Installation Manual
INST ALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X, FXM4X
496 01 5503 01 5
Specifications are subject to change without notice.
Figure 4
A- Coil in Horizontal Left Application (factory configuration)
A
B
C
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
AIR SEAL
ASSEMBLY
HORIZONTAL
DRAIN PAN
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
HORIZONTAL LEFT
PRIMARY DRAIN
HORIZONTAL LEFT
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
BRACKET
Horizontal Right Conversion of Units With Slope Coils
1. Remove blower and coil access panel and fitting panel
(refer to Figure 5).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to Figure 5).
5. Attach coil to casing flange using coil mounting screw
previously removed.
6. Align holes with tubing connections and condensate
pan connections, and reinstall access panels and
fitting panel. After brazing, make sure liquid and
suction tube grommets are in place to prevent air
leaks and cabinet sweating.
Figure 5
Conversion for Horizontal Right Applications - Slope Coil
COIL MOUNTING
SCREW
BLOWER
ASSEMBLY
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
PRIMARY DRAIN
DRAINPAN
SLOPE COIL
COIL SUPPORT RAIL