Service manual

12-34
CONTROL SYSTEM
SM CINCO 1-A.1 GB
12.10 Jumper/DIP-Switch Setting
12.10.1 Jumper/DIP-Switch Definition
0 = Open (Disconnected)
1 = Close (Shorted)
12.10.2 IDU Jumpers/DIP-Switch
12.10.2.1 Self test Jumper/DIP – J1
Position Status Description
0 Open (Disconnected) Normal Operation (Default)
1 Close (Shorted) Self Test enabled
Used for internal production line testing. For normal use must be set to OFF (0).
12.10.2.2 Compensation Jumper/DIP – J2
Model J2 (Default) Compensation
WNG/WNG18/WNG30 0 Activated
PXD 1 Deactivated
CK/LSN/DNG/TOP/HAD/Delta 1 Activated
12.10.2.3 Family selection Jumper/DIP – J3, J4, J5, J6, J11
Family Name – Family Number J11 J8 J7 J6 J5 J4 J3
Delta
A
- 0 0
See model
selection
0000
HAD/HCD
A
- 1 1 0001
WNG - 3 NA NA 0 1 1
PXD - 4 0 0 1 0 0
HAD/HCD/WNG18 - 8 0 1 0 0 0
WNG30 - 9 0 1 0 0 1
Delta
B
- 10 0 1 0 1 0
DNG 50- 12 NA 0 0 0 1 0 1
DNG 60- 12 NA 0 0 0 1 1 0
DNG 72- 12 NA 1 0 0 1 0 1
DNG 80- 12 NA 1 1 0 1 0 1
CN
A
- 16 1
See model
selection
0000
CN
B
- 17 1 0 0 0 1
LSN
A
- 24 1 1 0 0 0
LSN
B
- 25 1 1 0 0 1
TOP - 26 1 1 0 1 0
12.10.2.4 Model selection Jumper/DIP – J7, J8
Model J8 J7
A00
B01
C10
D11
12.10.2.5 Presence Detector/DIP – J9
Position Status Description
0 Open (Disconnected) Presence detector enabled (Default)
1 Close (Shorted) NA (Not to be used)