Service Manual

421 08 5600 02 1/18/2017
Specifications subject to change wi thout notice.
APPLICATION GUIDELINE &
SERVICE MANUAL
CVH8, HVH8, TVH8, CVA9, HVA9, TVA9
TABLE OF CONTENTS
PAGE
REFRIGERANT PIPING LENGTH LIMITATIONS 2...........
MAXIMUM LINE LENGTHS: 2.............................
MAXIMUM LINE LENGTHS 2.............................
MAXIMUM TOTAL EQUIVALENT LENGTH 2................
LONG LINE APPLICATIONS 2............................
GENERAL INFORMATION 3..............................
ELECTRICAL 3.........................................
ALUMINUM WIRE 3.....................................
UNIT ELECTRICAL POWER 3............................
MAJOR COMPONENTS 4................................
COMMUNICATION AND STATUS FUNCTION LIGHTS 6......
CHECK CHARGE 7.....................................
REQUIRED CHARGE ADJUSTMENT FOR INDOOR
COIL MODEL 7........................................
TROUBLESHOOTING 10.................................
FACTORY SUPPLIED MODEL PLUG INFORMATION 10.......
VARIABLE SPEED COMPRESSOR RESISTANCE
(WINDING RESISTANCE AT 70_F 20_F) 10................
RESISTANCE VALUES VS TEMPERATURE 12...............
FAULT CODE ACTIONS 14................................
VARIABLE SPEED DRIVE LED LOCATION
AND DESCRIPTION 21..................................
MOC LED DESCRIPTION 22..............................
COMPRESSOR POWER HARNESS
ASSEMBLY REPLACEMENT 23...........................
SMARTSENSE ASSEMBLY W SHIELD GASKET REMOVAL
AND INST ALLATION 25..................................
COMPRESSOR REPLACEMENT 28........................
WIRING DIAGRAMS 31..................................
REFRIGERATION SYSTEM 33.............................
REFRIGERANT 33.......................................
COMPRESSOR OIL 33...................................
SERVICING SYSTEMS ON ROOFS WITH
SYNTHETIC MATERIALS 33..............................
BRAZING 33............................................
SERVICE VALVES AND PUMPDOWN 33....................
PUMPDOWN & EVACUATION 34...........................
LIQUID LINE FILTER DRIER 35............................
SUCTION LINE FILTER DRIER 36..........................
THERMOSTATIC EXPANSION VALVE (TXV) 36..............
ACCUMULATOR 36......................................
REFRIGERATION SYSTEM REPAIR 37.....................
LEAK DETECTION 37....................................
COIL REMOVAL 38.......................................
SAFETY CONSIDERATIONS
Installation, service, and repair of these units should be
attempted only by trained service technicians familiar with
standard service instruction and training material.
All equipment should be installed in accordance with
accepted practices and unit Installation Instructions, and in
compliance with all national and local codes. Power should
be turned off when servicing or repairing electrical
components. Extreme caution should be observed when
troubleshooting electrical components with power on.
Observe all warning notices posted on equipment and in
instructions or manuals.
!
WARNING
ELECTRICAL HAZARD - HIGH VOLTAGE!
Failure to follow this warning could result in personal
injury or death.
Electrical components may hold charge. DO NOT
remove control box cover for 2 minutes after power has
been removed from unit.
PRIOR TO TOUCHING ELECTRICAL COMPONENTS:
Verify zero (0) voltage at inverter connections shown
on inverter cover.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect s witch.
Lock out and tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal
injury, and/or property damage.
Never use air or gases containing
oxygen for leak testing or
operating refrigerant compressors.
Pressurized mixtures of air or
gases containing oxygen can lead
to an explosion.
!
WARNING