Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols
This location can be in any one of the four sides of the coil box/supply plenum.
This location shall have a 1/4" (6 mm) diameter hole (HSPP) or a permanently affixed static pressure
probe (PSPP). The location shall be labeled "Title 24 – Supply Pressure Measurement Location" in at
least 12-point type.
RA3.3.1.2 Fan Flow Measurements
All measu
rements of distribution fan flows shall be made with measurement systems (i.e., sensor plus
data acquisition system) having an accuracy of ± 7% reading or ± 5 cfm whichever is greater.
RA3.3.1.3 Watt Measurements
All measu
rements of air handler watt draws shall be made with true power measurement systems (i.e.,
sensor plus data acquisition system) having an accuracy of ± 2% reading or ± 10 watts whichever is
greater.
RA3.3.2 Apparatus
RA3.3.2.1 System Fan Flows
HVAC sy
stem fan flow shall be measured using one of the following methods.
RA3.3.2.1.1 Plenum Pr
essure Matching Measurement
Air Flow
Evaporator Coil
A
B
.75B
.75A
1/4 inch diameter hole
or permanent static
pressure probe