Technical data

-
V
Precision Air Conditioning
Precision Air Conditioning
10
Technical Manual : 6258867 F 07/2012
General Description
OPTIONAL EXTRAS - GENERAL
Conductivity is a measure of the ability of water to pass an electric current, measured in
micro Siemens / centimetre (mS/cm). 3 different cylinders are available which correspond
to the supply water conductivity.
Matching the correct cylinder type with the conductivity of the supply water ensures
optimum performance and increases the life span of the cylinder.
1 Low Conductivity (Soft Water) - 100 to 350 mS/cm
2 Standard Conductivity (Moderate/Hard Water) - 350 to 750 mS/cm
3 High Conductivity (Very Hard Water) - 750 to 1250 mS/cm
Water Conductivity &
Cylinder Type
As standard the humidifier is fitted with the standard conductivity cylinder which covers
the majority of water supplies. Where the water conductivity is known, please specify at
order. For further details please contact Airedale.
Cleanable Humidifier
Cylinder
The humidifier can be fitted with a take apart cylinder enabling the bottle and the
electrodes to be cleaned and reused. The cylinder can typically be cleaned 3 times before
replacing either the electrodes or the entire cylinder.
The cleanable humidifier cylinders are available in 8kg and 15kg bottle sizes with
standard or high conductivity levels only. For further details please contact Airedale.
CAUTION
The supply water pressure to the humidifier assembly must be between 1 - 8 Barg.
Heating Options
Electric Heating
Multi-stage finned electric heating elements complete with auto and manual reset
overheat cut-out protection, phase balanced for increased efficiency.
or
A low pressure hot water coil constructed of refrigeration quality copper tube and
mechanically bonded aluminium fins can be factory fitted.
Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly.
Low Pressure Hot Water
Proportional heating control is provided by a factory fitted 3 port, raise/lower type,
modulating valve.
GENERAL