Connect the RPSU main power bus to the external DC power supply system using the
two-hole bolted connections as shown in Figure 5-6.
Power lugs and connection bolts are NOT supplied with the AirWalk system
Figure 5-6 External DC Bus Power Connections [DC models]
The following practices are recommended for DC bus connections:
- Use suitable lugs (Blackburn CTL2-2516 or equivalent lug recommended)
- Use suitable gauge cables (#2/#4 gauge flexible stranded recommended)
- Tighten bolts firmly to prevent movement or arcing
- Use heat shrink tubing, or equivalent, to cover and protect connections
- Power source should be independently fused at the origin point
IMPORTANT – Do not turn on power source until installation is fully completed.
IMPORTANT – Extra care is required when working with high current DC power systems
to avoid personal injury. Protect all DC connections to avoid accidental short circuits.