditioning General Description GENERAL STANDARD FEATURES Electrical The control panel contains the necessary fan motor contactors and overloads, compressor starter (X type units) contactors, transformer, sub circuit protection, volt free contacts, mains and inter-connecting terminals. The panel is situated within the cabinet and is hinged for easy access to other components within the unit. The electrical control panels are wired to the latest European standards and codes of practice.
Precision Air Conditioning -V General Description OPTIONAL EXTRAS - GENERAL This feature is included as part of the Intelligent Head Pressure Control option, as detailed above and comes as standard when the EEV options is selected. (A & X Models) Specifically designed for night time operation as optimum low noise levels are achieved with reduced ambient temperature and room loads, this feature is also ideal for residential and other outdoor noise critical applications.
Precision Air Conditioning -V General Description GENERAL OPTIONAL EXTRAS - GENERAL Water Conductivity & Cylinder Type Conductivity is a measure of the ability of water to pass an electric current, measured in micro Siemens / centimetre (mS/cm). 3 different cylinders are available which correspond to the supply water conductivity. Matching the correct cylinder type with the conductivity of the supply water ensures optimum performance and increases the life span of the cylinder.
Precision Air Conditioning -V General Description OPTIONAL EXTRAS - GENERAL 97mm, pleated disposable panel filters conforming to BS EN 779-F6. Protected by 22mm, disposable, synthetic type pre filters conforming to BS EN 779 G3. (Except Sizes 35, 55, 90 & 95) To maintain design ESP, fan selection may alter with high efficiency filters, please refer to General Specification.
-V Precision Air Conditioning General Description GENERAL OPTIONAL EXTRAS - GENERAL Fan & Motor Anti Vibration Mounts Spring type vibration isolators can be fitted between the fan and motor mounting plate and the unit chassis. Condensate Pump The condensate pump has a 6 litre reservoir with a capacity of 5 l/m at a head of 10.8m and is mounted in the unit base, for pump performance; refer to Design Features & Information.
Precision Air Conditioning -V General Description OPTIONAL EXTRAS - GENERAL Constructed to match main cabinet design Light Grey (RAL 7035) available: · Front only or 3 way discharge air · Egg crate or double deflection grilles Discharge Air Configuration Standard configuration is top forward air discharge. Top reverse air discharge is available, please specify at order.
Precision Air Conditioning -V Dimensional & Installation Data MODELS: A, X OR CW - STANDARD AIRFLOW CONFIGURATION (MM) A B E A B A B C D A B 800 9 - 16 D (1) 19 - 35 41 - 55 1450 G 65 - 95 A, X & CW A, X & CW A, X & CW A, X & CW A, X & CW CW G mm mm mm mm mm mm 2000 G HxDxW 1940 x 800 x 900 1940 x 800 x 1450 1940 x 800 x 1450 1940 x 800 x 2000 1940 x 800 x 2550 1940 x 800 x 2550 2550 G A(4) 282 (258) 282 (258) 596 (N/A) 478 (N/A) 698 (N/A) 698 (N/A) B(4) 337 (311) 401 (477) 477
Precision Air Conditioning -V Dimensional & Installation Data DIMENSIONS 1280 1 760 2040 (1) A, X & CW A, X & CW AD, XD & CW AD, XD & CW AD, XD & CW CW mm mm mm mm mm mm A 900 1450 1450 2000 2550 2550 V 9 - 23 V 23 - 55 V 65 - 90 V 95 A, X & CW AD, XD & CW AD, XD & CW CW mm mm mm mm A 350 450 550 550 V 9 - 16 V 19 - 23 V 23 - 35 V 41 - 55 V 65 - 90 V 95 A, X & CW A, X & CW AD, XD & CW AD, XD & CW AD, XD & CW CW mm mm mm mm mm mm A 820 1370 1370 1920 2470 2470 V 9 - 16 V 19 - 25 V 23 - 35 V
Precision Air Conditioning -V Dimensional & Installation Data GENERAL WEIGHTS 1 PIECE DELIVERY V9A V13A V16A V19A V23A V25A V23AD V31AD V35AD V41AD V45AD V50AD V55AD V65AD V80AD V90AD V9X V13X V16X V19X V23X V25X V23XD V31XD V35XD V41XD V45XD V50XD V55XD V65XD V80XD V90XD V9CW V13CW V16CW V19CW V23CW V25CW V31CW V35CW V41CW V45CW V50CW V55CW V65CW V80CW V90CW V95CW kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg kg
Precision Air Conditioning -V Dimensional & Installation Data POSITIONING Standard Front Return (1) (2) The unit is designed for use with either ducted discharge or a plenum. If neither is used, protection from rotating parts in the form of a grille must be used on the discharge air outlet. Placing objects near an unguarded fan may cause injury.
Precision Air Conditioning -V Controls GENERAL GENERAL As standard the units are supplied with an connected to a 4x20 back-lit LCD display keypad. microprocessor controller The microprocessor controller can be linked together locally to provide run/standby operation. Windows based supervisor software is also available for local or remote networking. This modular approach provides great flexibility while at the same time reducing installation and maintenance costs.
Precision Air Conditioning -V Controls STANDARD FEATURES The default screen shows the unit status and room condition (°C/RH %) without the need for interrogation and an easy to navigate menu structure for further interrogation and adjustment. Password Protection The control system integrity can be maintained by restricting access with a password PIN number. CAUTION IMPORTANT: To change the PIN number; please contact Airedale at time of order with the preferred 4 digit number.
-V Precision Air Conditioning Controls GENERAL STANDARD FEATURES Duty/Standby Operation The controller enables units to operate in run/standby mode, with up to 6 units networked together, without the need for additional hardware or controllers. Standby units can be configured to start when the run unit has a critical alarm and/or a high/low return air temperature alarm. Duty Rotation Networked units can be configured to duty rotate, providing equal hours run of fans and compressors.
Precision Air Conditioning -V Sound Measurement Method MEASUREMENT OF SOUND DATA All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1 : 1995. SEMI HEMISPHERICAL Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source is in junction with 2 boundaries i.e. the floor and 1 wall.
Precision Air Conditioning -V Design Features & Information Thermostatic Expansion Whilst offering versatile control at the full design duty of the unit, TEVs do not automatically optimise themselves to all operating conditions. Therefore, if the Valves (TEV) refrigeration system is operating at 40% or 50% of full load, especially at a lower ambient temperature than that for which the valve was sized, the conventional TEV must have the design head pressure available to ensure good refrigerant control.
Precision Air Conditioning -V Design Features & Information CONDENSATE PUMP (OPTIONAL EXTRA) The following illustrates the TOTAL static (head) pressure available. The system horizontal pipe losses and vertical lift should be factored in when calculating the condensate pump performance.
Precision Air Conditioning -V Design Features & Information Controlled by the microprocessor, electronic expansion valves are unlike their conventional thermostatic counterparts in that they can modulate independently of controller to the suction line temperature. This unique feature allows the (Only available with raise the superheat set-point, in turn dropping the evaporating temperature to a point at Electronic Expansion Valves which considerable de-humidification takes place.
Precision Air Conditioning -V Design Features & Information HUMIDIFICATION In a humidifier with electrodes, steam is produced by passing a current between electrode plates to generate heat. The higher the current being passed between the electrodes, the greater the quantity of steam that is produced. To modulate the rate of steam production, this system varies the level of water within the cylinder, thereby increasing the immersion level of the electrodes and the current being passed between them.
Precision Air Conditioning -V AIR C OOLED (A & X) MOD ELS Performance Data - Air Cooled Models COOLING DUTIES A Models Cooling Capacity (1) V9A / CUS3 V13A / CUS4 V16A / CUS5 AIR COOLED V19A / CUS6 V23A / CUS7.5 V25A / CUS8.5 V23AD / CUS4 x 2 V31AD / CUS5 x 2 V35AD / CUS5.5 x 2 V41AD/ CUS6 x 2 V45AD / CUS6.5 x 2 V50AD / CUS7.5 x 2 V55AD / CUS8.
Precision Air Conditioning -V Performance Data - Air Cooled Models COOLING DUTIES X Models Cooling Capacity (1) Ambient V9X / C11 V13X / C15 V16X / C20 V19X / C25 V23X / C35 V25X / C45 V23XD / C15 x 2 V31XD / C20 x 2 V35XD / C25 x 2 V41XD / C25 x 2 V45XD / C35 x 2 V50XD / C35 x 2 V55XD / C45 x 2 V65XD / C45 x 2 V80XD / C45 x 2 V90XD / CS50 x 2 TC = Total Cooling (1) 25°C TC (kW) 9.2 9.4 9.8 11.5 12.0 12.3 13.9 14.4 15.0 19.5 20.1 20.6 22.6 23.5 24.4 27.8 28.8 29.9 21.8 22.6 23.5 26.1 27.4 28.6 29.
Precision Air Conditioning -V General Specification - Air Cooled Models AIR COOLED MECHANICAL DATA Single Circuit A Model - Matched Condensing Unit X Model - Matched Condenser Capacity Nom Cooling (Gross) - A (1) Nom Cooling (Gross) - X (1) Capacity Steps Fan Gain Dimensions - H x D x W (2) Weight - Machine - A (2) Weight - Machine - X (2) Construction - Material / Colour Evaporator Coating Cooling/Dehum Stages Fan & Motor (3) Motor / Filter Type Quantity / Motor Size Speed @ 50Pa ESP Maximum ESP Speed
Precision Air Conditioning -V General Specification - Air Cooled Models MECHANICAL DATA Single Circuit (1) (2) (3) (4) (5) kW kW kW mm kg kg kW rpm Pa rpm m³/s l in in in mm kW kg/hr V23A V23X CUS7.5 C35 V25A V25X CUS8.5 C45 16.6 20.0 25.2 18.5 21.8 26.9 1 1 1 1 x 0.44 1 x 0.88 1 x 1.
Precision Air Conditioning -V General Specification - Air Cooled Models MECHANICAL DATA Dual Circuit AIR COOLED A Model - Matched Condensing Unit X Model - Matched Condenser Capacity Nom Cooling (Gross) - A (1) Nom Cooling (Gross) - X (1) Capacity Steps Fan Gain Dimensions - H x D x W (2) Weight - Machine - A (2) Weight - Machine - X (2) Construction - Material / Colour Evaporator Cooling/Dehum Stages Fan & Motor Motor / Filter Type Quantity / Motor Size Speed @ 50Pa ESP Maximum ESP Speed @ Maximum ESP
Precision Air Conditioning -V General Specification - Air Cooled Models MECHANICAL DATA Dual Circuit A Model - Matched Condensing Unit X Model - Matched Condenser Capacity Nom Cooling (Gross) - A (1) Nom Cooling (Gross) - X (1) Capacity Steps Fan Gain Dimensions - H x D x W (2) Weight - Machine - A (2) Weight - Machine - X (2) Construction - Material / Colour Evaporator (1) (2) (3) (4) (5) kW kW kW mm kg kg (3) kW rpm Pa rpm m³/s l (4) in in in mm V55AD V55AX CUS8.
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA A Models AIR COOLED Single Circuit A Model - Matched Condensing Unit Unit Data (1) Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply (2) Control circuit Evaporator Fan - Per Fan Quantity / Motor Size Full Load Amps Locked Rotor Amps OPTIONAL EXTRAS Electric Heating Stage of Reheat Number of Elements Rating (Total) Current Per Phase Humidifier Capacity Rating Fu
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA A Models Dual Circuit (1) (2) (3) V23AD CUS4 x 2 A A A mm² V VAC 34.4 34.4 40 35 24 V31AD CUS5 x 2 V35AD CUS5.5 x 2 37.2 46.2 43.8 61.4 40 50 35 35 400V / 3PH + N / 50Hz 24 24 V41AD CUS6 x 2 V45AD CUS6.5 x 2 47.4 65.5 50 35 47.4 65.5 50 35 24 24 kW A A 1 x 1.5 3.39 21.0 1 x 3.0 6.18 43.3 1 x 4.0 8.12 60.9 2 x 2.2 4.64 32.5 2 x 2.2 4.64 32.5 kW A 2 6 15.0 21.8 2 6 15.0 21.8 2 6 15.0 21.8 2 6 15.
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA A Models AIR COOLED Dual Circuit A Model - Matched Condensing Unit Unit Data (1) Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply (2) Control circuit Evaporator Fan - Per Fan Quantity / Motor Size Full Load Amps Locked Rotor Amps OPTIONAL EXTRAS Electric Heating Stage of Reheat Number of Elements Rating (Total) Current Per Phase Humidifier Capacity Rating Full
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA X Models Single Circuit (1) (2) (3) V9X C11 V13X C15 V16X C20 V19X C25 V23X C35 V25X C45 27.1 64.1 32 35 36.9 93.6 40 35 39.9 40.9 97.1 130.9 40 50 35 35 400V / 3PH + N / 50Hz 24 24 38.2 123.7 50 35 41.4 146.9 50 35 24 24 24 24 kW A A 1 x 0.60 6.60 16.50 1 x 0.60 6.60 16.50 1 x 0.74 7.60 19.00 1 x 1.50 3.39 23.1 1 x 2.20 4.64 32.50 kW A A 1 x 2.9 6.4 43.39 1 x 4.1 8.12 61.8 1 x 4.5 1 x 5.9 8.
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA X Models AIR COOLED Dual Circuit X Model - Matched Condensers Unit Data Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply Control circuit Evaporator Fan - Per Fan Quantity / Motor Size Full Load Amps Locked Rotor Amps Compressor - Per Compressor Quantity / Motor Size Nominal Run Amps Locked Rotor Amps Type of Start Oil Sump Heater OPTIONAL EXTRAS Electric Heati
Precision Air Conditioning -V General Specification - Air Cooled Models ELECTRICAL DATA X Models Dual Circuit (1) (2) V50XD C35 x 2 V55XD C35 x 2 V65XD C45 x 2 V80XD C45 x 2 V90XD CS50 x 2 78.3 200.4 100 50 90.0 240.9 100 50 24 24 (1) (2) A A A mm² V VAC 50.6 136.1 63 35 24 57.7 61.7 163.2 165.6 63 80 35 35 400V / 3PH + N / 50Hz 24 24 kW A A 2 x 2.2 4.64 32.5 2 x 3.0 6.18 43.3 2 x 3.0 6.18 43.3 2 x 4.0 8.12 60.9 2 x 5.5 10.9 69.8 kW A A 2 x 6.8 12.5 98.0 2 x 8.5 14.5 120.0 2 x 11.
AIR COOLED 38 Sound Data - Air Cooled Models Front Return Air V9A V13A V16A V19A V23A V23AD V31AD Key: (1) (2) (3) Overall dB(A) 70 51 51 36 76 57 57 42 81 62 62 47 86 60 60 45 81 63 63 49 85 67 67 52 83 65 65 50 88 70 70 55 63 62 64 64 50 68 70 70 55 73 75 75 61 73 73 73 58 74 76 76 62 75 77 77 62 76 78 78 63 81 83 83 68 125 64 61 61 46 70 66 66 52 75 72 72 57 79 69 69 55 78 73 73 59 81 76 76 62 79 75 75 60 85 80 80 65 Frequency (Hz) dB 250 500 1000 2000 70 70 64 57 51 47 44 41 51 47 44 41 3
A Models Rear & Base Return Air (Base Return Air Available on Sizes 19 - 90 Only) V9A V13A V16A V19A V23A V25A Precision Air Conditioning Technical Manual : 6258867 F 07/2012 V23AD V31AD Key: (1) (2) (3) Sound Measurement DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m Overall dB(A) 70 58 48 34 76 64 54 39 81 69 59 45 79 68 58 43 81 73 62 48 85 77 65 51 83 74 64 49 88 80 69 54 63 62 64 62 48 68 70 68 53 73 75 73 5
AIR COOLED 40 Sound Data - Air Cooled Models Front Return Air V9X V13X V16X V19X V23X V23XD V31XD Key: (1) (2) (3) Overall dB(A) 70 64 64 49 76 70 70 56 81 70 70 56 86 70 70 56 82 71 71 56 85 76 76 62 84 74 74 59 89 75 75 60 63 62 64 64 50 68 70 70 55 73 75 75 61 73 73 73 58 74 77 77 62 75 78 78 63 76 78 78 63 81 83 83 68 125 64 61 61 46 70 66 66 52 75 72 72 57 79 69 69 55 78 73 73 59 81 76 76 62 79 75 75 60 85 80 80 65 Frequency (Hz) dB 250 500 1000 2000 70 70 64 57 52 53 54 56 52 53 54 56 3
X Models Rear Return Air(1) V9X V13X V16X V19X V23X V25X Precision Air Conditioning Technical Manual : 6258867 F 07/2012 V23XD V31XD Key: (1) (2) (3) (4) Sound Measurement DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m Overall dB(A) 70 58 51 36 76 64 58 43 81 69 61 46 79 68 60 46 82 73 63 49 85 77 67 53 84 74 65 50 89 80 69 55 63 62 64 62 48 68 70 68 53 73 75 73 59 71 73 71 56 74 78 72 57 75 78 73 58 76 79 73 59
Precision Air Conditioning -V Design Data - Air Cooled Models LOW PRESSURE HOT WATER (OPTIONAL EXTRA) 60 AIR COOLED Waterside Pressure Drop (kPa) 65D – 90D 50 40 19 - 25 30 41D – 55D 20 9 - 16 23D - 35D 10 Includes coil, 3 port valve and pipework. To calculate 3 port valve pressure drop DP valve = æQ ö ç ÷ èMø 2 where DP = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M = M Values Model Sizes LPHW 42 9 - 90 0.
Precision Air Conditioning -V Design Data - Air Cooled Models SYSTEM PIPEWORK SCHEMATIC Design should be in accordance with good refrigeration practice to ensure good oil return to the compressor under all normal operating conditions to prolong the life of your unit.
Precision Air Conditioning -V Design Data - Air Cooled Models SYSTEM PIPEWORK SCHEMATIC KEY: LP AIR COOLED HP LT ST TP TEV EEV Low Pressure Switch High Pressure Switch Liquid Line Pressure Transducer Suction Line Pressure Transducer Suction Line Temperature Probe Thermostatic Expansion Valve Electronic Expansion valve Suction Line Liquid Line Schrader Point Sight Glass (Supplied Loose) Filter Drier (Supplied Loose) Shut Off Valve - Condensing Units Condensing Unit Fan & Motor Condensing Coil Compressor
Precision Air Conditioning -V Design Data - Air Cooled Models REFRIGERANT PIPE SIZING GUIDE Pipe lengths calculated for Indoor unit with standard Outdoor unit match. For Outdoor unit connections sizes, please refer to relevant Installation Manual. REFRIGERANT PIPEWORK SIZING GUIDE Indoor CUS3 C11 CUS4 C15 CUS5 C20 CUS6 C25 CUS7.5 C35 CUS8.5 C45 CUS4 x 2 C15 x 2 CUS5 x 2 C20 x 2 CUS5.5 x 2 C25 x 2 CUS6 x 2 C25 x 2 CUS6.5 x 2 C35 x 2 CUS7.5 x 2 C35 x 2 CUS8.
Precision Air Conditioning -V Design Data - Air Cooled Models REFRIGERANT CHARGING GUIDE The following information can be used to estimate the refrigerant quantity required in a split system installation. Unit Refrigerant Charge (Kg/Circuit) The following table shows the refrigerant charge / circuit for the indoor and outdoor units.
Precision Air Conditioning -V Design Data - Air Cooled Models REFRIGERANT CHARGING GUIDE To Calculate the Liquid Line Refrigerant Charge (kg) The liquid line refrigerant charge can be calculated using the following equation: LR = L x m Where: LR = L = m = Total Liquid Line Refrigerant charge (kg) Length of Interconnecting pipework (metres) Liquid Line Refrigerant charge / metre. Refer to Liquid Line Refrigerant Charge (kg/m) in this section.
Precision Air Conditioning -V Design Data - Air Cooled Models INTERCONNECTING WIRING - A MODELS Head Pressure Control - Standard (Stand Alone) Sizes 9 - 80AD No Sub Fusing (1) INDOOR UNIT L1 L2 L3 N PE ¡ ç ç ç ¡ Separate Mains Incoming Supply ç 400V / 3PH + N / 50Hz ¡ ç 502 545 ¡ è ¡ ç 514 500 ¡ ¡ è è ¡ ¡ è ¡ Separate Mains è Incoming Supply è 400V / 3PH + N / 50Hz è ¡ ¡ è ¡ è ¡ To Outdoor Unit 1 Trip Terminals ¡ L1 L2 L3 N PE ç ¡ 502 589 è è ¡ ¡ 576 577 è ¡ ¡ L1 L2 L3
Precision Air Conditioning -V Design Data - Air Cooled Models INTERCONNECTING WIRING - A MODELS Head Pressure Control - Standard (Stand Alone) Model V90AD No Sub Fusing (1) INDOOR UNIT L1 L2 L3 N PE ¡ ¡ ¡ ¡ ¡ ç ç ç ç ç 502 545 ¡ ¡ è ç 514 500 ¡ ¡ 502 546 516 500 è è ¡ ¡ ¡ ¡ ¡ L1 L2 L3 N PE To Outdoor CCT 1 Trip Terminals è ç ¡ ¡ 561 562 è è Cooling Signal to Outdoor CCT 1 è è ¡ ¡ 559 558 ¡ ¡ è ç To Outdoor CCT 2 Trip Terminals è ç ¡ ¡ 561 563 ¡ ¡ è è Cooling Signal to Outdo
Precision Air Conditioning -V Design Data - Air Cooled Models INTERCONNECTING WIRING - A MODELS Head Pressure Control - Optional Intelligent Head Pressure Control(1) INDOOR UNIT CIRCUIT 1 L1 L2 L3 N PE ¡ ¡ ¡ ç ç ç ¡ ç ¡ ç 502 545 ¡ è ¡ ç 514 500 ¡ ¡ è 500 833 ¡ è ¡ è è Separate Mains Incoming Supply 400V / 3PH + N / 50Hz ¡ Separate Mains è ¡ Incoming Supply è ¡ 400V / 3PH + N / 50Hz è ¡ To Outdoor Unit 1 Trip Terminals Cooling Signal to Outdoor Unit 1 è Fan Speed Control Signa
Precision Air Conditioning -V Design Data - Air Cooled Models INTERCONNECTING WIRING - X MODELS Head Pressure Control - Standard (Stand Alone) No Sub Fusing INDOOR UNIT CIRCUIT 1 L1 L2 L3 N PE ¡ ¡ ¡ ¡ ¡ ç ç ç ç ç Separate Mains Incoming Supply 400V / 3PH + N / 50Hz CIRCUIT 2 With Sub Fusing INDOOR UNIT CIRCUIT 1 CIRCUIT 2 C1 N PE ¡ è C2 N PE ¡ è ¡ è ¡ è ¡ ¡ ¡ L1 N PE OUTDOOR 1 Separate Mains è Incoming Supply è 230V/ 1PH +N / 50Hz è ¡ ¡ ¡ L1 N PE OUTDOOR 2 è ¡ è ¡ OUTDOOR 1 è ¡
Precision Air Conditioning -V Performance Data - Chilled Water Models COOLING DUTIES Cooling Capacity (1) V9CW V13CW V16CW V19CW V23CW V25CW V31CW V35CW V41CW V45CW V50CW CHILLED WATER V55CW V65CW V80CW V90CW V95CW TC = Total Cooling (1) (2) (3) Chilled Water Inlet/Outlet °C Air On ºC DB / % RH 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45 26 / 40 22 / 50 24 / 45
Precision Air Conditioning -V General Specification - Chilled Water Models MECHANICAL DATA V9CW (1) (2) (3) (4) V13CW V16CW V19CW (1) (2) (2) kW kW mm kg (3) kW rpm Pa rpm m³/s mm mm 8.9 11.4 13.6 19.8 1 x 0.35 1 x 0.35 1 x 0.35 1 x 0.
Precision Air Conditioning -V General Specification - Chilled Water Models MECHANICAL DATA CHILLED WATER V23CW Capacity Nom Cooling (Gross) Fan Gain Dimensions - H x D x W Weight - Machine Construction - Material / Colour Cooling Coil Coating Cooling/Dehum Stages Fan & Motor Motor / Filter Type Quantity / Motor Size Speed @ 50Pa ESP Maximum ESP Speed @ Maximum ESP Nominal Airflow Connections Inlet/Outlet Condensate Drain Hose Filtration Quantity OPTIONAL EXTRAS Electric Heating Humidifier Feed/Drain HE
Precision Air Conditioning -V General Specification - Chilled Water Models MECHANICAL DATA V41CW (1) (2) (3) (4) V45CW V50CW V55CW (1) (2) (2) kW kW mm kg (3) kW rpm Pa rpm m³/s mm mm 45.8 50.0 57.8 68.0 2 x 1.29 2 x 1.29 2 x 1.29 2 x 1.
Precision Air Conditioning -V General Specification - Chilled Water Models MECHANICAL DATA CHILLED WATER V65CW Capacity Nom Cooling (Gross) Fan Gain Dimensions - H x D x W Weight - Machine Construction - Material / Colour Cooling Coil Coating Cooling/Dehum Stages Fan & Motor Motor / Filter Type Quantity / Motor Size Speed @ 50Pa ESP Maximum ESP Speed @ Maximum ESP Nominal Airflow Connections Inlet/Outlet Condensate Drain Hose Filtration Quantity OPTIONAL EXTRAS Electric Heating Humidifier Feed/Drain HE
Precision Air Conditioning -V General Specification - Chilled Water Models ELECTRICAL DATA V9CW (1) Unit Data Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply Control circuit Evaporator Fan - Per Fan Quantity / Motor Size Full Load Amps Locked Rotor Amps OPTIONAL EXTRAS Electric Heating Stage of Reheat Number of Elements Rating (Total) Current Per Phase Humidifier Capacity Rating Full Load Amps HE & Pre Filter Motor Selection Quantity / Motor Size
Precision Air Conditioning -V General Specification - Chilled Water Models ELECTRICAL DATA CHILLED WATER V41CW Unit Data Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply Control circuit Evaporator Fan - Per Fan Quantity / Motor Size Full Load Amps Locked Rotor Amps OPTIONAL EXTRAS Electric Heating Stage of Reheat Number of Elements Rating (Total) Current Per Phase Humidifier Capacity Rating Full Load Amps HE & Pre Filter Motor Selection Quantity
Front Return Air V9CW V13CW V16CW V19CW V23CW V25CW Precision Air Conditioninge Technical Manual : 6258867 F 07/2012 V31CW V35CW Key: (1) (2) (3) Sound Measurement DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m DA RA CB S @ 3m Overall dB(A) 70 51 51 36 76 57 57 42 81 62 62 47 86 60 60 45 81 63 63 49 85 67 67 52 83 65 65 50 92 73 73 59 63 62 64 64 50 68 70 70 55 73 75 75 61 73 73 73 58 74 76 76 62 75 77 77 62 76 78 78 63 78 80 80
CHILLED WATER 60 Sound Data - Chilled Water Models V9CW V13CW V16CW V19CW V23CW V31CW V35CW Key: (1) (2) (3) Overall dB(A) 70 58 48 34 76 64 54 39 81 69 59 45 79 68 58 43 81 73 62 48 85 77 65 51 83 74 64 49 92 83 72 57 63 62 64 62 48 68 70 68 53 73 75 73 59 71 73 71 56 74 78 72 57 75 78 72 58 76 79 73 59 78 82 76 61 125 64 63 57 42 70 69 63 48 75 74 68 53 73 73 67 52 78 79 72 57 81 82 75 60 79 81 73 59 87 88 81 66 Frequency (Hz) dB 250 500 1000 2000 70 70 64 57 58 54 53 49 51 45 40 35 37 31 2
Precision Air Conditioning -V Design Data - Chilled Water Models WATERSIDE PRESSURE DROP (KPA) 9 - 16 Waterside Pressure Drop (kPa) 200 19 - 25 31 35 41 - 45 50 - 55 65 80 - 90 175 95 150 125 100 75 50 25 9 8 7 6 5 4 3 2 1 0 0 Waterflow (l/s) LOW PRESSURE HOT WATER (OPTIONAL EXTRA) 60 40 CHILLED WATER Waterside Pressure Drop (kPa) 65D – 95D 50 19 - 25 30 41D – 55D 20 9 - 16 23D - 35D 10 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.
Precision Air Conditioning -V Design Data - Chilled Water Models SYSTEM PIPEWORK SCHEMATIC Design should be in accordance with good refrigeration practice to ensure good oil return to the compressor under all normal operating conditions to prolong the life of your unit.
Precision Air Conditioning -V Design Data - Chilled Water Models ETHYLENE GLYCOL CORRECTION FACTORS For conditions outside those quoted, please refer to Airedale. The Use of Glycol Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be exposed to freezing temperatures. The effect of glycol in the system has a direct effect upon the Cooling Duty, the Design Flow Rate and the unit Pressure Drop.
Precision Air Conditioning -V Design Data - Chilled Water Models INTERCONNECTING WIRING (1) INDOOR UNIT (1) 64 ç ç ç ¡ ç ¡ ç Mains Incoming Supply 400V / 3PH + N / 50Hz ¡ ¡ ¡ ¡ ¡ ¡ è ç è è ç è Volt Free Alarm N/O Volt Free Alarm Common Volt Free Alarm N/C Volt Free Alarm N/O Volt Free Alarm Common Volt Free Alarm N/C 502 583 ¡ ¡ è Fire Shutdown input Healthy in N/C Condition INDOOR UNIT 502 522 ¡ è ¡ ç INDOOR UNIT Rx-/TxRx+/Tx+ GND ç ¡ çè ¡ çè ¡ çè Common Alarm Critical Alarm R
Precision Air Conditioning -V OUTDOOR UNIT (CUS & C) General Description UNIT IDENTIFICATION AIR COOLED CONDENSING UNITS AIR COOLED CONDENSERS CUS Condensing Units C..
-V Precision Air Conditioning General Description STANDARD FEATURES Fan & Motor Assembly Axial flow fan assembly with low noise blades. The motor has inbuilt thermal overload protection and the assembly is supplied complete with a finger guard for protection. The external rotor motor allows the use of a low power output single phase speed controllable motor to power the fan. CUS 3 - 4 Standard air discharge is horizontal. CUS 5 - 30D Standard air discharge is vertical.
Precision Air Conditioning -V General Description STANDARD FEATURES Mains Electric Isolator (CUS 3 - 12 & C 11 - 50) A weatherproof mains isolator is fitted to ensure complete unit isolation of the electrical panel during adjustment and maintenance.
-V Precision Air Conditioning General Description OPTIONAL EXTRAS Wall Mounting Brackets To allow wall mounting a bracket and fixing kit can be supplied. (CUS 3 - 4) Short Case Axial Fans (C 11 - 50) Short case axial fans can be supplied for indoor installations where discharge air requires to be ducted to an outdoor location. The fans will meet duty plus 75Pa of external static pressure. Refer to the Standard Features in this section for standard operating features.
Precision Air Conditioning -V Dimensional & Installation Data - Condensing Units CUS 3 - 30D DIMENSIONS / POSITIONING / WEIGHTS Refer to the relevant installation manual for full lifting and positioning information. IMPORTANT Unit diagrams can be supplied on request.
Precision Air Conditioning -V Dimensional & Installation Data - Condensing Units CUS 3 - 30D DIMENSIONS / POSITIONING / WEIGHTS Refer to the relevant installation manual for full lifting and positioning information. IMPORTANT Unit diagrams can be supplied on request. CUS 8.5 - 12 (mm) 1800 (2) (1) (1) (1) (1) 500 (2) 500 (2) B (4) D (1) (2) (3) (4) E A G C F Airflow Minimum Clearances 12.7mm Fixing Slots x 4 Incoming Services: Connections to left hand side of unit compressor compartment.
Precision Air Conditioning -V Dimensional & Installation Data - Condensers C 11 - 50 DIMENSIONS / WEIGHTS / POSITIONING Refer to the relevant installation manual for full lifting and positioning information. IMPORTANT Unit diagrams can be supplied on request.
Precision Air Conditioning -V General Specification - Condensing Units CUS 3 - 30D MECHANICAL DATA OUTDOOR UNIT Capacity Nom Cooling Capacity Nom Input Capacity Steps Dimensions Height Width Depth Weights Machine Operating Construction Material/Colour Condenser Quantity Total Face Area Nominal Airflow Discharge Fan & Motor Quantity Diameter Maximum Speed Compressor Quantity Oil Charge Volume (Total) Refrigeration Refrigerant Type Refrigerant Charge Coil Volume Connections Liquid Line Suction Line Hot Ga
Precision Air Conditioning -V General Specification - Condensing Units CUS3 - CUS30D ELECTRICAL DATA Unit Data Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Size Mains Supply Control Circuit Fan - Per Fan Motor Size Full Load Amps Locked Rotor Amps Compressor - Per Compressor Nominal Run Amps Locked Rotor Amps Motor Size Oil Sump Heater Rating Type of Start (1) Unit Data Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Size Max Mains Incoming Cable Si
Precision Air Conditioning -V General Specification - Condensers C 11 - 50 MECHANICAL DATA Total Heat of Rejection Dimensions - Horizontal Height Depth Width Dimensions - Vertical Height Depth Width Weight Machine Construction Material/Colour Condenser Quantity Total Face Area Nominal Airflow Discharge Fan & Motor Quantity Diameter Maximum Speed Refrigeration Refrigerant Type Holding Charge Coil Volume Refrigerant Charge Connections Liquid Line - Sweat Discharge Line - Sweat OPTIONAL EXTRAS Short Case Axi
Precision Air Conditioning -V Sound Data - Condensing Units CUS 3 - 30D METHOD OF SOUND MEASUREMENT Measurement of Sound Data All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated sound intensity meter in accordance with BS EN ISO9614 Part 1 : 1995. All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1 : 1995.
Precision Air Conditioning -V Sound Data - Condensers C 11 - 50 METHOD OF SOUND MEASUREMENT Measurement of Sound Data All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated sound intensity meter in accordance with BS EN ISO9614 Part 1 : 1995. All Sound Power Levels quoted are calculated from measured sound intensity according BS EN ISO9614 Part 1 : 1995.
Precision Air Conditioning -V Notes: Precision Air Conditioning Technical Manual : 6258867 F 07/2012 77
W here to Fin d U s Head Office: Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY United Kingdom Tel: Fax: e-mail: website: +44 (0) 113 239 1000 +44 (0) 113 250 7219 enquiries@airedale.com www.airedale.