Manual

ULTIMA COMPACT
Chillers
26
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Performance Data
SOUND DATA
Global Chiller Sound Level
Super Quiet - SSQ & DSQ Models
Sound Measurement
Overall
dB(A)
Frequency (Hz) dB
63
125
250
500
1000
2000
4000
UCC30SSQ-1/1
UCC30DSQ-1/1
Power
73
76
70
69
69
69
66
58
Pressure
@ 10m
41
44
38
37
37
37
34
26
UCC40SSQ-1/1
UCC40DSQ-1/1
Power
73
76
70
69
69
69
66
58
Pressure
@ 10m
41
44
38
37
37
37
34
26
UCC50SSQ-2/1
UCC50DSQ-2/1
Power
74
80
76
72
72
70
64
58
Pressure
@ 10m
42
48
44
40
40
38
32
26
UCC60SSQ-2/1
UCC60DSQ-2/1
Power
74
80
76
72
72
70
64
58
Pressure
@ 10m
42
48
44
40
40
38
32
26
UCC70SSQ-2/1
UCC70DSQ-2/1
Power
74
80
76
72
72
70
64
58
Pressure
@ 10m
42
48
44
40
40
38
32
26
UCC75DSQ-2/1
Power
73
76
80
76
67
68
62
53
Pressure
@ 10m
41
44
48
44
35
36
30
21
UCC80SSQ-2/1
UCC80DSQ-2/1
Power
75
74
73
73
72
71
68
61
Pressure
@ 10m
43
42
41
41
40
39
36
29
UCC100DSQ-3/1
Power
75
81
84
78
69
70
64
56
Pressure
@ 10m
43
49
52
46
37
38
32
24
UCC110DSQ-4/2
Power
77
82
84
76
74
73
67
61
Pressure
@ 10m
45
50
52
44
42
41
35
29
UCC125DSQ-4/1
Power
77
76
84
83
71
70
65
58
Pressure
@ 10m
45
44
52
51
39
38
33
26
UCC130DSQ-6/2
Power
80
80
84
82
76
75
69
63
Pressure
@ 10m
47
48
52
50
44
43
37
31
UCC150DSQ-4/1
Power
78
77
85
83
72
71
66
58
Pressure
@ 10m
46
45
53
51
40
39
34
26
UCC160DSQ-6/2
Power
80
80
84
82
76
75
69
63
Pressure
@ 10m
47
48
52
50
44
43
37
31
UCC180DSQ-6/2
Power
80
83
88
82
77
75
69
64
Pressure
@ 10m
48
51
56
50
45
43
37
32
UCC200DSQ-6/2
Power
81
81
87
85
78
75
69
64
Pressure
@ 10m
49
49
55
53
46
43
37
32
UCC225DSQ-8/2
Power
82
82
88
85
78
76
70
64
Pressure
@ 10m
50
50
56
53
46
44
38
32
UCC250DSQ-8/2
Power
82
82
88
85
78
76
70
64
Pressure
@ 10m
50
50
56
53
46
44
38
32
UCC275DSQ-10/2
Power
83
79
85
82
81
77
75
70
Pressure
@ 10m
51
47
53
50
49
45
43
38
UCC300DSQ-12/2
Power
83
80
85
83
81
77
75
70
Pressure
@ 10m
51
48
53
51
49
45
43
38
UCC330DSQ-14/2
Power
84
81
87
84
82
78
74
68
Pressure
@ 10m
51
48
54
51
49
45
41
35
UCC360DSQ-14/2
Power
84
81
87
84
83
79
74
67
Pressure
@ 10m
51
48
54
51
50
46
41
34
UCC400DSQ-16/2
Power
85
82
88
85
83
79
76
71
Pressure
@ 10m
52
49
55
52
50
46
43
38
UCC450DSQ-16/2
Power
86
82
88
85
84
80
78
72
Pressure
@ 10m
53
49
55
52
51
47
45
39
1
dB(A) is the overall sound level, measured on the A scale.
2
All sound data measured at nominal conditions: Water in/out 12/7°C at 30°C ambient.
3
Figures based on standard unit, for units fitted with optional pump packages, please contact Airedale.
The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If
the equipment is placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for
each side added.