Specifications
2008 Residential Appendices  RA3-25 
Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols 
RA3.4  Procedures for Verifying the Presence of a Charge Indicator Display or High 
Energy Efficiency Ratio Equipment 
RA3.4.1  Purpose and Scope 
The purpose of these procedures is to verify that residential space cooling systems and heat pumps have 
the required components to achieve the energy efficiency claimed in the compliance documents. The 
procedures only apply when a Charge Indicator Display (CID) is specified for split system equipment or 
an EER higher than the default is claimed. For dwelling units with multiple systems, the procedures shall 
be applied to each system separately. 
The installer shall certify to the builder, building official and HERS rater that he/she has installed all the 
correct components. 
The reference method algorithms adjust (improve) the efficiency of air conditioners and heat pumps when 
field verification indicates the specified components are installed. Table RA3.4-1 summarizes the 
algorithms that are affected. 
Table RA3.4-1 – SUMMARY OF FIELD VERIFICATION 
Field Verification Check   
Description  Standard Design Value 
Proposed Design 
Default 
Value  Procedure 
Presence of a CID   
F
CID 
takes on a value 
of 0.96 when the 
system has a verified 
CID or has been 
diagnostically tested 
for the correct 
refrigerant charge. 
Otherwise, F
CID
 has a 
value of 0.90. 
Split systems are 
assumed to have 
refrigerant charge 
testing or a CID, when 
required by Package D. 
No CID or 
refrigerant 
charge 
testing. 
Section 
RA3.4.2 
Presence of a matched High 
Efficiency Compressor Unit, 
Evaporator Coil, Refrigerant 
Metering Device, and 
(where specified) Air 
Handling Unit and/or Time 
Delay Relay. 
The EER is the 
Energy Efficiency 
Ratio at 95 F outdoors 
specified according to 
ARI procedures for 
the matched 
combination 
Systems are assumed 
to have the default EER 
based on SEER, 
Default 
EER 
Sections 
RA3.4.3 
and 
RA3.4.4 
RA3.4.2  CID Verification Procedure 
The procedure shall consist of visual verification that the CID is installed on the system. 
RA3.4.3  Time Delay Relay Verification Procedure 
Whe
n a high EER system specification includes a time delay relay, the installation of the time delay relay 
shall be verified. 
The procedure shall be: 
1)  Turn the thermostat down until the compressor and indoor fan are both running. 
2)  Turn the thermostat up so the compressor stops running. 
3)  Verify that the indoor fan continues to run for at least 30 seconds. 










