Installation Manual

6 484 01 3701 05
Specifications subject to change without notice.
an open drain or sump. Make sure that the outlet of each trap is
below its connection to condensate pan to prevent condensate from
overflowing the drain pan. Prime all traps, test for leaks, and
insulate traps and lines if located above a living area.
3” / 76mm
A08067
Fig. 8 Condensate Trap
NOTE: If unit is located in or above a living space, where damage
may result from condensate overflow, a fieldsupplied, external
condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4in. (19 mm) condensate
line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.
NOTE: To avoid drainage problems, test the primary drain line by
slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as
explained in the previous note provides further protection against
overflow due to a clogged primary drain.
NOTE: In applications where return air humidity levels stay at
70% or above for a prolonged period of time, condensation can
form on the bottom of pan and drip.
WASTE LINE CONNECTION
If the condensate line is to be connected to a waste (sewer) line, an
open trap must be installed ahead of the waste line to prevent
escape of sewer gases (See Fig. 9 ).
A10216
Fig. 9 Condensate Drain to Waste Line
EXPLOSION HAZARD
Failure to follow this warning could result in personal injury
or death.
Provide trap with air gap in drain line when connecting to
waste (sewer) line.
!
WARNING
Copyright 2018 International Comfort Products