Technical data

-
V
Precision Air Conditioning
Precision Air Conditioning
36
Technical Manual : 6258867 F 07/2012
General Specification - Air Cooled Models
ELECTRICAL DATA
X Models
Dual Circuit
V23XD
V31XD
V35XD
V41XD
V45XD
X Model - Matched Condensers C15 x 2
C20 x 2
C25 x 2
C25 x 2
C35 x 2
Unit Data
(1)
Nominal Run Amps A 34.4
37.2
46.2
47.6
51.5
Maximum Start Amps A 87.7
94.0
104.0
137.6
137.5
Recommended Mains Fuse Size A 40
40
50
63
63
Max Mains Incoming Cable Size mm² 35
35
35
35
35
Mains Supply (2) V 400V / 3PH + N / 50Hz
Control circuit VAC 24
24
24
24
24
Evaporator Fan - Per Fan
Quantity / Motor Size kW 1 x 1.5
1 x 3.0
1 x 4.0
2 x 2.2
2 x 2.2
Full Load Amps A 3.39
6.18
8.12
4.64
4.64
Locked Rotor Amps A 21.0
43.3
60.9
32.5
32.5
Compressor - Per Compressor
Quantity / Motor Size kW 2 x 4.1
2 x 4.5
2 x 5.3
2 x 5.9
2 x 6.7
Nominal Run Amps A 8.12
8.3
9.1
11.0
12.9
Locked Rotor Amps A 61.8
65.5
70.5
101.0
99.0
Type of Start Direct On Line
Oil Sump Heater W N/A
N/A
N/A
N/A
N/A
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2
2
2
2
2
Number of Elements 6
6
6
6
6
Rating (Total) kW 15.0
15.0
15.0
15.0
15.0
Current Per Phase A 21.8
21.8
21.8
21.8
21.8
Humidifier
Capacity kg 1.6 - 8.00
1.6 - 8.00
1.6 - 8.00
3.0 - 15.00
3.0 - 15.00
Rating kW 6.00
6.00
6.00
6.00
11.25
Full Load Amps A 8.70
8.70
8.70
8.70
15.80
HE & Pre Filter Motor Selection
Quantity / Motor Size
kW 1 x 2.2
1 x 4.0
N/A
2 x 2.2
2 x 3.0
Full Load Amps A 4.64
8.12
N/A
4.64
6.18
Locked Rotor Amps A 32.5
60.9
N/A
32.5
43.3
Larger Fan Motor - Per Fan
Quantity / Motor Size
kW 1 x 2.2
1 x 4.0
N/A
2 x 3.0
2 x 3.0
Full Load Amps A 4.64
8.12
N/A
6.18
6.18
Locked Rotor Amps A 32.5
60.9
N/A
43.3
43.3
Next Larger Fan Motor - Per Fan
Quantity / Motor Size
kW 1 x 3.0
N/A
N/A
2 x 4.0
2 x 4.0
Full Load Amps A 6.18
N/A
N/A
8.12
8.12
Locked Rotor Amps A 43.3
N/A
N/A
60.9
60.9
(1) Values given for full function units (incl. electric heating and humidification) at ARI conditions with EFF1 (IE2) fan motors and standard filters, for
optional data, please contact Airedale.
(2) Values given for non sub fused products, for sub-fused values, please contact Airedale.
AIR COOLED