Multi Split Cinco DCI Indoor Units Image Wall mounted Type Ducted Low Silhouette Floor / Ceiling Cassette Outdoor Units Model Model PNX 009 PNX 012 PNX 018 PNX 021 PNX 024 HFD 007 HFD 009 HFD 012 HFD 018 HAD 007 HAD 009 HAD 012 HAD 018 HAD 021 HAD 024 XLF 009 XLF 012 CK 009 CK 012 CK 018 CK 021 CK 024 PXD 009 PXD 012 PXD 018 PXD 021 PXD 024 DLF 009 DLF 012 DLF 018 DLF 021 DLF 024 DLS 018 DLS 021 DLS 024 CINCO 100 DCI YAZ5036-H11 REFRIGERANT HEAT PUMP R410A SM CINCO 1-A.
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ MAY 2010 Total number of pages in this publication is 148 consisting of the following: Page No. Revision No. # Page No. Revision No.
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The Cinco DCI Multi is a total Multi System in one unit: Duo/Trio/Quattro/Cinco. The multi-split inverter is a high level technology product for residential and commercial application offering comfort, low noise operation and energy saving. 1.2 Main Features 1.2.1 High Technology 1.2.2 1.3 Sine wave form in both OFAN and Compressor drives.
INTRODUCTION 1.4 Inbox Documentation Outdoor unit is supplied with its installation manual and flare type adaptor connectors. Each indoor unit is supplied with its own installation and operation manuals. 1.5 Matching Table R410A Indoor unit Type Indoor Unit Capacity [kW] (kBtu/h) Dimensions (W x D x H) mm Model LEX/ PNX Wall- Mounted 2.5 (9) 3.5 (12) 5.0 (18) 6.0 (21) 7.0 (24) ♦ 810x210x285 ♦ ♦ 1060x221x295 680x185x250 HFD/ DELTA 2.
INTRODUCTION 1.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.1 Outdoor Unit Specifications. Model Operation Mode Starting Current Circuit Breaker Current Power Supply Cinco 100 DCI / YAZ5036-H11 Cooling < 10 25 220-240V/ 1PH / 50Hz INDOOR A A V/Ph/Hz See DCI Single Electronic expansion valve Refrigerant control Compressor type Twin Rotary DC Inverter Model Sanyo C-7RVN153HOW Protection device Outdoor SW control, HPS, LPS Heat exchanger Hydrophilic corrugated fins ,Grooved tubes OUTDOOR Fan x No.
PRODUCT DATA SHEET 2.2 Outdoor Unit Capacity 2.2.1 Cinco (HAD) Model Operation Mode Capacity (2) Nominal (minimum–Maximum) Total Input E.E.R (Cooling) / C.O.P (Heating) Running Current (3) 2.2.2 ODU IDU Cooling Btu/hr 32,400 (13,650 -34,800) kW 9.5 (4.0-10.2) W 2,940 (780-3,500) W/W 3.05 A 13.0 ODU IDU Cinco 100 DCI / YAZ5036-H11 LEX 25+ LEX 25+ LEX 25 + LEX 25+ LEX 25 Btu/hr kW W W/W A Cooling 34,120 (14,710-37,530) 10.0(4.3-11.0) 2,940 (780-3,500) 3.15 13.
PRODUCT DATA SHEET 2.2.5 Duo (LEX 50) Model ODU IDU Operation Mode Capacity (2) Nominal (minimum–Maximum) Total Input E.E.R (Cooling) / C.O.P (Heating) Running Current (3) 2.2.6 Btu/hr kW W W/W A Cooling 30,710(9,030-37,530) 9.0 (2.6-11.0) 3,000 (590-3,160) 3.0 13.3 Heating 35,960 (9,030-39,240) 10.0 (2.6-11.5) 2,940 (590-3,160) 3.58 13.1 Duo (LEX 60) Model ODU IDU Operation Mode Capacity (2) Nominal (minimum–Maximum) Total Input E.E.R (Cooling) / C.O.P (Heating) Running Current (3) 2.2.
PRODUCT DATA SHEET 2.3 Indoor Units Data 2.3.1 PNX009 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Packaged weight Units per pallet Stacking height 2.3.
PRODUCT DATA SHEET 2.3.4 PNX021 DCI Specifications INDOOR Model Indoor Unit / Type Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D. Dimensions Weight Package Dimensions Packeged wight Units per pallet Stacking Height 2.3.
PRODUCT DATA SHEET 2.3.7 HFD009 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Packaged weight Units per pallet Stacking height 2.3.
PRODUCT DATA SHEET 2.3.10 HAD007 DCI Specifications Model Indoor Unit / Type INDOOR Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D. Dimensions Weight Package Dimensions Packeged wight Units per pallet Stacking Height 2.3.
PRODUCT DATA SHEET 2.3.13 HAD021 DCI Specifications INDOOR Model Indoor Unit / Type Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D. Dimensions Weight Package Dimensions Packeged wight Units per pallet Stacking Height 2.3.
PRODUCT DATA SHEET 2.3.16 XLF012 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Packaged weight Units per pallet Stacking height 2.3.
PRODUCT DATA SHEET 2.3.19 CK018 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Packaged weight Units per pallet Stacking height 2.3.
PRODUCT DATA SHEET 2.3.22 SX009 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Package weight Units per pallet Units stacking 2.3.
PRODUCT DATA SHEET 2.3.25 SX021 DCI Specifications INDOOR Model Indoor Unit / Type Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D. Dimensions Weight Package Dimensions Packeged wight Units per pallet Stacking Height 2.3.
PRODUCT DATA SHEET 2.3.28 DLF012 DCI Specifications Model Indoor Unit INDOOR Installation Method of Pipe Power supply Fan type & quantity Fan speeds Air flow(1) External static pressure Sound power level(2) Sound pressure level(3) Moisture removal Condenstate drain tube I.D Dimensions Net Weight Package dimensions Package weight Units per pallet Units stacking 2.3.29 DLF012 DCI DUCTED 220-240/1/50 Centifugal x 2 980/860/730 650/580/490 0-30 53/49/45 31/27/24 1.
PRODUCT DATA SHEET 2.3.31 DLF024 DCI Specifications INDOOR Model Indoor Unit / Type Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D. Dimensions Weight Package Dimensions Packeged wight Units per pallet Stacking Height 2.3.
PRODUCT DATA SHEET 2.3.34 DLS024 DCI Specifications INDOOR Model Indoor Unit / Type Installation Method of pipe Power Supply Fan Type & Quantity Fan speed Airflow(2) External static pressure Sound Power Level(3) Sound Pressure Level (4) Moisture removal Condensate Drain Tube I.D.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.1 Operating Limits Indoor Cooling Heating Voltage Outdoor Upper limit 32oC DB 23oC WB 46oC DB Lower limit 21oC DB 15oC WB -10oC DB Upper limit 27oC DB 24oC DB 18oC WB Lower limit 10oC DB -15oC DB -16oC WB 1PH 198 – 264 V 3PH N/A SM CINCO 1-A.
OUTLINE DIMENSIONS OUTLINE DIMENSIONS 4.1 Indoor Unit: PNX009 / PNX012 DCI MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL CEELING 18.5 810.0 MOUTING PLATE OUTLINE 30.0 167.5 167.5 100.0 MIN 4. INDOOR UNIT OUTLINE 83.0 83.0 42.0 42.0 100.5 100.5 285.0 8.0 8.0 93.0 70.0 TUBING WALL OPENING (FOR REAR ROUTING) 93.0 70.0 TUBING WALL OPENING (FOR REAR LEFT ROUTING) 210 811 285 AIR INTAKE AIR INTAKE AIR OUTLET Indoor Unit: PNX018 / PNX021 / PNX024 DCI 295 4.
OUTLINE DIMENSIONS 4.3 Indoor Units: HFD007 / HFD009 DCI 4.4 Indoor Unit: HFD012 DCI 4-2 SM CINCO 1-A.
OUTLINE DIMENSIONS Indoor Unit: HFD018 DCI MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL CEILING 483 203 60 Min50 4.5 INDOOR UNIT OUTLINE 42 76 295 177 60 88 225 88 440 900 TUBING WALL OPENING (FOR REAR ROUTING) TUBING WALL OPENING (FOR REAR LEFT ROUTING) 205 900 AIR INTAKE 295 AIR INTAKE AIR OUTLET 4.6 Indoor Unit: HAD007 / HAD009 DCI 676 250 188 SM CINCO 1-A.
OUTLINE DIMENSIONS 4.7 Indoor Units: HAD012 DCI 836 250 188 4.8 Indoor Units: HAD018 / HAD021 / HAD024 DCI 1060 295 219 4-4 SM CINCO 1-A.
OUTLINE DIMENSIONS 4.9 Indoor Unit: XLF009 / XLF012 DCI AIR OUTLET AIR OUTLET AIR OUTLET AIR OUTLET AIR INTAKE AIR INTAKE AIR INTAKE AIR INTAKE 4.10 Indoor Unit: CK009 / CK012 / CK018 / CK021 / CK024 DCI Unit Model 009/012 018/021/024 Main unit A Insulation B Front Step C Front width D 219 270 SM CINCO 1-A.
OUTLINE DIMENSIONS Indoor Unit: SX009 / SX012 SX018 / SX021 / SX024 DCI 4.12 Indoor Unit: DLF009 / DLF012 / DLF018 / DLF021 / DLF024 DCI A B C 59 4.11 565 4-6 21 160 200 59 27 629 (640 With air filter) Nominal Capacity 2.5 -5.0 kW 6.0-7.2 kW A B C 750 696 790 1050 996 1090 SM CINCO 1-A.
OUTLINE DIMENSIONS 4.13 Indoor Unit: DLS018 / DLS021 / DLS024 DCI K L 73 80 F G J I H 36 359 E D 61 19 A B C Model A B C D E F G H I J K L DLS018 / DLS021 / DLS024 790 653 749 758 797 256 195 702 599 684 162 242 4.14 Outdoor Units: Cinco 100 DCI SM CINCO 1-A.
PERFORMANCE DATA 5. PERFORMANCE DATA 5.1 Outdoor Unit Cinco 100 DCI Combinations (Delta + LEX) 5.1.1 Cooling Model 7 9 12 18 21 24 7+7 7+9 7+12 7+18 7+21 7+24 9+9 9+12 9+18 9+21 9+24 12+12 12+18 12+21 12+24 18+18 18+21 18+24 21+21 21+24 24+24 7+7+7 7+7+9 7+7+12 7+7+18 7+7+21 7+7+24 7+9+9 7+9+12 7+9+18 7+9+21 7+9+24 7+12+12 7+12+18 7+12+21 7+12+24 7+18+18 7+18+21 7+18+24 7+21+21 7+21+24 9+9+9 9+9+12 9+9+18 9+9+21 9+9+24 Power Consumption [kW] Cooling Capacity [KW] EER A B C D E Nom. Min.
PERFORMANCE DATA 9+12+12 9+12+18 9+12+21 9+12+24 9+18+18 9+18+21 9+18+24 9+21+21 9+21+24 12+12+12 12+12+18 12+12+21 12+12+24 12+18+18 12+18+21 7+7+7+7 7+7+7+9 7+7+7+12 7+7+7+18 7+7+7+21 7+7+7+24 7+7+9+9 7+7+9+12 7+7+9+18 7+7+9+21 7+7+9+24 7+7+12+12 7+7+12+18 7+7+12+21 7+7+18+18 7+9+9+9 7+9+9+12 7+9+9+18 7+9+9+21 7+9+9+24 7+9+12+12 7+9+12+18 7+9+12+21 7+9+18+18 7+9+18+21 7+12+12+12 7+12+12+18 7+12+12+21 9+9+9+9 9+9+9+12 9+9+9+18 9+9+9+21 9+9+9+24 9+9+12+12 9+9+12+18 9+9+12+21 9+9+18+18 9+12+12+12 9+12+12+18
PERFORMANCE DATA 7+7+7+7+12 7+7+7+7+18 7+7+7+7+21 7+7+7+9+9 7+7+7+9+12 7+7+7+9+18 7+7+7+12+12 7+7+9+9+9 7+7+9+9+12 7+7+9+9+18 7+7+9+12+12 7+9+9+9+9 7+9+9+9+12 7+9+9+9+18 7+9+9+12+12 9+9+9+9+9 9+9+9+9+12 9+9+9+9+18 9+9+9+12+12 Power Consumption [kW] Cooling Capacity [KW] Model EER A B C D E Nom. Min. Max. Nom. Min. Max. Nom. 1.7 1.5 1.4 1.7 1.6 1.5 1.6 1.7 1.6 1.4 1.5 1.6 1.5 1.3 1.3 2.0 1.9 1.8 1.9 1.7 1.5 1.4 1.7 1.6 1.5 1.6 1.7 1.6 1.4 1.5 2.1 2.0 1.7 1.7 2.0 1.9 1.8 1.9 1.7 1.5 1.4 1.
PERFORMANCE DATA 5.1.2 Heating 7 9 12 18 21 24 7+7 7+9 7+12 7+18 7+21 7+24 9+9 9+12 9+18 9+21 9+24 12+12 12+18 12+21 12+24 18+18 18+21 18+24 21+21 21+24 24+24 7+7+7 7+7+9 7+7+12 7+7+18 7+7+21 7+7+24 7+9+9 7+9+12 7+9+18 7+9+21 7+9+24 7+12+12 7+12+18 7+12+21 7+12+24 7+18+18 7+18+21 7+18+24 7+21+21 7+21+24 9+9+9 9+9+12 9+9+18 9+9+21 9+9+24 9+12+12 9+12+18 9+12+21 9+12+24 9+18+18 5-4 Power Consumption [kW] Heating Capacity [KW] Model COP A B C D E Nom. Min. Max. Nom. Min. Max. Nom. 2.8 3.
PERFORMANCE DATA 9+18+21 9+18+24 9+21+21 9+21+24 12+12+12 12+12+18 12+12+21 12+12+24 12+18+18 12+18+21 7+7+7+7 7+7+7+9 7+7+7+12 7+7+7+18 7+7+7+21 7+7+7+24 7+7+9+9 7+7+9+12 7+7+9+18 7+7+9+21 7+7+9+24 7+7+12+12 7+7+12+18 7+7+12+21 7+7+18+18 7+9+9+9 7+9+9+12 7+9+9+18 7+9+9+21 7+9+9+24 7+9+12+12 7+9+12+18 7+9+12+21 7+9+18+18 7+9+18+21 7+12+12+12 7+12+12+18 7+12+12+21 9+9+9+9 9+9+9+12 9+9+9+18 9+9+9+21 9+9+9+24 9+9+12+12 9+9+12+18 9+9+12+21 9+9+18+18 9+12+12+12 9+12+12+18 9+12+12+21 12+12+12+12 7+7+7+7+7 7+7+7+
PERFORMANCE DATA 7+7+7+9+18 7+7+7+12+12 7+7+9+9+9 7+7+9+9+12 7+7+9+9+18 7+7+9+12+12 7+9+9+9+9 7+9+9+9+12 7+9+9+9+18 7+9+9+12+12 9+9+9+9+9 9+9+9+9+12 9+9+9+9+18 9+9+9+12+12 Power Consumption [kW] Heating Capacity [KW] Model COP A B C D E Nom. Min. Max. Nom. Min. Max. Nom. 1.8 2.0 2.0 1.9 1.7 1.8 1.9 1.8 1.6 1.6 2.4 2.3 2.0 2.2 1.8 2.0 2.0 1.9 1.7 1.8 2.5 2.3 2.1 2.1 2.4 2.3 2.0 2.2 1.8 2.0 2.5 2.4 2.2 2.3 2.5 2.3 2.1 2.1 2.4 2.3 2.0 2.2 2.3 2.5 2.5 2.4 2.2 3.1 2.5 2.3 2.1 2.1 2.4 2.3 2.
PERFORMANCE DATA 5.2 LEX 25 DCI 5.2.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.
PERFORMANCE DATA 5.2.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 TC PI TC PI TC PI TC PI TC 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 PI 0.89 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 TC PI TC PI TC PI TC PI 1.04 0.94 1.10 1.
PERFORMANCE DATA 5.3 LEX 35 DCI 5.3.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.
PERFORMANCE DATA 5.3.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 15 20 25 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.
PERFORMANCE DATA 5.4 LEX 50 DCI 5.4.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.4.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 0.32 0.80 0.47 0.89 0.58 0.96 0.63 0.99 0.67 1.
PERFORMANCE DATA 5.5 LEX 60 DCI 5.5.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.5.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.6 LEX 70 DCI 5.6.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.6.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.7 CN 25 DCI 5.7.1 Cooling Capacity Factors - Unit A,B,C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.
PERFORMANCE DATA 5.7.3 Heating Capacity Factors - Unit A, B ,C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 15 20 25 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.
PERFORMANCE DATA 5.8 CN 35 DCI 5.7.1 Cooling Capacity Factors - Run Mode Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.
PERFORMANCE DATA 5.7.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed OD COIL ENTERING AIR DB/ WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 15 20 25 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.
PERFORMANCE DATA 5.9 CN 50 DCI 5.9.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.08 1.
PERFORMANCE DATA 5.9.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.32 0.80 0.47 0.89 0.58 0.96 0.63 0.99 0.67 PI 0.92 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 TC PI TC PI TC PI TC PI 1.07 0.95 1.12 0.97 1.18 0.
PERFORMANCE DATA 5.10 CN 60 DCI 5.10.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.10.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA 15-24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC (Protection Range) PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.11 CN 70 DCI 5.11.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.11.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. w ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.12 PXD 25 DCI 5.12.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.
PERFORMANCE DATA 5.12.3 Heating Capacity Factor - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 1.00 1.00 1.06 1.06 1.12 1.
PERFORMANCE DATA 5.13 PXD 35 DCI 5.13.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.
PERFORMANCE DATA 5.13.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] ID COIL ENTERING AIR DB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 PI 0.89 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 1.04 0.94 1.10 1.00 1.16 1.05 1.00 1.00 0.96 1.06 1.01 1.12 1.07 1.
PERFORMANCE DATA 5.14 PXD 50 DCI 5.14.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.14.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.32 0.80 0.47 0.89 0.58 0.96 0.63 0.99 0.67 PI 0.92 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 TC PI TC PI TC PI TC PI 1.07 0.95 1.12 0.97 1.18 0.
PERFORMANCE DATA 5.15 PXD 60 DCI 5.15.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.15.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.16 PXD 70 DCI 5.16.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.
PERFORMANCE DATA 5.16.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.17 Tubing Length Capacity Correction Factor 5.17.1 Cooling Tubing Length Capacity Ratio - Cooling (1 Unit) 1.06 Capacity Ratio 1.01 0.96 0.91 0.86 0.81 0.76 0 5.17.2 5 10 15 Tubing Length [m] 20 25 30 25 30 Heating Tubing Length Capacity Ratio - Heating (1 Unit) 1.06 Capacity Ratio 1.01 0.96 0.91 0.86 0.81 0.76 0 5 SM CINCO 1-A.
PERFORMANCE DATA 5.18 Model Correction Factors (FM) Capacity Model LEX DCI INV DELTA DCI INV HAD DCI INV TOP DCI INV CN DCI INV PXD DCI INV LSN DCI INV DNG DCI INV 15.19 Power input Cooling Heating Cooling Heating 1.00 0.88 0.88 0.88 1.03 1.00 1.05 1.05 1.00 0.88 0.88 0.88 1.07 1.00 1.07 1.07 1.00 0.93 0.93 0.93 1.01 1.00 0.95 1.10 1.00 0.93 0.93 0.93 1.10 1.00 0.90 1.
PRESSURE CURVES 6. OPERATING CURVES 6.1 Cooling – Technician Mode Suction Pressure - Cooling (Technician Mode) (5xLEX009 ; 5m each) Bar(g) 14.0 13.0 12.0 32/23 11.0 29/21 27/19 10.0 24/17 22/15 9.0 8.0 7.0 6.0 10 15 20 25 30 35 40 45 40 45 Outdoor DB Temperature [C] Discharge Pressure - Cooling (Technician Mode) (5xLEX009 ; 5m each) Bar(g) 40.0 35.0 32/23 29/21 30.0 27/19 24/17 25.0 22/15 20.0 15.0 10 SM CINCO 1-A.
PRESSURE CURVES 6.2 Heating – Technician Mode Suction Pressure - Heating (Technician Mode) (5xLEX009 ; 5m each) Bar(g) 12.00 11.00 10.00 9.00 25 8.00 20 15 7.00 6.00 5.00 4.00 3.00 -15 -10 -5 0 5 10 15 20 15 20 Outdoor WB Temperature [C] Discharge Pressure - Heating (Technician Mode) (5xLEX009 ; 5m each) Bar(g) 30.00 28.00 26.00 24.00 25 20 22.00 15 20.00 18.00 16.00 14.00 -15 6-2 -10 -5 0 5 Outdoor WB Temperature [C] 10 SM CINCO 1-A.
PRESSURE CURVES 6.3 Tubing Length correction Factor Tubing Length Pressure Ratio - Cooling 1.02 1.01 1.01 Cooling Pd Cooling Ps 1.00 1.00 0.99 0.99 0.98 0.98 0 10 20 30 40 50 Total Tubing Lengtht [m] 60 Discharge Pressure Ratio Suction Pressure Ratio 1.02 70 1.02 1.01 1.01 1.00 1.00 Heating Ps 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.96 Discharge Pressure Ratio Suction Pressure Ratio Tubing Length Pressure Ratio - Heating 1.02 0.95 0.95 Heating Pd 0.94 0.94 0 6.
PRESSURE CURVES 6.5 Calculation Example Outdoor Unit Indoor Combination Operation Mode Conditions Indoor Conditions Oudoor Tubing length Cinco DCI LEX009+LEX009+LEX009+CK009+LEX018 Cooling Mode 22°CDB/15°WB 30°CDB 20m+10m+10m+5m+15m Cooling Pressure calculation: Pressure [Barg] = Nominal x FC x FT Unit Code Room A – LEX009 Room B – LEX009 Room C – LEX009 Room D – CK009 Room E – LEX018 ODU Code (Total) 1.0 1.0 1.0 1.0 2.0 6.
SOUND LEVEL CHARACTERISTICS 7. SOUND LEVEL CHARACTERISTICS 7.1 Outdoor Units 1.0 m Center for Unit Figure 1 7.2 Sound Pressure Level Spectrum (Measured as Figure 1) CINCO 100 DCI Heating NC-70 NC-60 NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 BAND CENTER FREQUENCIES, Hz SM CINCO 1-A.1 GB OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.
ELECTRICAL DATA 8. ELECTRICAL DATA 8.1 Cinco 100 DCI Power Supply Connected to Maximum Current Inrush Current 1 PH, 220-240 VAC, 50Hz Outdoor 25 A 35 A Starting Current Circuit breaker Power supply wiring - No. x cross section Interconnecting cable - No. x cross section 11 A 25 A 3 X 4.0 mm2 4 X 1.5 mm2 (For each IDU) Note: Inrush current is the current when power is up. (charging the DC capacitors at outdoor PCB). Starting current is the current at comp; start up.
WIRING DIAGRAMS & ELECTRICAL CONNECTIONS 9. WIRING DIAGRAMS & ELECTRICAL CONNECTIONS 9.
WIRING DIAGRAMS & ELECTRICAL CONNECTIONS 9.2 1PH UNIT POWER SUPPLY TO OUTDOOR OUTDOOR UNIT To unit A N To unit B LC N LNC 2 LC L NC 4x1.5 To unit C N To unit D LC N L NC 4x1.5 LC L NC 4x1.5 Power supply to outdoor unit To unit E N N L LC L NC 4x1.5 4x1.
REFRIGERATION DIAGRAMS 10. REFRIGERATION DIAGRAMS 10.1 CINCO 100 DCI Outdoor Unit Refrigerant System Diagram Oil cappilary tube 2.5mmx0.6mmx1000mm Filling tube P LPS RGE 1/2" RGD 1/2" RGC 3/8" RGB 3/8" RGA 3/8" M RLE 1/4" M RLD 1/4" M RLC 1/4" M RLB 1/4" RLA 1/4" HPS CCT P Main accumulator Sub accumulator 2.
TUBING CONNECTIONS 11. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8. SM CINCO 1-A.
CONTROL SYSTEM 12. CONTROL SYSTEM 12.
CONTROL SYSTEM 12.2 Product Overview 12.2.1 Block Diagram Compressor Driver Line Filter 230VAC M Speed HST AC Current DC Current Driver Control M ODU Controller OFAN Control DMSMP CINCO IDU Comm Temp. Inputs RGT x5 RLT x5 IDU Communication EEV Output Temp.
CONTROL SYSTEM 12.2.2 Controller overview 12.2.2.1 Main Controller Outdoor Unit Driver Comm. Inrush / DMSMP Comm Power Supply + Ground IDU-ODU Comm. Fuse 3.15A DIP-SWITCHES OFAN_UP LEDs ALARM Power Shedding STAND BY NIGHT OFAN_DN HIGH PRESSURE SWITCH LOW PRESSURE SWITCH RV OMT OCT BASE HEATER CRANK CASE HEATER DISPLAY HMI (7-segments) 12.2.2.
CONTROL SYSTEM 12.2.3 Control Features 12.2.3.1 Compressor DC brush less and sensor less motor inverter driven compressor. 12.2.3.2 Compressor Drive DC inverter module to drive compressor. 12.2.3.3 Outdoor Fan DC brush less motor(s) drive the outdoor unit fan(s). 12.2.3.4 RV Reverse Valve set the direction of refrigerant flow in the system, thus setting the operation mode for cooling or heating. When the solenoid is powered, system will work in heat mode. 12.2.3.
CONTROL SYSTEM 12.2.3.9 Base Heater Heating element designed to melt any ice that is accumulated on the outdoor unit base during low heating operation. The base heater will be working only when RV is “ON” according to the following graph: Base Heater OFF ON 0 2 OAT When OAT is faulty the base heater will be “ON” continuously in HEAT mode. 12.2.3.10 Cranckcase Heater Heating element designed to heatup the compressor oil cranck case during low outdoor ambient temeratures.
CONTROL SYSTEM 12.3.2 Communication with Indoor Unit 12.3.2.1 Communication Failures Definition 12.3.2.1.1 ‘Bad Communication’ fault The system keeps a balance of a good/bad communication packet ratio. When the ratio becomes high the system enters ‘Bad Communication’ fault. The system recovers from that fault when the ratio becomes small again. When in ‘Bad Communication’ fault, system continues its normal operation and fault code is shown in diagnostics. 12.3.2.1.2 1. 2.
CONTROL SYSTEM The following combinations show the allowed and not allowed capacity group: ODU Model Communication channel 0 12.3.3.4 Multi AB (4HP DCR and CINCO) Single Com Channel 1 Com Channel 2 Com Channel 3 Com Channel 4 Com Channel 5 Is it allowed capacity group? Indoor Capacity 1 2 3 No Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes No No No No No No No No No No Yes Yes 4 Yes No No No Yes Yes Indoor Total Capacity Test This test is performed only for Multi split units.
CONTROL SYSTEM 12.3.5.2 The following thermistor faults are detected by the system: Thermistor Thermistor is Disconnected OCT OAT CTT HST OMT RGT RLT ICT RAT 12.3.5.
CONTROL SYSTEM 12.4.2.2 Indoor fan control - Cool Mode When T/H/M/L speed is set by user, IFAN will work in constant requested speed. When Auto-Fan speed is set by user, IFAN speed will be set according to LOAD(n) as in the following graph: IFAN Speed IFTURBO IFHIGH IFMED IFLOW IFVLOW 25 12.4.2.3 Indoor fan control – Heat Mode 12.4.2.3.
CONTROL SYSTEM 12.4.3 Cooling Mode 12.4.3.1 Cooling Mode – General a. Mode Definition Mode: COOL, AUTO (at Cooling) Temp: Fan: b. Selected desired temperature. LOW, MED, HIGH, TURBO, AUTO. Timer: Any I-FEEL: ON or OFF Room Temperature, RT, is detected by: RAT in normal operation, or RCT (R/C sensor) in I-FEEL mode. c. 12.4.3.2 Indoor Coil Temp is detected by ICT. Control Functions a. COMP Operation In general – the operation is set by the NLOAD calculation in indoor unit side.
CONTROL SYSTEM 12.4.4 Heating Mode 12.4.4.1 Heating - General a. Mode Definition Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: LOW, MED, HIGH, TURBO, AUTO. Timer: Any I-FEEL: ON or OFF b. Room Temperature, RT, is detected by: RAT in normal operation, or RCT (R/C sensor) in I-FEEL mode. c. 12.4.4.2 Indoor Coil Temp is detected by ICT. Control Functions a. COMP Operation In general – the operation is set by the NLOAD calculation in indoor unit side.
CONTROL SYSTEM 12.4.4.4 Temperature Compensation A compensation value of 2-4 degrees is reduced from room temperature reading (except when in I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and for coil heat radiation on room thermistor. The temperature compensation can be enabled/disabled by closing/opening J2 on the indoor unit controller. No compensation will be activated in Forced operation modes. 12.4.4.
CONTROL SYSTEM 12.4.6 Dry Mode 12.4.6.1 DRY - General a. 12.4.6.2 Mode Definition Mode: DRY Temp: Selected desired temperature Fan: LOW (automatically selected by software) Timer: Any I-FEEL: ON or OFF Control function a. b. COMP Operation In general – the operation is set by the NLOAD calculation in indoor unit side. Other rules are according to section 12.5.1. OFAN Operation In normal operation OFAN operates together with the COMP. Other rules are according to section 12.5.3. c.
CONTROL SYSTEM 12.4.7 Sleep Mode 12.4.7.1 Sleep Mode - General a. 12.4.7.2 Any Temp: Selected desired temperature IFan: Any Timer: See below I-FEEL: ON or OFF Control function o o o o o o o 12.4.7.3 Mode Definition Mode: The Sleep mode is activated by using the SLEEP button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort for the sleeping user. Sleep is treated as TIMER function.
CONTROL SYSTEM 12.4.9 Indoor Units Operation when Indoor Unit Mode is Different than Outdoor Unit Mode Open louvers according to user selection. Indoor fan is forced to OFF. 12.4.10 Heating Element Control Heating element can be turn on if high LOAD is more then 80% and Indoor Coil temperature is less then 45C. The heating element will be off when LOAD is less then 50% OR if Indoor Coil temperature is more then 50C. 12.4.
CONTROL SYSTEM STBY Cool Heat Auto Fan Dry OFF SPT SPT SPT SPT SPT OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF User setting IFAN speed User setting IFAN speed User setting IFAN speed User setting IFAN speed User setting IFAN speed OFF (Low) OFF (Med) OFF (High) OFF (Turbo) OFF (Auto) Backlight(red) OFF OFF ON ON ON OFF Backlight(green) OFF ON OFF ON ON ON 12.4.14.
CONTROL SYSTEM 12.5 Run Mode Run mode is the default operation mode of the system. This is the standard operation mode that is active in field application (at customer site). System can go from run mode to other operation modes through keyboard or serial ports. 12.5.1 Mode Setting 12.5.1.1 General Rules Thermal mode defines the ODU operation mode. There are three possible operation modes: 1. STBY – Standby mode 2. COOL - the unit operate at cooling cycle 3.
CONTROL SYSTEM 12.5.2.1 Compressor Min On/Off time Compressor minimum ON and OFF time is 3 minutes except during protections. 12.5.2.2 Compressor Startup When started, compressor speed reaches certain level (usually 30÷40 RPS) and will not go below that during the first 5 minutes except when compressor is forced OFF. 12.5.2.3 Compressor start up fail If the compressor does not succeed to complete the startup procedure, it will report a compressor lock fault code.
CONTROL SYSTEM ODUCodeH setting: ODUCodeH E D C B A -15 -5 2 15 Point (Set by the graph above) 21 24 OAT ODUCodeH A B C (or OAT faulty) D E 2.0 2.5 3.5 4.0 4.5 ODUCodeC setting: ODUCodeC ALL 3.0 12.5.3 EEV Control 12.5.3.1 EEV General Rules The EEV is controlled to keep the discharge superheat temperature within preset control values. 12.5.3.
CONTROL SYSTEM 12.5.3.6 EEV correction definition The following table describes the closed loop control type (EEV correction): Indoor Active Indoor Super Heat Control AND Discharge Super Heat Control. Indoor Sub-cooling AND Discharge Super Heat Control. Mode Cool Heat 12.5.3.7 Inactive NA Flow Balance Accumulative correction value storage For each combination of active IDUs, the accumulated EEV correction value (for each IDU) will be stored in the memory.
CONTROL SYSTEM 12.6.2 IDU Protections ICT Value Indoor Coil Indoor Coil Defrost Over Heating Protection Protection ICT < -2 -2 ≤ ICT < 0 0 ≤ ICT < 2 2 ≤ ICT < 4 4 ≤ ICT < 6 6 ≤ ICT < 8 8 ≤ ICT 12.6.
CONTROL SYSTEM 12.6.4.2 Deicing Protection Procedure OCT 12 0 Threshold COMP ON T1 T2 T1 max. 12 minutes RV COOL OFAN DT HEAT T3 T3 ON OFF EEVDeicerOpen EEV Any T1 = T2 = 36 seconds, T3 = 6 seconds 12.6.5 Condensate Water over Flow Protection Each of the pins P1, P2, P3 can have two options: 1 – When it is shorted with P4 0 – When it is not shorted to P4 12.6.5.1 3 Level Logic Used in Floor/Ceiling models. P2 P3 Level 0 1 1 0 0 0 1 1 L0 L1 L2&3 L4 12-22 SM CINCO 1-A.
CONTROL SYSTEM Water Level LEVEL4 LEVEL2&3 LEVEL1 ON Pump OFF ANY NLOAD 0 On Overflow signal Off to ODU BLINK OPER LED NORMAL 12.6.5.2 1 Level Logic Used in all models except for Floor/Ceiling models. P2 P3 Level Don’t care Don’t care 1 0 Normal Overflow Overflow when unit is ON Overflow Water Level Overflow when unit is OFF Normal ON OPER LED OFF BLINK ANY NLOAD NLOAD is forced to 0 0 ON PUMP OFF 8 min SM CINCO 1-A.
CONTROL SYSTEM 12.6.6 High/Low Pressure Protection Whenever high or low pressure accures in the system which extend beind the system pre-defined limits, the high and low pressure switchs turns on (short) and stops the compressor until these limits are redrawn. Fault code error 8 (HPS) or 9 (LPS) will be shown until compressor will resume operation. 12.7 Installation Test Mode 12.7.1 Test Objectives 12.7.2 12.7.3 Find tube-communication wires mismatch.
CONTROL SYSTEM Electrical Power Up IsInstTestCompleted=1 No Yes Blink “it” 1 hr passed? Yes Else No Enter or ESC is pressed? ESC Present Normal HMI Enter Start Installation test 4. 5. 6. During the test, the unit will show count down counter (in minutes). The test maximum time is 20 minutes. When the test is finished, the system will show the test result, pass or fail. You can scroll the menu to observe: a. Observe the matrix result b. Guide for problem correction. 7.
CONTROL SYSTEM How to interpret the results (pf sub menu): Test Result (pf) 12.7.9 Interpretation NUL PAS FAL The test has never been done before. The test is pass The test is fail OAT Outdoor air temperature is lower than 5 degrees. The installation test cannot be done. IDU The selected number of the installed indoor units by the technician does not match the number of indoor units detected by the system.
CONTROL SYSTEM Examples: Problem Correction (Crt) # 1,2 3,4 5,6 7,8 HMI Display 2--:Cb 3--:Cc 1--:Cd 4--:CA HMI Display 1--:Cb 2--:CA HMI Display 4--:Cd 1--:Cb 2--:Cc 4--:CA EA--:o HMI Display 1--:CA 2--:Cb 3--:Cd 4--:Cc Ec--:c HMI Display Technician Interpretation Keep wire 2 on communication channel CB Keep Wire 3 on communication channel CC Move wire 1 to communication channel CD Move Wire 4 to communication channel CA Technician Interpretation Move wire 1 to communication channel CB Move Wire 2
CONTROL SYSTEM Stored Matrix Type [Rows, Column] 2x2 3x3 4x4 How to present? Repeat: r1(keep 2 sec) X1Y1 (keep 2 sec) Repeat: r2 (keep 2 sec) X2Y2 (keep 2 sec) Repeat: r1 (keep 2 sec) X1Y1Z1 ( keep 2 sec) Repeat: r2 (keep 2 sec) X2Y2Z2 (keep 2 sec) Repeat: r3 (keep 2 sec) X3Y3Z3 (keep 2 sec) Repeat: r1 (keep 2 sec) X1Y1Z1 (keep 2 sec) W1 (keep 2 sec) Repeat: r2 (keep 2 sec) X2Y2Z2 (keep 2 sec) W2 (keep 2 sec) Repeat: r3 (keep 2 sec) X3Y3Z3 (keep 2 sec) W3 (keep 2 sec) Repeat: r4 (k
CONTROL SYSTEM 12.9 User Interface 12.9.1 User interface description o The user interface uses three 7 segments, and 4 keys. o Keys, The 4 keys are: - Scroll - used to scroll between options (up and down) Up - Select - use to select an option - Escape - Will go up one level in the menu Esc Select o The user interface concept is Tree menus. o Active selection or status will be indicated by a dot at the right side of the Down third digit. 12.9.
CONTROL SYSTEM 12.9.3 Menus 12.9.3.
CONTROL SYSTEM o Technician Test mode is exited after 60 minutes from entry. o All the menus, except technician menus- Status, Technician Test and their sub menus, are automatically exited to the main menu after 1 continuous minute out of any press. o When Technician test cool or heat menu is selected, it will blink constantly until this menu is escaped. o Pressing select and escape buttons together when in RST for more than 5 seconds will restore only the parameters of the factory settings.
CONTROL SYSTEM 12.9.3.2 Status (Sub Menu) Status (Stt) IDU ICT ICT-A ICT-B ICT-C ICT-D ICT-E Operation Mode Operation Mode-A Operation Mode-B Operation Mode-C Operation Mode-D Operation Mode-E Load Load-A Load-B Load-C Load-D Load-E Capacity Code Code-A Code -B Code -C Code -D Code -E Family Family -A Family -B Family -C Family -D Family -E Model Model -A Model -B Model -C Model -D Model -E 12-32 SM CINCO 1-A.
CONTROL SYSTEM ODU Operation Mode OFAN Up OFAN Down RV Speed CTT OMT OCT HST OAT RGT-A RGT-B RGT-C RGT-D RGT-E RLT-A RLT-B RLT-C RLT-D RLT-E EEV A EEV B EEV C EEV D EEV E Power (System) AC Current DC Current ODU Model SW version Timer Compressor Time Notes: For the temperature display, when a thermistor is shorted or disconnected it shows FLT (FLt), when it is disabled it shows DIS (dis).
CONTROL SYSTEM 12.10 Jumper/DIP-Switch Setting 12.10.1 Jumper/DIP-Switch Definition 0 = Open (Disconnected) 1 = Close (Shorted) 12.10.2 IDU Jumpers/DIP-Switch 12.10.2.1 Self test Jumper/DIP – J1 Position Status Description 0 1 Open (Disconnected) Close (Shorted) Normal Operation (Default) Self Test enabled Used for internal production line testing. For normal use must be set to OFF (0). 12.10.2.
CONTROL SYSTEM 12.10.2.6 Installation height /DIP – J12/13 Installation Height designation Installation Height H0 H1 (default) H2 H3 J13 J12 2.1-2.7m 2.7-3.3m >3.3m 0 0 1 0 1 0 Reserved 1 1 12.10.3 ODU Jumpers 12.10.3.1 Self test Jumper/DIP – J1 Position Status Description 0 1 Open (Disconnected) Close (Shorted) Normal Operation (Default) Self Test enabled Used for internal production line testing. For normal use must be set to OFF (0). 12.10.3.
CONTROL SYSTEM RC-3 12.11 System Parameters 12.11.1 General Parameters for All Models # 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 12. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30.
CONTROL SYSTEM # 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 12.11.2 № 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 12. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. Name ICTOH4 ICTOH5 ICTOH6 EEVLearning EEVTimeSingleDSH EEVTimeSingleCTT EEVTimeMultiSHC EEVTimeMultiDSHC EEVTimeMultiSCH EEVTimeMultiDSHH EEVTimeMultiFBH UpToDownHzUp PSFactor Default Value Units 55 58 61 1 30 40 30 30 30 30 60 1 0.
CONTROL SYSTEM № Name AB Unit 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59. 60. 61. 62. 63. 64. 65. 66. 67. 68. 69. 70. 71. 72. 73. 74. 75. 76.
CONTROL SYSTEM 12.11.3.1 Model Depended Parameters: 12.11.3.1.
CONTROL SYSTEM 12.11.3.1.3 Wall Mounted Models- Top Parameter name 25 35 Model NLOAD limits as a function of selected indoor fan speed MaxNLOADIF1C 47 42 MaxNLOADIF2C 70 59 MaxNLOADIF3C 127 127 MaxNLOADIF4C 127 127 MaxNLOADIF5C 127 127 Indoor Fan speed IFVLOWC 400 400 IFLOWC 450 450 IFMEDC 490 510 IFHIGHC 520 540 IFTURBOC 570 590 IFVLOWH 400 400 IFLOWH 450 450 IFMEDH 490 510 IFHIGHH 520 590 IFTURBOH 620 820 12.11.3.1.
CONTROL SYSTEM 12.11.3.1.
TROUBLESHOOTING 13. TROUBLESHOOTING 13.1 Precaution, Advise and Notice Items 13.1.1 High voltage in Indoor and Outdoor unit electrical assembly Open the Outdoor unit controller assembly only after one minute from power off. Whole controller assembly, including the wires, connected to the Outdoor unit may have the potential hazard voltage when power is on. Touching the Outdoor unit controller assembly may cause an electrical shock.
TROUBLESHOOTING 13.2 № General System Failures and Corrective Actions SYMPTOM / PROBLEM PROBABLE CAUSE Indoor unit Indoor unit power supply 1 No Power supply indicator (Red LED) does not light up. Miss-wiring 2 Fuse burned in indoor unit controller 3 Indoor unit does not respond to remote control message 4 Indoor unit responds to remote control message but Operate indicator (Green LED) does not light up Check supply voltage to main terminals L and N with volt meter.
TROUBLESHOOTING № SYMPTOM / PROBLEM 11 Compressor does not start operation 12 Cooling capacity is not sufficient 13 Heating capacity sufficient 14 Compressor is over heated 15 Compressor stops many times during operation 16 Not all units are operating 17 Unit is cooling while in heat mode SM CINCO 1-A.
TROUBLESHOOTING № 18 19 20 21 22 23 13.3 SYMPTOM / PROBLEM PROBABLE CAUSE CORRECTIVE ACTION Compressor is generating Phase order to Check compressor phase order abnormal noise compressor is wrong Compressor internal Replace compressor (14.1.11.) parts wearing Check all piping connections Check compressor rubbers are fixed well Vibration Check all screws on unit metal chassis are tightened Check that no piping is in contact with each other or with other parts.
TROUBLESHOOTING № Problem AO 5 4 3 2 1 1 OCT is shorted/disconnected Yes 0 0 0 0 1 2 CTT is shorted/disconnected Yes 0 0 0 1 0 3 HST is shorted/disconnected Yes 0 0 0 1 1 4 OAT is shorted/disconnected Yes 0 0 1 0 0 5 OMT is shorted/disconnected Yes 0 0 1 0 1 6 RGT is shorted/disconnected Yes 0 0 1 1 0 7 RLT is shorted/disconnected Yes 0 0 1 1 1 8 High pressure protection Yes 0 1 0 0 0 9 Low pressure protection Yes 0 1 0 0 1 10
TROUBLESHOOTING 13.4.2 № 1 2 3 4 5 6 7 8 Outdoor unit diagnostics and corrective actions Fault Name OCT short/disconnect CTT short/disconnect HST short/disconnect OAT short/disconnect OMT short/disconnect RGT short/disconnect RLT short/disconnect High pressure protection Fault Description Thermistor damaged not connected Corrective Action or Check Thermistor (13.5.
TROUBLESHOOTING № 22 23 24 25 26 27 28 29 30 31 Fault Name Compressor Over Heating Fault Description Corrective Action Compressor stopped due to over Normally no action is required heat protection If the problem persists for more than twice on each hour, check for refrigerant leak and thermodynamic operation (13.
TROUBLESHOOTING Channel LED LEDO LED4 LED3 LED2 LED1 The relevant LEDi will be ON. The relevant LEDi will be Off.
TROUBLESHOOTING № 27 28 29 30 31 Fault Name Using EEPROM data Model A Model B Model C Model D 5 4 3 2 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 0 0 1 1 1 0 1 0 1 1 - ON; 0 - OFF Only one code is shown. Order of priority is lower to the higher number. Diagnostics is continuously ON as long power is on. 13.4.5 Indoor unit diagnostics and corrective actions №.
TROUBLESHOOTING 13.5 Procedures for checking Main Parts 13.5.1 Discharge DC Voltage High voltage!!! Wait for DC voltage to be discharged before re touching any part of the driver to avoid electric shock. Check to ensure that DC voltage has reduced to below 50VDC, if not, keep waiting until it does. 13.5.2 Checking Mains Voltage Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected.
TROUBLESHOOTING 13.5.7 Checking Outdoor Fan Motor This type of fault may occur during very high winds outdoors that may stop the fan rotation for short periods. If so, need to relocate the outdoor unit to a more protected place from winds or install measure of air deflection in front of the fan outlets. 1) Check OFAN connections - Repair if needed.
TROUBLESHOOTING 13.5.8 Checking Compressor 1) Check Compressor connections - Repair if needed. 2) Check the resistance between the three phases – all three coil resistances should be the same: around 0.788Ω. 3) Check the compressor current while operating to be the same on each wire - In case of abnormal current (no current or excessive current), the problem could be of driver or compressor – if driver is checked to be operating well (13.5.5), replace the compressor. COMPESSOR U W V 18.
TROUBLESHOOTING OAT, OCT, OMT, ICT, RAT, RGT, RLT, HST Chart R-T Table R25°C=10k: ȕ25/85°C=3977K 1000.0 Resistance [kOhm] 100.0 10.0 1.0 0.1 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 80 90 100 Temperature [C] CTT Chart R-T Table R25°C=50k: ȕ25/85°C=3977K 1000.0 Resistance [kOhm] 100.0 10.0 1.0 0.1 -30 -20 -10 0 10 20 30 40 50 60 70 Temperature [C] Replacing thermistor - (14.1.12.) Replacing main board - (14.1.13.) SM CINCO 1-A.
TROUBLESHOOTING 13.5.12 Checking High Pressure Switch (HPS) 1) Disconnect HPS connector from the main board and check resistance between the 2 pins of the HPS connector – if shorted the HPS is OK, otherwise replace HPS. Replacing HPS - (14.1.10) 13.5.13 Checking Low Pressure Switch (LPS) 1) Disconnect LPS connector from the main board and check resistance between the 2 pins of the HPS connector – if shorted the LPS is OK otherwise replace LPS. Replacing LPS - (14.1.10.) 13.5.
TROUBLESHOOTING 13.5.18.2 EMC interference to near by home appliances Locations most susceptible to interference: 1) A television or radio is located near the A/C and A/C wiring. 2) The antenna cable for a television or radio is located close to the A/C and A/C wiring. 3) Locations where television and radio signals are weak. Problem: 1) Noise appears in the television picture, or the picture is distorted. 2) Static occurs in the radio sound. Correction Actions: 1) Select a separate power source.
SERVICING 14. SERVICING TURN OFF ALL POWER SOURCE BEFORE HANDLING THE UNIT Note: To reassemble perform the procedures in reverse. 14.1 Removing Service (front) panel Remove the fixing screws and slide the service (front) panel downwards to remove it. Note: Do not flip the panel forward on the top side as not to damage the controller. 14.2 Removing side (Service) panel Remove the fixing screws and slide the panel downwards to remove it. 14.
SERVICING 14.5 Removing Air Outlet Grille(s) Remove the fixing screws of the each grille. 14.6 Removing Outdoor Fan 1. Remove the air outlet grille according to 14.5. 2. Remove the hex nut from the motor shaft. To ease the removal, use rubber hammer to hit on the hex nut while pulling out the fan. NOTES for re-assemble the fan: 1. Insert the skidding protection part of fan boss in accordance with the cutting part of the motor shaft. Push hard until fan can no longer be inserted. 2.
SERVICING 14.8 Removing Reversing Valve coil 1. 2. 3. 4. Remove the service front panel according to 14.1. Check to ensure that LEDs and display board are OFF. Disconnect the RV connector from the main board. Remove the RV wires from the cable holders along the electronics box. 5. Remove the fixing screw from the reversing valve coil and take the coil out. 14.9 Removing Reversing Valve coil Removing Expansion Valve coil 1. 2. 3. 4. Remove the service front panel according to 14.1.
SERVICING Remove the nuts fixing the compressor and lift the compressor. NOTES for re-assembling new compressor: 1. To prevent contamination of the refrigerant with water or foreign particles, do not expose open pipes to atmosphere for long periods. If necessary, seal pipe ends using caps or tape. 2. Remove the caps for the new compressor just before replacing the compressor. Seal suction and discharge pipe using tape when mounting to prevent the foreign particles entering the compressor.
SERVICING 14.13 Removing main boards 1. Remove the service panels according to 14.1 and 14.2. 2. Check to ensure that LEDs and display board are OFF. 3. Disconnect all connectors from the main boards. 4. Squeeze the spacers head with LongNose Pliers and pull out the board. Note: It might be easier to remove the main board panel first and than pull out the board from its spacers. Notes for re-assemble the main board: 1. Make sure to connect all the connectors into the right locations.
SERVICING 14.15 Removing driver module 1. Remove the electrical assembly according to 14.14. 2. Remove the screws fixing the main board panel to the assembly and take the panel out. 3. Remove the screws fixing the terminal panel to the assembly and take the panel out. 4. Disconnect all the wires from the driver terminals and the communication connector. 14.16 Removing driver cover Removing terminal panel Removing Line Filter board 1. Perform the driver module removal procedure in 14.15. 2.
EXPLODED VIEWS AND SPARE PARTS LISTS 15. EXPLODED VIEWS AND SPARE PARTS LISTS 15.1 Outdoor Unit: Cinco 100 DCI 1 11 31 7 18 10 8 9 12 12a 12c 12b 23 5 26 SM CINCO 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.2 Outdoor Unit: Cinco 100 DCI 69 39 16 50b 50a 33 49 49 50c 50d 37 49 49 50e 49 43b 43 40 21 70 38 31 45a 45 43a 14 48 72 65 75 47 61 53 64 34 51 19a 19b 52 34a 19n 19m 15-2 64 SM CINCO 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.3 SP No.
OPTIONAL ACCESSORIES 16. OPTIONAL ACCESSORIES 16.1 RCW Wall Mounted Remote Control 16.1.1 The RCW wall mounted remote control can be fitted to a large range and models, It can be used as IR (wirless mode) or wired controler.the RCW can control up to15 indoor units using the same settings (on its wired aplication). The max wiring length between the controller to the last indoor unit is 300m. for application on WNG LED indoor units an additional interface PCB is needed.
OPTIONAL ACCESSORIES 16.2 RCW2 Wall Mounted Remote Control 16.2.1 The RCW2 wall mounted remote controler is a wired controler that can provide affective controling management up to 15 different settings and temp’ zones. The RCW2 can be connected up to a max’ of 32 units,allowing a max wiring length of 1000m for application on WNG LED indoor units an additional interface PCB is needed. Ordering code no’: RCW2 – SP000000081 WNG add’ PCB - SP000000290 1 2 3 1 2 4 3 4 16-2 Display screen.
OPTIONAL ACCESSORIES 16.3 Base Heater PN: 439878 Before starting the heaters connection verify that the unit is disconnected from main power supply!! BASE HEATERT INSTALLATION INSTRUCTIONS Check the installation manual for further information The kit includes: 1. 2. 3. 4. One 70W PT heating element. One Heater holder. Two magnets for assemble of heater to outdoor base. 4 Strips. Instructions: 1. Open the outdoor unit electrical cover and service panel. 2.
OPTIONAL ACCESSORIES 16.4 Crank Case Heater PN: 190443 Before starting the heaters connection verify that the unit is disconnected from main power supply!! CRANK CASE HEATERS INSTALLATION INSTRUCTIONS Check the installation manual for further information The kit includes: 1. One 50W heating element. 2. One spring holder. Instructions: 1. Open the outdoor unit electrical cover and service panel. 2. Remove the compressor insulation layers. 3.
OPTIONAL ACCESSORIES 16.5 Room Thermostat Room Thermostat kit PN: 442298 Thermistor with connector PN: 442296 Before starting the connection verify that the unit is disconnected from main power supply!! ROOM THERMOSTAT INSTALLATION INSTRUCTIONS Check the installation manual for further information Supplied components list: No.
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► INSTALLATION MANUAL CINCO 100 DCI SM CINCO 1-A.