Installation Manual

Specifications subject to change without notice.
440 01 4900 00 31
Table9–Cooling
4
and Heating Air Delivery -- CFM (Bottom Return
5
with Filter)
( S W 1 --- 5 a n d S W 4 --- 3 s e t t o O F F, e x c e p t a s i n d i c a t e d . S e e n o t e s 1 a n d 2 . )
Unit Size: 0601714 Clg/CF Switch settings External Static Pressure (ESP)
Clg Switches S W 2 --- 3 S W 2 --- 2 S W 2 --- 1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
CF Switches S W 3 --- 3 S W 3 --- 2 S W 3 --- 1
L o w --- C l g D e f a u l t : OFF OFF OFF 565 565 555 540 530 See note 4
Cooling Airflow (SW2)
Low---Cooling Airflow
(SW3)
OFF OFF ON 565 565 555 540 530 See note 4
OFF ON OFF 695 710 715 710 705 700 695 685 680 675
OFF ON ON 940 945 940 935 935 930 920 900 890 875
ON OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON OFF ON 1285 1290 1295 1295 1285 1250 1220 1185 1155 1120
ON ON OFF 1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
ON ON ON 1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
Maximum Clg Airflow
2
1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
CF Switches S W 3 --- 3 S W 3 --- 2 S W 3 --- 1
Cont. Fan Default: OFF OFF OFF 565 565 555 540 530 See note 4
Continuous Fan Airflow
(SW3)
OFF OFF ON 565 565 555 540 530 See note 4
OFF ON OFF 695 710 715 710 705 700 695 685 680 675
OFF ON ON 940 945 940 935 935 930 920 900 890 875
ON OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON OFF ON 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON ON OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON ON ON 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
Heating (SW1)
High Heat Airflow
3
1055 1060 1065 1065 1055 1050 1040 1035 1025 1010
Low Heat Airflow
3
750 770 775 775 770 765 755 745 740 735
Unit size: 0801714 Clg/CF Switch settings
Clg Switches S W 2 --- 3 S W 2 --- 2 S W 2 --- 1
Clg Default: OFF OFF OFF 1085 1095 1095 1100 1100 1095 1090 1095 1085 1080
CF Switches S W 3 --- 3 S W 3 --- 2 S W 3 --- 1
L o w --- C l g D e f a u l t : OFF OFF OFF 550 550 545 535 520 See note 4
Cooling Airflow (SW2)
Low---Cooling Airflow
(SW3)
OFF OFF ON 550 550 545 535 520 See note 4
OFF ON OFF 705 710 710 710 700 See note 4
OFF ON ON 885 900 910 910 910 905 900 895 885 875
ON OFF OFF 1085 1095 1095 1100 1100 1095 1090 1095 1085 1080
ON OFF ON 1255 1265 1265 1270 1275 1275 1255 1220 1190 1160
ON ON OFF 1420 1410 1375 1345 1310 1280 1255 1220 1190 1160
ON ON ON 1420 1410 1375 1345 1310 1280 1255 1220 1190 1160
Maximum Clg Airflow
2
1445 1410 1375 1345 1310 1275 1255 1220 1190 1160
CF Switches S W 3 --- 3 S W 3 --- 2 S W 3 --- 1
Cont. Fan Default: OFF OFF OFF 550 550 545 535 520 See note 4
Continuous Fan Airflow
(SW3)
OFF OFF ON 430 410 390 370 350 See note 4
OFF ON OFF 485 475 455 440 420 See note 4
OFF ON ON 550 550 545 535 520 See note 4
ON OFF OFF 550 550 545 535 520 See note 4
ON OFF ON 550 550 545 535 520 See note 4
ON ON OFF 550 550 545 535 520 See note 4
ON ON ON 550 550 545 535 520 See note 4
Heating (SW1)
High Heat Airflow
3
1235 1245 1250 1255 1255 1260 1255 1220 1190 1160
Low Heat Airflow
3
1005 1010 1015 1015 1020 1000 995 990 980 970