Service manual
12-41
CONTROL SYSTEM
SM CINCO 1-A.1 GB
12.11.3.1.5 Cassettes Models - CN
Parameter name
Model
25 35 50 60 72
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 47 42 55 56 50
MaxNLOADIF2C 70 60 78 81 70
MaxNLOADIF3C 127 127 127 127 127
MaxNLOADIF4C 127 127 127 127 127
MaxNLOADIF5C 127 127 127 127 127
Indoor Fan speed
IFVLOWC 400 400 500 550 600
IFLOWC 450 450 550 600 650
IFMEDC 500 520 620 660 700
IFHIGHC 550 600 680 720 750
IFTURBOC 650 700 800 900 1000
IFVLOWH 400 400 500 550 600
IFLOWH 450 450 550 600 650
IFMEDH 520 550 620 660 700
IFHIGHH 600 650 680 720 750
IFTURBOH 650 700 850 950 1000
12.11.3.1.6 Ducted Models - LSN
Parameter name
Model
25 35 50 60 72
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 127 127 127 127 127
MaxNLOADIF2C 127 127 127 127 127
MaxNLOADIF3C 127 127 127 127 127
MaxNLOADIF4C 127 127 127 127 127
MaxNLOADIF5C 127 127 127 127 127
Indoor Fan speed
IFVLOWC 740 730 860 960 980
IFLOWC 740 730 860 960 980
IFMEDC 810 860 980 1050 1050
IFHIGHC 920 980 1100 1170 1200
IFTURBOC 960 1060 1170 1240 1280
IFVLOWH 740 730 860 960 980
IFLOWH 740 730 860 960 980
IFMEDH 810 860 980 1050 1050
IFHIGHH 920 980 1100 1170 1200
IFTURBOH 960 1060 1220 1240 1280
12.11.3.1.7 Ducted Models - DNG
Parameter name
Model
50 60 72
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 50 50 127
MaxNLOADIF2C 63 63 127
MaxNLOADIF3C 127 127 127
MaxNLOADIF4C 127 127 127
MaxNLOADIF5C 127 127 127
Indoor Fan speed
IFVLOWC
Fix RPM Motor
IFLOWC
IFMEDC
IFHIGHC
IFTURBOC
IFVLOWH
IFLOWH
IFMEDH
IFHIGHH
IFTURBOH