Natural Gas to Propane Conversion Instructions

14 AG--KC019SNP--02
Specifications subject to change wi thout notice.
Modulating Gas Valve
Figure 21 Example of Modulating Furnace Control for ECM Blower Motor
24-V THERMOSTAT
TERMINALS
PL2 HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
PL1 LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3 ECM BLOWER
HARNESS
CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
MODEL PLUG
CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
OUTDOOR
A
IR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24
-
VAC
0.5 AMP MAX.
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SW4 SETUP
SWITCHES
SOFTWARE
VERSION
PART NUMBER AND
DATE CODE WWYY
PL8 - MODULATING
GAS VALVE
CONNECTOR
L11F061
Representative drawing only, some models may vary in appearance.
1.TurnSetupSwitchSW1--2onfurnacecontrolON(see
Figure 21).
2. Jumper R--W/W1 and R --W2 thermostat connections on
control.
3. When main burners ignite, confirm inlet gas pressure is
between 12.0--in. w.c. and 13.6 --in. w.c.
4. Remove jumper across R --W/W1 and R--W2 thermostat
connections to terminate call for heat.
5. Turn furnace gas valve switch to OFF position.
6. Turn gas supply manual shutoff valve to OFF position.
7. Turn off furnace power supply.
8. Remove manometer and on some models remove
pressure tap fitting.
9. On some models, apply pipe dope sparingly to the end of
inlet gas pipe plug and install into unused end of 1/8--in.
(3 mm) tee. Use a small back --up wrench on tee when
tightening gas inlet pipe plug. Or, on some models, tighten
set screw on inlet tower pressure tap with a 3/32--in. hex
wrench. (See Figure 15 or Figure 16,orFigure 14)