Multi Splits Series HKD Indoor Units HND Indoor Units CBD Indoor Units XAD Indoor Units DCD Indoor Units AWSI-HKD009-N11 AWSI-HND009-N11 Outdoor Units AWAU-YCZ218-H11 AWSI-HKD012-N11 AWSI-HND012-N11 AWSI-CBD012-N11 AWSI-XAD012-N11 AWSI-DCD012-N11 AWAU-YCZ327-H11 AWSI-HKD018-N11 AWSI-HND018-N11 AWAU-YCZ430-H11 AWAU-YCZ536-H11 REFRIGERANT REFRIGERANT REFRIGERANT R410A SM YCZ DCI 1-A.
Contents Part 1 General Information .................................................................................................... 1 Part 2 Indoor Units ............................................................................................................... 11 Part 3 Outdoor Units............................................................................................................. 53 Part 4 Installation.....................................................................................
General Information Part 1 General Information 1. Model Lists ..........................................................................2 2. External Appearance ........................................................3 2.1 Indoor Units ................................................................................. 3 2.2 Outdoor Units .............................................................................. 3 3. Product specification .......................................................
Model Lists 1. Model Lists 1.
External Appearance 2. External Appearance 2.1 Indoor Units HKD HND Four-way cassette(Compact) Duct Console 2.
Product specification 3. Product specification Model Outdoor Unit AWAU-YCZ218-H11 Installation Method of Pipe 2 x AWSI-HND009-N11 2 x AWSI-HKD009-N11 Installation Method of Pipe Flared Flared Characteristics Heating Cooling Capacity (1) kW 5.2 6 5.2 6 Pdesign kW 5.2 5.9 5.2 5.6 SEER / SCOP (2) W/W Energy efficiency class Annual energy consumption Cooling Heating Units Average Average 6.1 4.1 5.6 3.
Product specification Model Outdoor Unit AWAU-YCZ327-H11 Installation Method of Pipe 3 x AWSI-HND009-N11 3 x AWSI-HKD009-N11 Installation Method of Pipe Flared Flared Characteristics Capacity (1) Pdesign SEER / SCOP (2) Units Cooling kW 7.8 kW W/W Energy efficiency class Heating Cooling Average Heating Average 8.5 7.8 8.5 7.8 8 7.8 8 6.6 3.9 6.1 3.
Product specification AWAU-YCZ430-H11 Model Outdoor Unit Installation Method of Pipe 4 x AWSI-HND009-N11 4 x AWSI-HKD009-N11 Installation Method of Pipe Flared Flared Characteristics Heating Cooling Capacity (1) kW 8.5 9 8.5 9 Pdesign kW 8.5 8.2 8.5 8.2 SEER / SCOP (2) W/W Energy efficiency class Annual energy consumption Cooling Heating Units Average Average 6.6 3.9 5.8 3.
Product specification AWAU-YCZ536-H11 Model Outdoor Unit Installation Method of Pipe 5 x AWSI-HND009-N11 5 x AWSI-HKD009-N11 Installation Method of Pipe Flared Flared Characteristics Heating Cooling Capacity (1) kW 10.5 11.5 10.5 11.5 Pdesign kW 10.5 10.5 10.5 10.5 W/W 5.6 3.8 5.1 3.
Product specification AWSI-HND009-N11 Model Indoor Unit Installation Method of Pipe Flared Characteristics Capacity (4) Power supply Cooling Heating Cooling Heating kW 2.7 2.8 3.5 3.
Product specification AWSI-HKD012-N11 Model Indoor Unit Installation Method of Pipe Flared Characteristics Capacity (4) Power supply Cooling Heating Cooling Heating kW 3.2 3.5 5 5.
Product specification AWSI-CBD012-N11 Model Indoor Unit Installation Method of Pipe Flared Characteristics Capacity (4) Units Cooling kW 3.5 V Power supply 1 Hz 50 Centrifugal fan x1 Cooling SH/H/M/L Heating Air flow (1) INDOOR External static pressure RPM 830/720/660 SH/H/M/L RPM 830/720/660 SH/H/M/L m3/hr 800/710/560 Min Pa 0 Sound power level (2) SH/H/M/L dB(A) 55 Sound pressure level(3) SH/H/M/L dB(A) 44/41/38 l/hr 1.5 Moisture removal Condensate drain tube I.
Indoor Units Part 2 Indoor Units HKD Type .............................................................................12 HND Type .............................................................................22 Light Commercial................................................................
HKD Type HKD Type 1. Function...........................................................................13 2. Dimensions......................................................................14 3. Wiring Diagrams .............................................................15 4. Exploded View and Spare Part list ................................
Function 1. Function Filter 2 ways of drainage Killer Of Formaldehyde Louver Position Memory Function Ionizer(O) Refrigerant Leakage Detect Silver Ico Filter(O) Self-diag.
Dimensions 2.
Wiring Diagrams 3.
Exploded View and Spare Part list 4.
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HKD009-N11 No. Part Name Qty BOM Code No. Part Name Qty BOM Code Louver motor 1 202400200031 1 Panel assembly 1 2011325A5387 16.1 3 Display box assembly 1 2033325A2367 17 Pipe clamp board 1 201119900949 3.
Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HKD012-N11 18 Indoor Units
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HKD012-N11 No. Part Name Qty BOM Code No. Part Name Qty BOM Code Louver motor 1 202400200031 1 Panel assembly 1 2011325A5387 16.1 3 Display box assembly 1 2033325A2367 17 Pipe clamp board 1 201119900949 3.
Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HKD018-N11 20 Indoor Units
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HKD018-N11 No. Part Name Qty BOM Code No. Part Name Qty BOM Code Chassis assembly 1 201132790680 Louver motor 1 202400200031 1 Panel assembly 1 2011327A4068 16 2 Air filter 2 201132790664 16.
HND Type HND Type 1. Function...........................................................................23 2. Dimensions......................................................................24 3. Wiring Diagrams .............................................................26 4. Exploded View and Spare Part list ................................
Function 1. Function Ionizer(O) Silent mode(O) Plasma(O) Horizontal &Vertical Swing Function(O) Silver Ico Filter(O) Louver Position Memory Function Vitamin C Filter(O) Refrigerant Leakage Detect 3M HAM Filter(O) Self-diag.
Dimensions 2.
Dimensions Model L(mm) R(mm) H(mm) Dimension of installation hole(mm) AWSI-HND009-N11 180 140 110 110 45 45 ¢65 Model L(mm) R(mm) H(mm) AWSI-HND018-N11 260 135 45 AWSI-HND012-N11 Indoor Units Dimension of installation hole(mm) ¢65 25
Wiring Diagrams 3.
Exploded View and Spare Part list 4.
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HND009-N11 No. Name Qty BOM Code No. Part Name Qty BOM Code Chassis assembly 1 201132391058 Louver motor 1 202400200031 1 Panel assembly 1 2011323A3829 16 2 Air filter 2 201132391052 16.1 3 Display box assembly 1 2033323A2544 17 Pipe clamp board 1 201119900949 Display assembly 1 2013330A0830 18 Installation plate 1 201232590037 1 201119901024 19 1 2033323A2552 1 201132392602 19.
Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HND012-N11 Indoor Units 29
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HND012-N11 No. Name Qty BOM Code No. Part Name Qty BOM Code Chassis assembly 1 201132590963 Louver motor 1 202400200031 1 Panel assembly 1 2011325A5384 16 2 Air filter 2 201132590962 16.1 3 Display box assembly 1 2033323A2544 17 Pipe clamp board 1 201119900949 Display assembly 1 2013330A0830 18 Installation plate 1 201232590037 1 201119901024 19 1 2033325A2373 1 201132591059 19.
Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HND018-N11 Indoor Units 31
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-HND018-N11 No. Name Qty BOM Code No.
Light Commercial Light Commercial 1. Features ...........................................................................34 2. Dimensions......................................................................40 3. Service Space(unit:mm) .................................................42 4. Wiring Diagrams .............................................................44 5. Exploded View and Spare Part list ................................
Features 1. Features 1.1 Four-way cassette type(compact) ⑴ New panel 360°surrounding air outlet design, affords comfortable feeling ⑵ Compact design The body size is 570×260×570mm, it’s just smaller than the ceiling board, so it’s very easy for installation and will not damage the decoration. The panel size is 647×50×647mm. The hooks are designed in the four corners of the body, which can save installation space.
Features Fresh Air Dimension:Φ75mm ⑸ Air passage function Reserves the space for air outlet from the side of indoor unit; It’s availed to connect air duct from the two sides to the nearby small rooms.
Features 1.2 A5 Duct ⑴ Installation accessories: (Optional) Front Board, Canvas Air Passage, Filter, Panel, for easy installation Front Board Canvas Air Passage Filter Panel ⑵ Easy Installation: Two air inlet styles (Bottom side or Rear side) Air inlet from rear is standard for all capacity; air inlet from bottom is optional.
Features Replace the motor or centrifugal fan Remove the ventilated panel firstly. Remove a half of blower housing and take out the motor with centrifugal fan. Directly remove two bolts, and then replace the motor or centrifugal fan easily.
750mm upmost Features ⑺ Built-in display board The standard indoor unit can be controlled by wired controller. There is a display board with a receiver in the E-box. Move out the display, and fix it in other place, even in the distance of 10m. The unit will realized remoter control. The wired controller and the display board can display the error code or production code when the chips detect some failure.
Features 1.3 Console (1) Consumes up to 30% less energy than non-inverter units ——DC inverter compressor ——indoor fan motor adopts DC motor (2) Achieves set temperature more quickly ——air supplying from top and bottom or from top only ——air inlet from four directions (3) Compact unit body, space saving ——this unit body is very thin and harmonious with room. It is beautiful, elegant and space saving. ——lightweight and compact. (4) Flexible installation.
Dimensions 2. Dimensions 2.1 Four-way cassette type(compact): B H G 2.
Dimensions Model AWSI-DCD012-N11 Outline dimension(mm) Air outlet opening size Air return opening size A B C D E F G H I J K 700 210 635 570 65 493 35 119 595 200 80 Size of outline dimension mounted plug L M 740 350 2.
Service Space(unit:mm) 3. Service Space(unit:mm) 3.1 Four-way cassette(compact) 3.2 A5 Duct Ensure enough space required for installation and maintenance. All the indoor units reserve the hole to joint the fresh air pipe.
Service Space(unit:mm) 3.
Wiring Diagrams 4.
Wiring Diagrams AWSI-DCD012-N11 Light Commercial 45
Wiring Diagrams AWSI-XAD012-N11 46 Indoor Units
Exploded View and Spare Part list 5.
Exploded View and Spare Part list Spare part list of indoor unit:AWSI-CBD012-N11 No. Qty BOM Code No. Part Qty BOM Code Panel 1 2011099A2555 14 Ventilation ring 1 201142390003 1.1 Display box assembly 1 203342090008 15 Centrifugal fan 1 201100100804 1.2 Horizontal louver 4 201109991797 16 Asynchronous motor 1 202400300052 1.3 Air filter 1 P0000453127 17 Fan motor fixing base 1 201280490338 1.
Exploded View and Spare Part list Exploded View of indoor unit: AWSI-DCD012-N11 Light Commercial 49
Exploded View and Spare Part list Spare part list of indoor unit: AWSI-DCD012-N11 No. Part Name Qty BOM Code No. Part Name Qt y BOM Code 1 Chassis assembly 1 201285190007 14 Pipe temperature sensor assembly 1 202440500004 2 Up volute shell 2 201185190001 15 Water collector 1 202285190003 3 Centrifugal fan 2 201100100809 16 Right assembly 1 201270290089 4 Below volute shell 2 201185190002 16.
Exploded View and Spare Part list Exploded View of indoor unit:AWSI-XAD012-N11 Light Commercial 51
Exploded View and Spare Part list Spare part list of indoor unit:AWSI-XAD012-N11 No. Name Qty BOM Code No. Part Name Main control board assembly Fixing board of electronic control box I Auxiliary electric heater control board Qty BOM Code 1 2013440A0029 1 201244090004 1 201344090029 1 Panel assembly 1 2011440A0001 9.10 2 Air filter 1 201144090002 9.11 3 Panel assembly 1 201144090022 9.14 4 Evaporator assembly 1 201544090014 10 Water collector 1 201144090044 4.
Outdoor Units Part 3 Outdoor Units 1. Dimensions ......................................................................54 2. Service Space ..................................................................58 3. Refrigeration Cycle Diagram..........................................59 4. Wiring Diagrams .............................................................61 5. Indoor units combination ...............................................63 6. Operation Limits................................................
Dimensions 1. Dimensions AWSI-XAD012-N11 243.6 200.
Dimensions AWAU-YCZ327-H11 L2 H 8 12 860 L1 285.7 238.
Dimensions AWAU-YCZ430-H11 238.4 285.
Dimensions AWAU-YCZ536-H11 Outdoor Units 57
Service Space 2.
Refrigeration Cycle Diagram 3. Refrigeration Cycle Diagram 3.1 Refrigeration cycle diagram of inverter 1 drive 2 type INDOOR OUTDOOR LIQUID VALVE A EXV A CAPILIARY A CHECK VALVE LIQUID VALVE B EXV B CAPILIARY B CAPILIARY TUBE HEAT EXCHANGE (EVAPORATOR) T4 Ambient temp. sensor T1 Room temp. sensor T3 Condenser temp. sensor HEAT EXCHANGE (CONDENSER) T2B-A Evaporator T2 Evaporator temp. sensor middle GAS VALVE A temp. sensor outlet 4-WAY VALVE GAS VALVE B T2B-B Accumulator T5 Discharge temp.
Refrigeration Cycle Diagram INDOOR OUTDOOR EXV A CAPILIARY A LIQUID VALVE A EXV B CAPILIARY B LIQUID VALVE B CHECK VALVE EXV C CAPILIARY C LIQUID VALVE C EXV D CAPILIARY D LIQUID VALVE D HEAT EXCHANGE (EVAPORATOR) CAPILIARY TUBE T4 Ambient temp. sensor T1 Room temp. sensor T3 Condenser temp. sensor HEAT EXCHANGE (CONDENSER) T2B-A Evaporator temp. sensor outlet GAS VALVE A T2 Evaporator temp.
Wiring Diagrams 4.
Wiring Diagrams AWAU-YCZ430-H11 AWAU-YCZ536-H11 62 Outdoor Units
Indoor units combination 5. Indoor units combination 5.1 Indoor unit combination for AWAU-YCZ218-H11 AWAU-YCZ218-H11 Two IDU 9+9 9+12 9+18 12+12 5.2 Indoor unit combination for AWAU-YCZ327-H11 AWAU-YCZ327-H11 Three IDU 9+9+9 9+12+12 9+9+12 9+12+18 9+9+18 12+12+12 Two IDU 9+18 12+18 18+18 5.3 Indoor unit combination for AWAU-YCZ430-H11 AWAU-YCZ430-H11 Three IDU 9+9+9 9+12+12 9+9+12 9+12+18 9+9+18 12+12+12 Two IDU 9+18 12+18 18+18 Four IDU 9+9+9+9 9+9+9+12 5.
Operation Limits 6. Operation Limits Temperature Mode Room temperature Cooling operation Heating operation ≥17℃ ≤30℃ 0℃~50℃ Outdoor temperature -15℃~50℃ (For the models with low temperature cooling system) -15℃~24℃ CAUTION: 1. If the air conditioner is used beyond the above conditions, certain safety protection features may come into operation and cause the unit to operate abnormally. 2. The room relative humidity should be less than 80%.
Sound Levels 7. Sound Levels Outdoor Unit Microphone H 1.0m Note: H= 0.
Exploded View and Spare Part list 8.
Exploded View and Spare Part list Spare part list of outdoor unit: AWAU-YCZ218-H11 No. Part Name Qty BOM Code No. Part Name BOM Code 1 201257190118 1 203357090061 1 Ambient temperature sensor assembly 1 202301310075 19 2 Rear net 1 2011481G0001 20 3 Condenser assembly 1 201537990084 20.1 Cover of electronic control box 1 201157190011 3.1 Input pipe assembly 1 201637991011 20.2 Outdoor main control board assembly 1 201357090064 3.2 Condenser 1 201537990003 20.
Exploded View and Spare Part list Exploded View of outdoor unit: AWAU-YCZ327-H11 68 Outdoor Units
Exploded View and Spare Part list Spare part list of outdoor unit: AWAU-YCZ327-H11 No. Part Name Qty BOM Code No. Part Name Qty BOM Code 1 202301901173 1 203357190096 1 Ambient temperature sensor assembly 1 202301310075 20.5 Radiator 2 Rear net 1 2011482G0001 21 Terminal assembly 3 Condenser assembly 1 201557190037 21.1 Wire joint 2 202301450156 4 Pipe temperature sensor assembly 1 202301300422 21.
Exploded View and Spare Part list Exploded View of outdoor unit: AWAU-YCZ430-H11 70 Outdoor Units
Exploded View and Spare Part list Spare part list of outdoor unit: AWAU-YCZ430-H11 No. Part Name Qty BOM Code No. Part Name Qty BOM Code Terminal board 1 201257190120 Liquid valve assembly 1 201657190352 1 Ambient temperature sensor assembly 1 202301310069 21.2 2 Rear net 1 2011482G0001 22 3 Condenser assembly 1 201557190037 22.1 Liquid valve 1 201600740091 1 202301300421 22.
Exploded View and Spare Part list Exploded View of outdoor unit: AWAU-YCZ536-H11 72 Outdoor Units
Exploded View and Spare Part list Spare part list of outdoor unit: AWAU-YCZ536-H11 No. Part Name Qty BOM Code No. 1 Rear net 1 2011487G0001 21.7 2 Ambient temperature sensor assembly 1 202301310075 21.8 3 Condenser assembly 1 201557190043 22 Part Name Electronic installing box assembly Active PFC Module Subassembly Compressor Qty BOM Code 1 201257190055 1 201319901145 1 201401500220 1 202448200000 1 201657190376 3.1 Input pipe assembly 1 201657290044 24 3.
Installation Part 4 Installation 1.Wrench torque sheet for installation ...................................................75 2.Connecting the cables ..........................................................................75 3.Pipe length and the elevation ...............................................................75 4 Installation for the first time .................................................................77 5 Adding the refrigerant after running the system for many years .....
Wrench torque sheet for installation 1. Wrench torque sheet for installation Outside diameter Torque Additional tightening torque mm N.cm N.cm Ф6.35 1500(153kgf.cm) 1600(163kgf.cm) Ф9.52 2500(255kgf.cm) 2600(265kgf.cm) Ф12.7 3500(357kgf.cm) 3600(367kgf.cm) 2. Connecting the cables The power cord of connect should be selected according to the following specifications sheet. Rated current of appliance Nominal cross-sectional area (mm²) >3 and ≤6 0.75 >6 and ≤10 1 >10 and ≤16 1.
Pipe length and the elevation Indoor unit Model 7K9K12K 18K Pipe diameter (mm/inch) Extension pipe diameter (mm/inch) Liquid 6.35(1/4) Liquid 6.35(1/4) Gas 9.52(3/8) Gas 9.52(3/8) Liquid 6.35(1/4) Liquid 6.35(1/4) Gas 12.7(1/2) Gas 12.7(1/2) Liquid 6.35(1/4) Gas 9.
Installation for the first time 4. Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below: ● Pressure in the system rises. ● Operating current rises. ● Cooling or heating efficiency drops. ● Moisture in the refrigerant circuit may freeze and block capillary tubing. ● Water may lead to corrosion of parts in the refrigerant system.
Installation for the first time 7) Turn the flare nut of the 3-way valves about 45°counterclockwise for 6 or 7seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve. 8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve. 4.2. Air purging by refrigerant Procedure: 1).
Installation for the first time 7). Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m. Be sure to check the gas leakage. 4.3. Adding the refrigerant if the pipe length >5m Electronic scale Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
Adding the refrigerant after running the system for many years 5. Adding the refrigerant after running the system for many years Electronic scale Procedure: 1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve. Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge. 2). Purge the air from the charge hose.
Re-installation while the indoor unit need to be repaired 6. Re-installation while the indoor unit need to be repaired 6.1. Collecting the refrigerant into the outdoor unit Procedure 1). Confirm that both the 2-way and 3-way valves are set to the opened position Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
Re-installation while the indoor unit need to be repaired 6.2. Air purging by the refrigerant Procedure: 1). Confirm that both the 2-way and 3-way valves are set to the closed position. 2). Connect the charge set and a charging cylinder to the service port of the 3-way valve Leave the valve on the charging cylinder closed. 3). Air purging. Open the valves on the charging cylinder and the charge set.
Re-installation while the outdoor unit need to be repaired Be sure to check the gas leakage. 7. Re-installation while the outdoor unit need to be repaired 7.1. Evacuation for the whole system Procedure: 1). Confirm that both the 2-way and 3-way valves are set to the opened position. 2). Connect the vacuum pump to 3-way valve’s service port. 3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa. 4).
Re-installation while the outdoor unit need to be repaired 7.2. Refrigerant charging Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge. 2).
Electrical Control System Part 5 Electrical Control System 1. Electrical Control Function...........................................86 2. Troubleshooting ...........................................................
Electrical Control Function 1. Electrical Control Function 1.1 Definition T1: Room Air Thermistor (RAT) T2: Indoor Coil Thermistor (ICT) T2B: Indoor Return Gas Thermistor (RGT) T3: Outdoor Coil Thermistor (OCT) T4: Outdoor Air Thermistor (OAT) T5: Compressor Discharge Thermistor (CTT) 1.2 Main Protection 1.2.1 Three minutes delay at restart for compressor. 1.2.2 Temperature protection of compressor discharge When the compressor discharge temp.
Electrical Control Function COOL_F6 ICOOLLMT2 COOL_F5 ICOOLLMT1 If the current frequency is lower than COOL_F4, the frequency will not be limited. After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds and stop. The AC will restart 3 minutes later.
Electrical Control Function 3.5 High 3.0 Medium 1.5 1.0 Low For HKD,HND, Console T1-24 6.0 5.0 4.0 2.5 1.0 H a (H-L)*0.75+L (H-L)*0.5+L (H-L)*0.25+L L b c d e 1.3.2 Cooling Mode 1.3.2.1 Compressor running rules The compressor will run at corresponding frequency according to the gross amendatory capacity demand. Frequency Amendatory capacity demand.
Electrical Control Function T4 28℃ A DC_FAN_HI_SPD_ADD B DC_FAN_MID_SPD_ADD C DC_FAN_MIN_SPD_ADD D DC_FAN_SLOW_SPD_ADD E DC_FAN_SSLOW_SPD_ADD 26℃ 25℃ 23℃ 22℃ 20℃ 19℃ 17℃ 1.3.2.3 Indoor fan running rules For Cassette、A5 In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. The auto fan: 3.5 High 3.0 1.5 Medium 1.
Electrical Control Function The auto fan acts as below rules: T1-Ts 6.0 5.0 4.0 2.5 1.0 H a b c d e (H-L)*0.75+L (H-L)*0.5+L (H-L)*0.25+L L 1.3.2.4 Condenser temperature protection When T3>65℃ for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue. When T3<52℃, the protection will release and the compressor will restart after 3 minutes. 1.3.2.
Electrical Control Function T4 21℃ E DC_FAN_SSLOW_SPD_ADD D DC_FAN_SLOW_SPD_ADD C DC_FAN_MIN_SPD_ADD B DC_FAN_MID_SPD_ADD A DC_FAN_HI_SPD_ADD 19℃ 18℃ 16℃ 15℃ 13℃ 12℃ 10℃ 1.3.3.3 Indoor fan running rules: For HKD,HND, Console In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold-wind function has the priority.
Electrical Control Function T1-Ts+ΔT 0.0 -1.0 L (H+-L)*0.2+L (H+-L)*0.4+L -2.0 -3.0 (H+-L)*0.6+L -4.0 (H+-L)*0.6+L -5.0 -6.0 -6.5 (H+-L)*0.8+L H+ For Cassette & Duct: When the compressor is on, the indoor fan can be set to high, medium, low and auto. And the anti-cold wind function has the priority. Auto fan action: T1-Ts-ΔT Low -3.5 -4 Medium -4.5 -5 High 1.3.3.
Electrical Control Function ----T3 rises to be higher than TCDE1℃. ----T3 keeps to be higher than TCDE2℃ for 80 seconds. ----The machine has run for 10 minutes in defrosting mode. Defrosting action: 4-Way valve no longer than 10min Compressor Indoor fan Cool-F9 TimeA 10S 10S 30S Anti cold wind Outdoor fan PMV running 4 mins with 480P PMV 480P 1.3.3.5 High evaporator coil temp.T2 protection: If T2>63℃, the indoor unit has no capacity demand and resume till 48℃. . 1.3.
Electrical Control Function Low indoor room temperature protection All protections are active and the same as that in cooling mode. For other models: Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode. Low indoor room temperature protection In drying mode, if room temperature is lower than 10℃, the compressor will stop and not resume until room temperature exceeds 12℃. All protections are active and the same as that in cooling mode. 1.3.
Electrical Control Function 1.3.10 Forced operation function 1.3.10.1 Enter forced operation function: Press the touch button continually, the AC will run as below sequence: Forced auto→Forced cooling→Off When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if pressing the button once again, the machine will turn into forced cooling mode. In forced cooling mode, pressing touch button will turn off the machine. 1.3.10.
Electrical Control Function from follow-me signal every 3 minutes. 3) The PCB will take action to the mode change information from remote controller signal, and the follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
Electrical Control Function function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to get into the check function display. After 1.5s, it will display the content corresponding to No. N. The digital display tube will display the follow procedure when push SW1 each time. Display Remark 0 Normal display Display running frequency, running state or malfunction code 1 No.
Electrical Control Function 38 EXV open angle for B indoor unit 39 EXV open angle for C indoor unit 40 EXV open angle for D indoor unit 41 EXV open angle for E indoor unit If the value is higher than 99, the digital display tube will show single digit and tens digit. For example ,the digital display tube show “2.0”,it means the EXV open angle is 120×4=480p.) Bit6 Frequency limit caused by IGBT radiator Frequency limit caused by PFC Bit5 Frequency limit caused by T4.
Electrical Control Function T1 Ts 4 3 2 1 0 f e d c b a 3 2 1 0 -1 Capacity area a b c d e f Norm value (N) 3 2 1.5 1 0.5 0 1.3.12.4 Number of indoor unit Display 1 Number of indoor unit 1 2 2 3 3 4 4 5 5 1.3.12.
Troubleshooting 2. Troubleshooting 2.1 Display board 2.1.1 Icon explanation on indoor display board (HKD& HND). ION indication lamp(optional function):This lamp illuminates when Clean Air feature is activated. DEFROST indication lamp(For cooling & heating models only): Lights up when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating operation. OPERATION indication lamp:This lamp illuminates when the air conditioner is in operation.
Troubleshooting 2.1.3 Icon explanation on indoor display board (Compact cassette). Infrared signal receiver Temporary button Operation temp. Timer indicator Alarm indicator PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type) 2.1.4 Icon explanation on indoor display board (Console) Infrared signal receiver Operation temp. Timer indicator PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type) FUNC Temporary button 2.1.
Troubleshooting 2.
Troubleshooting For Console: NO. Malfunction Running lamp Timer lamp Defrosting lamp 1 Open or short circuit of T1 temperature sensor ☆ X X 2 Open or short circuit of T2 temperature sensor X X ☆ 3 Communication malfunction between indoor and outdoor units.
Troubleshooting 2.
Troubleshooting 2.4 Solving steps for typical malfunction 2.4.1 For the indoor unit 2.4.1.1 Indoor EEPROM malfunction Shut off the power supply and turn it on 1 minute later. Is it still displaying the error code? Yes If the EEPROM chip is welded on PCB, replace the PCB directly. Otherwise, check whether the EEPROM chip plugged in PCB well? No Insert the EEPROM well Yes Replace the indoor PCB.
Troubleshooting 2.4.1.2 Indoor / outdoor units communication error Indoor / outdoor units communication error Start: Power off , then Power on the A/C by the Breaker. (reconnect the power wire). Is it still displaying the error code? Yes Check wiring on the outdoor and indoor terminal follow the wiring diagram. Is all connecting correctly? No Reconnect the wiring No No Reconnect the wiring Yes Turn on all indoor unit by remote controller.
Troubleshooting Pic 1: check the voltage of N to S (Vs), is it moving alternately between positive value and negative value? Pic 2: :IPM (For dual/tri-zone) Operating Self-Check Pic 2: :IPM (For qua-zone) els) Power, Self-Check Operating Electrical Control System 107
Troubleshooting PIC3 :Main board LED when power on and unit standby. .
Troubleshooting 2.4.1.3 indoor unit fan speed has been out of control Shut off the power supply and turn it on 1 minute later. Is it still displaying the error code? No The unit operates normally. Yes Shut off the power supply, rotate the fan by hand. Does it rotate properly? No Find out the cause and have it solved. For example, check whether the fan is blocked or the bearing is broken? No Correct the connections. Yes Check the wires of fan motor.
Troubleshooting For console: 5 4 6 3 1 2 NO. Color 1 Red 2 --- 3 White 4 Blue 5 Yellow 6 Black For other models: NO. 1 2 3 4 5 6 Color Red --Black White Yellow Blue Index2: 1: Indoor AC fan motor Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V power supply), the PCB must have problems and need to be replaced. 2.
Troubleshooting For console: 5 4 6 3 1 2 DC motor voltage input and output For HKD &HND: NO. Color Signal Voltage 1 Red Vs/Vm 280V~380V 2 --- --- --- 3 Black GND 0V 4 White Vcc 14-17.5V 5 Yellow Vsp 0~5.6V 6 Blue FG 14-17.5V For Duct & Cassette: NO. Color Signal Voltage 1 Red Vs/Vm 192V~380V 2 --- --- --- 3 Black GND 0V 4 White Vcc 13.5-16.5V 5 Yellow Vsp 0~6.5V 6 Blue FG 15V For console: NO.
Troubleshooting 2.4.1.4 Open or short circuit of temperature sensor. Check the connections between temperature No Correct the connections. sensor and PCB. Are the connections good? Yes Check the resistance value of the sensor via Appendix 1 Is it normal? Yes Replace indoor or outdoor PCB. No Replace the sensor 2.4.1.
Troubleshooting 2.4.2 For the outdoor unit 2.4.2 1 Outdoor EEPROM malfunction(ODU E0) Outdoor EEPROM malfunction Yes If the EEPROM chip is welded on PCB, replace the PCB directly.
Troubleshooting 2.4.2.2 Communication malfunction between IPM board and outdoor main board(ODU E3) Communication malfunction between IPM board and outdoor main board Is there at least one LED in the IPM board light? No Check the signal wire between the IPM module and the main board, is it connected good? Yes No Yes Reconnect and retry.
Troubleshooting 2.4.2.
Troubleshooting 2.4.2.4 Outdoor unit fan speed has been out of control (E8) Shut off the power supply and turn it on 1 minute later. Is it still displaying the error code? No The unit operates normally. Yes Shut off the power supply, rotate the fan by hand. Does it rotate properly? No Find out the cause and have it solved. For example, check whether the fan is blocked or the bearing is broken? No Correct the connections. Yes Check the wires of fan motor.
Troubleshooting Index 1: 1.Outdoor DC fan motor(control chip is inside fan motor) Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan motor must have problems and need to be replaced. NO. 1 2 3 4 5 6 Color Red --Black White Yellow Blue Index2: 1. Outdoor DC fan motor(control chip is inside fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector.
Troubleshooting 2.4.2.
Troubleshooting 2.4.2.
Troubleshooting 2.4.2.7 Current protection of compressor(ODU P3) Current protection of compressor Judge 1: Check whether the input current of the power supply wire is more than 15A (For 27K(1x3) , it is 18.5A .
Troubleshooting 2.4.2.8 Temperature protection of compressor discharge(ODU P4) Temperature protection of compressor discharge Check whether the compressor discharge temp. is more than 115°C ? Check whether the refrigerant is leak Yes Yes Stop leaking and add refrigerant No Check whether the wiring connection is right between compressor discharge temp. sensor and PCB according to wiring diagrams? No Correct the wiring connection Yes Judge: The discharge temp.
Troubleshooting 2.4.2.9 High temperature protection of condenser(ODU P5) When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. High temperature protection of condenser Replace the temperature sensor No Check whether the condenser temperature is more than 65°C Check whether the resistance of condenser temp.
Troubleshooting 2.4.2.
Troubleshooting 2.4.3 Main parts check Spec.
Troubleshooting 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor. Measure the resistance value of each winding by using the multi-meter.
Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4,T2B (℃--K) ℃ 126 K Ohm 115.266 ℃ 60 K Ohm 2.35774 ℃ 20 K Ohm 12.6431 ℃ -20 100 K Ohm 0.62973 -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5000 62 2.19073 102 0.59386 -17 96.3423 23 10.9731 63 2.11241 103 0.57683 -16 89.5865 24 10.4736 64 2.03732 104 0.56038 -15 84.2190 25 10.000 65 1.96532 105 0.54448 -14 79.3110 26 9.55074 66 1.89627 106 0.
Troubleshooting Appendix 2 Temperature Sensor Resistance Value Table for T5 (℃--K) ℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm -20 542.7 20 68.66 60 13.59 100 3.702 -19 511.9 21 65.62 61 13.11 101 3.595 -18 483 22 62.73 62 12.65 102 3.492 -17 455.9 23 59.98 63 12.21 103 3.392 -16 430.5 24 57.37 64 11.79 104 3.296 -15 406.7 25 54.89 65 11.38 105 3.203 -14 384.3 26 52.53 66 10.99 106 3.113 -13 363.3 27 50.28 67 10.61 107 3.025 -12 343.6 28 48.
Troubleshooting 2.Compressor checking Measure the resistance value of each winding by using the tester. Position Blue - Red 128 Resistance Value DA150S1C-20FZ DA250S2C-30MT TNB306FPGMC-L 0.95Ω(20℃) 0.55Ω(20℃) 0.
Troubleshooting 3. IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N. Digital tester Normal resistance value Digital tester Normal resistance value (+)Red (-)Black (+)Red (-)Black U N ∞ ∞ V U (Several MΩ) N (Several MΩ) P W V (+)Red W 4: Indoor AC Fan Motor Measure the resistance value of each winding by using the tester.
SERVICE MANUAL Multi Splits Series