Installation Manual

42101590002 17
Specifications subject to change without notice.
960 Size Outdoor With FCM4X60***L Stage 5 Indoor Cooling
Outdoor Ambient Temperature - Degrees F, Dry Bulb
65 75 85 95 105 115#
Entering Indoor Temperature - Degrees F, Wet Bulb
STAGE- 5 Mode 72 67 63†† 57 72 67 63†† 57 72 67 63†† 57 72 67 63†† 57 72 67 63†† 57 72 67 63†† 57
Comfort
+
De- Humidify
SCFM 1488 1566 1514 1440 1367
MBh† 71.59 65.29 60.75 55.91 68.97 62.96 58.62 54.72 65.28 59.62 55.53 51.93 61.47 56.15 52.31 48.92 57.61 52.65 49.06 45.90
S/T‡ 0.51 0.67 0.70 1.00 0.52 0.69 0.71 1.00 0.52 0.69 0.71 1.00 0.52 0.69 0.71 1.00 0.52 0.69 0.71 1.00
AMPS* 12.59 10.61 16.67 18.98 14.52 12.64 19.00 8.86 16.32 14.79 8.87 10.76 18.53 16.81 10.77 12.63 8.60 19.23 12.64 14.62
HI PR 340 306 443 502 390 352 503 256 435 403 256 298 495 448 298 344 263 508 344 393
LO PR 126 161 148 150 129 163 150 132 126 165 132 137 129 163 136 138 157 165 138 140
Efficiency
SCFM 1600 1600 1600 1600 1600 1600
MBh† 72.44 66.10 61.52 57.24 69.15 63.13 58.78 55.06 65.82 60.10 55.99 52.83 62.40 57.00 53.13 50.51 58.86 53.83 50.18 48.12 55.24 50.50 47.11 45.62
S/T‡ 0.51 0.68 0.71 1.00 0.52 0.69 0.72 1.00 0.52 0.70 0.73 1.00 0.53 0.71 0.74 1.00 0.54 0.72 0.75 1.00 0.54 0.74 0.76 1.00
AMPS* 8.60 8.76 8.87 8.92 10.61 10.71 10.77 10.77 12.64 12.64 12.64 12.62 14.79 14.71 14.63 14.60 16.81 16.66 16.52 16.45 19.23 18.98 18.78 18.71
HI PR 263 259 256 254 306 302 298 297 352 347 344 342 403 397 393 392 448 442 439 437 508 502 499 497
LO PR 157 143 132 125 161 147 136 132 163 148 138 135 165 150 139 137 163 148 137 134 165 150 139 137
Maximum
SCFM 1680 1905 2000 2000 1600 1600
MBh† 72.23 66.23 61.81 58.03 69.91 64.18 59.97 57.77 66.70 61.24 57.27 56.00 63.17 58.03 54.29 53.46 58.65 53.88 50.35 48.26 55.04 50.57 47.31 45.78
S/T‡ 0.52 0.69 0.72 1.00 0.54 0.73 0.76 1.00 0.55 0.76 0.78 1.00 0.56 0.77 0.80 1.00 0.54 0.72 0.75 1.00 0.54 0.74 0.76 1.00
AMPS* 8.60 8.76 8.87 8.92 10.61 10.71 10.77 10.77 12.64 12.64 12.64 12.62 14.79 14.71 14.63 14.60 16.81 16.66 16.52 16.45 19.23 18.98 18.78 18.71
HI PR 263 259 256 254 306 302 298 297 352 347 344 342 403 397 393 392 448 442 439 437 508 502 499 497
LO PR 157 143 132 125 161 147 136 132 163 148 138 135 165 150 139 137 163 148 137 134 165 150 139 137
Total capacities are net (I.D blower heat subtracted) system capacities based on 25’ line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
* System amps are total of indoor and outdoor amps
S/T are based on 80 F db entering air at the indoor coil. For sensible capacities at other than 80 F db, deduct 835 Btuh per 1000 cfm of indoor
coil air from MBhxS/T for each degree below 80 F, or add 835 Btuh per 1000 cfm of indoor coil air from MBhxS/T for each degree above 80 F
†† At TVA rating indoor condition (75 F db/ 63 F wb), All other indoor air temperatures are at 80 F db
# System runs Stage 5 Efficiency Mode for Comfort+dh Mode at 115 degrees F outdoor temperature.