Installation Data
WATER SYSTEM GENERAL SPECIFICATION
UCFC75D-2/1
UCFC100D-2/1
UCFC125D-3/1
UCFC150D-3/1
UCFC160D-6/2
Connections
Water Inlet / Outlet
PN16 DN65
PN16 DN65
PN16 DN65
PN16 DN65
PN16 DN80
Water Drain / Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(1)
l
377
469
419
727
717
Max. System Press
Bar
10
10
10
10
10
OPTIONAL EXTRAS - ALL MODELS
Water Pump
(2) & (3)
In Line Pump
Single Head or Run/Standby
Nom External Head - Standard
kPa
143
109
145
122
187
Nom External Head - Larger
kPa
184
150
190
185
254
Twin Head
Nom External Head - Standard
kPa
100
82
88
89
184
Nom External Head - Larger
kPa
146
125
133
152
254
UCFC180D-6/2
UCFC200D-6/2
UCFC225D-6/2
UCFC250D-8/2
UCFC275D-8/2
Connections
Water Inlet / Outlet
PN16 DN80
PN16 DN80
PN16 DN80
PN16 DN80
PN16 DN100
Water Drain / Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(1)
l
645
715
811
1156
1004
Max. System Press
Bar
10
10
10
10
10
OPTIONAL EXTRAS - ALL MODELS
Water Pump
(2) & (3)
In Line Pump
Single Head or Run/Standby
Nom External Head - Standard
kPa
169
160
151
136
163
Nom External Head - Larger
kPa
236
226
217
201
228
Twin Head
Nom External Head - Standard
kPa
166
156
147
130
157
Nom External Head - Larger
kPa
235
225
215
199
225
UCFC300D-8/2
UCFC330D-10/2
UCFC360D-10/2
UCFC400D-12/2
UCFC450D-12/2
Connections
Water Inlet / Outlet
PN16 DN100
PN16 DN100
PN16 DN100
PN16 DN100
PN16 DN100
Water Drain / Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(1)
l
1374
1168
1122
1337
1395
Max. System Press
Bar
10
10
10
10
10
OPTIONAL EXTRAS - ALL MODELS
Water Pump
(2) & (3)
In Line Pump
Single Head or Run/Standby
Nom External Head - Standard
kPa
151
138
121
125
108
Nom External Head - Larger
kPa
218
206
190
196
182
Twin Head
Nom External Head - Standard
kPa
144
129
110
109
87
Nom External Head - Larger
kPa
213
198
180
181
161
(1)
For minimum system volume calculation method, refer to Technical Manual.
(2)
Based on 12/7°C water temperature and 35°C ambient with a 20% Ethylene Glycol Water Concentration.
(3)
Based on D Model, for DQ & DSQ details, please contact Airedale.