Technical information

54
Features
Our advanced refrigerant control technology allows us to achieve a
total refrigerant piping length of 180 m. This opens up new
possibilities in system design.
Long Piping Length
Heating capacity is improved at low
outdoor temperature by our advanced
technology.
Powerful Heating
Connection check function : Possible to confirm whether wiring
connection and address setting are correct by a quick check run
function.
Easier Installation
Height difference between
outdoor and indoor units
30m max.
Height difference between
indoor and indoor units
15m max.
Actual piping length
120m max.
Piping length from first
separation tube to the
farthest indoor unit
40m max.
180m max.
Total pipe length
• Display connected indoor unit numbers
• Duplicately set address number of indoor unit can
be displayed
7
Current model (
6HP class)
16.6
J-II series (6HP)
Outdoor temperature (°C)
Current model
(
6HP class)
-20
-10 0
H
eating c
a
pacity
(kW)