Service manual
12-38
CONTROL SYSTEM
SM CINCO 1-A.1 GB
№ Name AB Unit
39. EEVMultiMinOperOpenC 50 step
40. EEVMultiMinOperOpenH 50 step
41. EEVMinOperOpenHInactive 50 step
42. EEVMaxOperOpenHInactive 120 step
43. NormAccel 1 Hz/s
44. NormDecel 1 Hz/s
45. OCTExitDeicer 12 °C
46. MaxDeicerTime 12 minute
47. EEVDecierOpenMulti 160 Step
48. DeicerCoef 0.8 NA
49. EEV_Active_H_Isotherm 6 °C
50. EEV_Active_H_SC 15 °C
51. EEV_Active_H_SC_Crct 1°C
52. EnableExceedCond 0NA
53. MinSumCapCode1 1NA
54. MinSumCapCode2 4NA
55. MinSumCapCode3 3NA
56. MinSumCapCode4 4NA
57. MinSumCapCode5 5NA
58. MaxSumCapCode1 4NA
59. MaxSumCapCode2 6NA
60. MaxSumCapCode3 6NA
61. MaxSumCapCode4 6NA
62. MaxSumCapCode5 6NA
63. Max_IDU_Number 5 NA
64. NightRPS 70 RPS
65. CCHoutput 0 NA
66. CCHDuty 0 No.
67. OCT_OFAN_Noise_Max
8 °C
68. OMT_OFAN_Noise_Max 38 °C
69. Target_CTT_Alpha_C 1.663 NA
70. Target_CTT_Beta_C 0.785 NA
71. Target_CTT_Gamma_C 0.1 NA
72. Target_CTT_Delta_C 0 NA
73. Target_CTT_Alpha_H 1.559 NA
74. Target_CTT_Beta_H 0.906 NA
75. Target_CTT_Gamma_H 0.044 NA
76. Target_CTT_Detla_H 0 NA
12.11.3 Indoor Units SW Parameters
ICTST Speed ICT to stop indoor fan 25
ICTVLSpeed ICT to go down to very low speed 28
ICTLSpeed ICT to start in very low speed 30
ICTHSpeed ICT to start in increase speed from very low 32
ICTTSpeed ICT to enable Turbo fan speed 40
ICTDef1 ICT to go back to normal 8
ICTDef2 ICT to ‘stop rise’ when ICT decrease 6
ICTDef3 ICT to ‘stop rise’ when ICT is stable 4
ICTDef4 ICT to ‘Hz Down’ when ICT decrease 2
ICTDef5 ICT to ‘Hz Down’ when ICT is stable 0
ICTDef6 ICT to stop compressor -2