Natural Gas to Propane Conversion Instructions

The closed switch completes control circuit. Should an
interruption or reduction in gas supply occur, the gas pressure at
switch drops below low gas pressure switch setting, and switch
opens. Any interruption in control circuit (in which low gas
pressure switch is wired) quickly c loses gas valve and stops gas
flow to burners. When normal gas pressure is restored, the
system must be electrically reset to re--establish normal heating
operation.
Before leaving installation, observe unit operation through two
complete heating cycles. During this time, turn gas supply to gas
valve off just long enough to completely extinguish burner flame,
then instantly restore full gas supply. To ensure proper low gas
pressure switch operation, observe that there is no gas supply
to burners until after hot surface igniter begins glowing.
LABEL APPLICATION
1. Fill in Conversion Responsibility Label 344675--205 and
apply to Blower Access Door of furnace. Date, name, and
address of organization making this conversion are
required. (See Figure 24)
2. Attach Conversion Rating Plate Label 344675 --201 to
outer door of furnace. (See Figure 5)
3. Attach Gas Control Conversion Label 344675--202 to gas
valve. Do not use 344675--203, which is similar.
CHECKOUT
1. Observe unit operation through two complete heating
cycles.
2. See Sequence of Operation in furnace Installation,
Start--Up, and Operating Instructions.
3. Set room thermostat to desired temperature.
Figure 24
Gas Conversion Responsibility Label
A190114
Figure 25 Gas Control Conversion Label
A190077
Copyright 2019 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: AG---KC019SNP---02
Replaces: AG--KC019NP--01 REV B
Edition Date: 09/19