Specifications
2008 Residential Appendices  RA3-14 
Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols 
  Actual Superheat = Tsuction, – Tevaporator, sat. 
2.  Determine the Target Superheat using Table RA3.2-2 using the return air wet-bulb temperature (T
return, 
wb
) and condenser air dry-bulb temperature (Tcondenser, db). 
3.  If a dash mark is read from Table RA3.2-2, the target superheat is l
ess than 5°F. Note that a valid 
refrigerant charge verification test cannot be performed under these conditions. The usual 
reason for a target superheat determination of less than 5°F is that outdoor conditions are too hot and 
dry. One of the following is needed so a target superheat value can be obtained from Table RA3.2-2 
either 1
) turn on the space heating system and/or open the windows to warm up indoor temperature; or 
2) retest at another time when conditions are different. Repeat the measurement procedure as 
necessary to establish the target superheat. Allow system to stabilize for 15 minutes before the final 
measurements are taken. 
4.  Calculate the difference between actual superheat and target superheat (Actual Superheat - Target 
Superheat). 
5.  In order to allow for inevitable differences in measurements, the Pass/Fail criteria are different for the 
Installer and the HERS Rater. 
For the Installer, if the difference is between minus 5°F and plus 5°F, then the system passes the 
required refrigerant charge criterion. 
For the HERS Rater inspecting the system, if the difference is between minus 6°F and plus 6°F, then 
the system passes the required refrigerant charge criterion. 
6.  For the Installer, if the difference is greater than plus 5°F, then the system does not pass the required 
refrigerant charge criterion and the Installer shall add refrigerant. Adjust refrigerant charge and check 
the measurements as many times as necessary to pass the test. After the final adjustment has been 
made, allow the system to run 15 minutes before completing the final measurement procedure. 
7. For the Installer, if the difference is between minus 5°F and minus100°F, then the system does not pass 
the required refrigerant charge criterion, the Installer shall remove refrigerant. Adjust refrigerant charge 
and check the measurements as many times as necessary to pass the test. After the final adjustment 
has been made, allow the system to run 15 minutes before completing the final measurement 
procedure. 
RA3.2.2.6.2 Variable Me
tering Device Calculations 
The Subcooling Charging Method is used only for systems equipped with variable metering devices. These 
include Thermostatic Expansion Valves (TXV) and Electronic Expansion Valves (EXV). Since variable metering 
devices are constant superheat valves, measuring the superheat determines whether they are working 
properly. 
1.  Calculate Actual Subcooling as the condenser saturation temperature minus the liquid line 
temperature. Actual Subcooling = T
condenser, sat – Tliquid. 
2.  Determine the Target Subcooling specified by the manufacturer. 
3.  Calculate the difference between actual subcooling and target subcooling (Actual Subcooling - Target 
Subcooling 
4.  In order to allow for inevitable differences in measurements, the Pass/Fail criteria are different for the 
Installer and the HERS Rater. 
  For the Installer, If the difference is between minus 3°F and plus 3°F, then the system passes the 
required refrigerant charge criterion. 
  For the HERS Rater inspecting the system, if the difference is between minus 4°F and plus 4°F, then 
the system passes the required refrigerant charge criterion 
5.  For the Installer, if the difference is greater than plus 3°F, then the system does not pass the required 
refrigerant charge criterion and the Installer shall remove refrigerant. Adjust refrigerant charge and 










