Service manual

2-1
PRODUCT DATA SHEET
SM CINCO 1-A.1 GB
2. PRODUCT DATA SHEET
2.1 Outdoor Unit Specifications.
Model Cinco 100 DCI / YAZ5036-H11
Operation Mode Cooling Heating
Starting Current A < 10
Circuit Breaker Current A 25
Power Supply V/Ph/Hz 220-240V/ 1PH / 50Hz
INDOOR
See DCI Single
OUTDOOR
Refrigerant control
Electronic expansion valve
Compressor type Twin Rotary DC Inverter
Model Sanyo C-7RVN153HOW
Protection device Outdoor SW control, HPS, LPS
Heat exchanger Hydrophilic corrugated fins ,Grooved tubes
Fan x No. Propeller x 2
Airflow m
3
/hr 4,150
Motor output W 2 x 50
Sound level
(1)
Pressure
dB(A)
57 59
Power 68 69
Dimensions WxDxH mm 900 x 970 x 340
Weight Kg 80
Package WxDxH mm 985 x 1020 x 435
Packaged Weight Kg 85
Units per pallet Units 6
Stacking height
Units 2
TUBING
Refrigerant Charge (Precharged)
g (m) 3,000 (30m)
Additional charge (30-80m) g 400
Tube size
O.D.
Liquid mm 5 x 6.35
Suction mm 3x 9.53 + 2x 12.7
Connection
method
between the
indoor and
outdoor units
Indoor & outdoor Flared
Height difference between indoor
units
Max.15m
Height difference between indoor &
outdoor
Max.15m
Tubing length
Max.25m for one unit and 80m total
Operation control type
LCD Remote Control
Heating elements kW BH 70W (Optional)
Others
Notes:
(1)
Sound pressure level measured at 1 meter distance from unit at nominal (cool/heat) conditions.