Indoor Units Outdoor Units HAD007 GC 7 DCI HAD009 GC 9 DCI GCD009 HAD012 HAD018 HAD022 HAD024 GC 12 DCI GCD012 GC 18 DCI GC 21 DCI GC 24 DCI REFRIGERANT R410A SM HADDCI 1-A.2 GB HEAT PUMP MARCH – 2010 CONTENTS cybairnet@airwell.
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ August 2009 Total number of pages in this publication is 171 consisting of the following: Page No. Revision No. # Page No. Revision No.
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The new HAD DC Inverter series is split wall mounted type indoor unit. It has innovative flat design with background display and range comprise the following RC (heat pump) models: ● ● ● HAD007 HAD009 HAD012 ● ● ● HAD018 HAD022 HAD024 The indoor HAD units are available as LED display types only, featuring esthetic design, compact dimensions, and low noise operation. 1.
INTRODUCTION 1.3 Indoor Unit The indoor unit is a wall mounted type, and can be easily fitted to many types of residential and commercials applications. It includes: ● Casing with air inlet and outlet grills. ● A large-diameter tangential fan. ● Bended coil with treated aluminum fins. ● Motorized flaps. ● Variable Speed motor (PG). ● Advanced electronic control box assembly. ● Interconnecting wiring terminal block. ● Mounting plate. 1.
INTRODUCTION 1.7 Tubing Connections Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Outdoor Chapter 9. 1.8 Accessories RCW Wall Mounted Remote Control The RCW remote control is mounted on the wall (RC-2), and controls the unit either as an infrared remote control or as a wired controller. The wired controller can control up to 10 Indoor units with the same program settings and adjustments.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.3 HAD009 / GCD009 DCI Model Indoor Unit Model Outdoor Unit HAD009 DCI GCD 009 R410A Installation Method of Pipe Characteristics Capacity (4) Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class INDOOR OUTDOOR Connections between units Operation control type Heating elements (Option) Others (1) (2) (3) (4) In.(mm) In.(mm) m. Max. 15 m. Max.
PRODUCT DATA SHEET 2.4 HAD012 / GC 12 WDI DCI HAD012 Model Indoor Unit GC 12 WDI DCI Model Outdoor Unit Installation Method of Pipe Characteristics Capacity Flared (1) Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure INDOOR Sound power level (3) Sound pressure level (4) Moisture removal Condenstate drain tube I.
PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.
RATING CONDITIONS 3. RATING CONDITIONS Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.1 Operating Limits 3.1.1 R410A Indoor Cooling Heating Upper limit 32oC DB 23oC WB 46oC DB Lower limit 21oC DB 15oC WB -10oC DB (0oC matching GCD) Upper limit 27oC DB 24oC DB 18oC WB Lower limit 10oC DB -15oC DB -16oC WB Voltage SM HADDCI 1-A.
OUTLINE DIMENSIONS 4. OUTLINE DIMENSIONS 4.1 Indoor Unit: HAD007, HAD009 676 250 188 4.2 Indoor Unit: HAD012 836 250 188 4.3 Indoor Unit: HAD018, HAD022, HAD024 1060 295 219 SM HADDCI 1-A.
OUTLINE DIMENSIONS 4.4 Outdoor Unit: GC 7, GC 9, GC 12, GCD009, GCD012 AIR INTAKE AIR OUTLET 4.5 4-2 Outdoor Unit: GC 18 CONTENTS SM HADDCI 1-A.
OUTLINE DIMENSIONS 4.6 Outdoor Unit: GC 21 4.7 Outdoor Unit: GC 24 SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5. PERFORMANCE DATA 5.1 HAD007 / GC 7 RC DCI 5.1.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] OD COIL ENTERING AIR DB TEMPERATURE [oC] DATA 22/15 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 24/17 27/19 29/21 32/23 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 2.08 1.72 0.51 1.98 1.67 0.57 2.21 1.75 0.52 2.11 1.
PERFORMANCE DATA & PRESSURE CURVES 5.1.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] ID COIL ENTERING AIR DB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) 15 20 25 1.37 0.37 1.53 0.44 1.64 0.50 1.70 0.53 1.74 1.28 0.40 1.43 0.48 1.55 0.53 1.61 0.56 1.65 1.18 0.44 1.34 0.52 1.45 0.57 1.51 0.60 1.55 0.54 0.58 0.62 2.25 2.20 0.
PERFORMANCE DATA & PRESSURE CURVES 5.1.5 Capacity Correction Factor Due to Tubing Length 5.1.5.1 Cooling &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ 5.1.5.2 Heating &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.2 HAD009 / GC 9 RC DCI 5.2.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [oC] ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA 22/15 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 24/17 27/19 29/21 32/23 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 2.41 1.67 0.59 2.30 1.63 0.66 2.57 1.71 0.60 2.46 1.67 0.67 2.73 1.74 0.61 2.
PERFORMANCE DATA & PRESSURE CURVES 5.2.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [oC] OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA 15-24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC (Protection Range) PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 1.57 0.41 1.74 0.50 1.88 0.56 1.94 0.59 1.99 1.46 0.46 1.63 0.54 1.77 0.60 1.83 0.64 1.88 1.35 0.50 1.52 0.58 1.66 0.65 1.72 0.68 1.77 0.62 0.66 0.70 2.57 0.
PERFORMANCE DATA & PRESSURE CURVES 5.2.5 Capacity Correction Factor Due to Tubing Length 5.2.5.1 Cooling &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ 5.2.5.2 Heating &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ 5-6 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.3 HAD012 / GC 12 RC DCI 5.3.1 Cooling Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] OD COIL ENTERING AIR DB TEMPERATURE [oC] DATA 22/15 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI -10 - 20 (protection range) 25 30 35 40 46 24/17 27/19 29/21 32/23 3.26 2.59 0.79 3.11 2.52 0.88 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 3.48 3.69 3.90 2.64 2.69 2.75 0.80 0.82 0.83 3.
PERFORMANCE DATA & PRESSURE CURVES 5.3.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [oC] OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA 15-24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC (Protection Range) PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 2.17 0.58 2.41 0.70 2.60 0.79 2.69 0.84 2.75 2.02 0.64 2.26 0.76 2.44 0.85 2.54 0.90 2.60 1.86 0.70 2.11 0.82 2.29 0.91 2.38 0.95 2.45 0.87 0.93 0.98 3.56 0.
PERFORMANCE DATA & PRESSURE CURVES 5.3.5 Capacity Correction Factor Due to Tubing Length 5.3.5.1 Cooling &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ 5.3.5.2 Heating &DSDFLW\ 5DWLR 7XELQJ /HQJWK >P @ SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.4 HAD009 / GCD009 5.4.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [oC] ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA 22/15 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC -10 - 20 (protection range) 25 30 35 40 46 24/17 27/19 29/21 32/23 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal PI 2.41 1.67 0.59 2.30 1.63 0.66 2.57 1.71 0.60 2.46 1.67 0.67 2.73 1.74 0.61 2.
PERFORMANCE DATA & PRESSURE CURVES 5.4.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [oC] OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 1.78 0.49 1.98 0.59 2.14 0.67 2.21 0.71 2.26 1.66 0.54 1.86 0.64 2.01 0.72 2.09 0.76 2.14 1.53 0.59 1.73 0.69 1.89 0.77 1.96 0.81 2.01 0.73 0.78 0.83 2.92 0.77 3.09 0.82 3.25 0.86 2.50 0.69 2.
PERFORMANCE DATA & PRESSURE CURVES 5.4.5 Capacity Correction Factor Due to Tubing Length 5.4.5.1 Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 11 12 13 14 15 16 17 18 19 Tubing Length(m) 5.4.5.2 Heating 1.05 1.00 Capacity Ratio 0.95 0.90 0.85 0.80 0.75 0.70 1 2 3 4 5 6 7 8 9 10 Tubing Length (m) 5-12 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.5 HAD012 / GCD012 5.5.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB TEMPERATURE [oC] ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA 22/15 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC -10 - 20 (protection range) 25 30 35 40 46 PI 24/17 27/19 29/21 32/23 3.38 2.54 0.81 3.22 2.48 0.90 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 3.60 3.82 4.04 2.59 2.64 2.69 0.83 0.84 0.86 3.44 3.
PERFORMANCE DATA & PRESSURE CURVES 5.5.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [oC] OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 2.29 0.63 2.55 0.76 2.75 0.86 2.84 0.91 2.91 2.13 0.69 2.39 0.82 2.58 0.92 2.68 0.97 2.75 1.97 0.76 2.23 0.89 2.42 0.98 2.52 1.03 2.59 0.94 1.00 1.07 3.76 0.99 3.97 1.04 4.17 1.10 3.50 0.97 3.
PERFORMANCE DATA & PRESSURE CURVES 5.5.5 Capacity Correction Factor Due to Tubing Length 5.5.5.1 Cooling 1.02 Capacity Ratio 1.00 0.98 0.96 0.94 0.92 0.90 0.88 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Tubing Length (m) 5.5.5.2 Heating 1.01 Capacity Ratio 1.00 0.99 0.98 0.97 0.96 0.95 0.94 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Tubing Length (m) SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.6 HAD018 / GC 18 5.6.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] OD COIL ENTERING AIR DB TEMPERATURE [oC] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC 4.93 4.10 1.10 4.67 3.94 1.26 4.42 3.78 1.41 4.17 3.62 1.56 3.86 3.43 5.22 4.16 1.13 4.96 4.00 1.28 4.71 3.84 1.44 4.46 3.68 1.59 4.15 3.49 5.51 4.
PERFORMANCE DATA & PRESSURE CURVES 5.6.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] ID COIL ENTERING AIR DB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 2.73 1.16 3.60 1.31 4.26 1.43 4.59 1.48 4.81 1.52 6.39 1.58 6.72 1.61 7.06 1.64 2.34 1.24 3.21 1.40 3.87 1.51 4.19 1.57 4.41 1.60 6.00 1.66 6.33 1.69 6.66 1.72 1.94 1.33 2.82 1.48 3.47 1.59 3.80 1.
PERFORMANCE DATA & PRESSURE CURVES 5.6.5 Capacity Correction Factor Due to Tubing Length 5.6.5.1 Cooling 5.6.5.2 Heating 5-18 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.7 HAD022 / GC 21 5.7.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] OD COIL ENTERING AIR DB TEMPERATURE [oC] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC 5.91 4.64 1.50 5.61 4.46 1.71 5.30 4.28 1.92 5.00 4.10 2.13 4.64 3.88 6.26 4.71 1.54 5.96 4.53 1.75 5.65 4.35 1.96 5.35 4.17 2.17 4.99 3.95 6.61 4.
PERFORMANCE DATA & PRESSURE CURVES 5.7.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] ID COIL ENTERING AIR DB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 2.96 1.33 3.90 1.50 4.61 1.63 4.97 1.70 5.21 1.74 6.93 1.81 7.28 1.84 7.64 1.87 2.53 1.42 3.48 1.60 4.19 1.73 4.54 1.79 4.78 1.84 6.50 1.90 6.86 1.93 7.22 1.97 2.11 1.52 3.05 1.69 3.76 1.82 4.12 1.
PERFORMANCE DATA & PRESSURE CURVES 5.7.5 Capacity Correction Factor Due to Tubing Length 5.7.5.1 Cooling 5.7.5.2 Heating SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.8 HAD024 / GC 24 5.8.1 Cooling Capacity (kW) – Run Mode 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [oC] OD COIL ENTERING AIR DB TEMPERATURE [oC] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 32/23 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC 6.70 5.04 1.70 6.35 4.85 1.94 6.01 4.65 2.17 5.67 4.45 2.41 5.26 4.22 7.09 5.12 1.74 6.75 4.92 1.98 6.41 4.73 2.21 6.06 4.53 2.45 5.65 4.29 7.49 5.
PERFORMANCE DATA & PRESSURE CURVES 5.8.3 Heating Capacity (kW) - Run Mode 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR DB/WB TEMPERATURE [oC] ID COIL ENTERING AIR DB TEMPERATURE [oC] DATA TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15 20 25 3.21 1.53 4.23 1.73 5.00 1.88 5.39 1.96 5.65 2.01 7.51 2.08 7.90 2.12 8.29 2.16 2.75 1.64 3.77 1.84 4.54 1.99 4.93 2.07 5.18 2.12 7.05 2.15 7.44 2.23 7.83 2.27 2.28 1.75 3.31 1.95 4.08 2.10 4.47 2.
PERFORMANCE DATA & PRESSURE CURVES 5.8.5 Capacity Correction Factor Due to Tubing Length 5.8.5.1 Cooling 5.8.5.2 Heating 5-24 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9 Model: HAD007 / GC 7 RC DCI 5.9.1 Cooling Suction Pressure VS. Outdoor Temp [oC] Discharge Pressure VS. Outdoor Temp [oC] SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.2 Heating Suction Pressure VS. Outdoor Temp [oC] Discharge Pressure VS. Outdoor Temp [oC] 5-26 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.3 Model: HAD009 / GC 9 RC DCI 5.9.3.1 Cooling Suction Pressure VS. Outdoor Temp [oC] Discharge Pressure VS. Outdoor Temp [oC] SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.3.2 Heating Suction Pressure VS. Outdoor Temp [oC] Discharge Pressure VS. Outdoor Temp [oC] 5-28 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.4 Model: HAD012 / GC 12 RC DCI 5.9.4.1 Cooling Suction Pressure VS. Outdoor Temp [oC] Discharge Pressure VS. Outdoor Temp [oC] SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.4.2 Heating Suction Pressure VS. Outdoor Temp Indoor DB [oC] Discharge Pressure VS. Outdoor Temp Indoor DB [oC] 5-30 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.5 Model: HAD009 / GCD009 5.9.5.1 Cooling [oC] [oC] SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.5.2 Heating [oC] [oC] 5-32 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.6 Model: HAD012 / GCD012 5.9.6.1 Cooling [oC] [oC] SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.6.2 Heating [oC] [oC] 5-34 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES Model: HAD018 / GC 18 5.9.7.1 Cooling Suction Pressure [kPa] 5.9.7 1400 1300 1200 1100 1000 900 800 700 600 500 Indoor DB/WB Temp. 22/15 24/17 27/19 29/21 32/23 10 15 20 25 30 35 40 45 Discharge Pressure [kPa] Outdoor DB Temperature Indoor DB/WB Temp. 4250 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 22/15 24/17 27/19 29/21 32/23 10 15 20 25 30 35 40 45 Outdoor DB Temperature SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES Suction Pressure [kPa] 5.9.7.2 Heating 1100 1000 900 800 700 Indoor 15 20 25 600 500 400 300 200 -15 -10 -5 0 5 10 15 Discharge Pressure [kPa] Outdoor WB Temperature 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 Indoor 15 20 25 -15 -10 -5 0 5 10 15 Outdoor WB Temperature 5-36 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES Model: HAD022 / GC 22 5.9.8.1 Cooling Suction Pressure [kPa] 5.9.8 Indoor DB/WB Temp. 1400 1300 1200 1100 1000 900 800 700 600 500 22/15 24/17 27/19 29/21 32/23 10 15 20 25 30 35 40 45 Discharge Pressure [kPa] Outdoor DB Temperature 4250 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 Indoor DB/WB Temp. 22/15 24/17 27/19 29/21 32/23 10 15 20 25 30 35 40 45 Outdoor DB Temperature SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES Suction Pressure [kPa] 5.9.8.2 Heating 1100 1000 900 800 700 Indoor 15 20 25 600 500 400 300 200 -15 -10 -5 0 5 10 15 Discharge Pressure [kPa] Outdoor WB Temperature 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 Indoor 15 20 25 -15 -10 -5 0 5 10 15 Outdoor WB Temperature 5-38 CONTENTS SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.9.9 Model: HAD024 / GC 24 5.9..1 Cooling 6.3.1 Cooling-Test Mode Suction Pressure [kPa] 1100 Indoor DB/WB 22/15 24/17 27/19 29/21 32/23 1000 900 800 700 10 15 20 25 30 35 40 45 Discharge Pressure [kPa] Outdoor DB Temperature 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 Indoor DB/WB 22/15 24/17 27/19 29/21 32/23 10 15 20 25 30 35 40 45 Outdoor DB Temperature SM HADDCI 1-A.
PERFORMANCE DATA & PRESSURE CURVES Suction Pressure [kPa] 5.9.9.2 Heating 1200 1100 1000 900 800 700 600 500 400 300 Indoor DB 15 20 25 -15 -10 -5 0 5 10 15 Discharge Pressure [kPa] Outdoor WB Temperature 4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 15 20 25 -15 -10 -5 0 5 10 15 Outdoor WB Temperature 5-40 CONTENTS SM HADDCI 1-A.
SOUND LEVEL CHARACTERISTICS 6. SOUND LEVEL CHARACTERISTICS 6.1 Sound Pressure Level Figure 1. Wall Mounted 6.2 Sound Pressure Level Spectrum (Measured as Figure 1) HAD009 -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.
SOUND LEVEL CHARACTERISTICS HAD0018 -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL HAD0012 -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE Hz, BAND CENTER FREQUENCIES Hz, BAND CENTER FREQUENCIES HAD024 -70NC -60NC -50NC -40NC -30NC -20NC MICRO BAR0.
SOUND LEVEL CHARACTERISTICS 6.3 Outdoor units Microphone Distance from Unit 6.4 Sound Pressure Level Spectrum (Measured as Figure 5) GC 7 RC DCI Heating -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.
SOUND LEVEL CHARACTERISTICS GC 12 RC DCI Heating -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL GC 12 RC DCI Cooling -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE Hz, BAND CENTER FREQUENCIES Hz, BAND CENTER FREQUENCIES GCD009 Heating -70NC -60NC -50NC -40NC -30NC -20NC MICRO BAR0.
SOUND LEVEL CHARACTERISTICS GCD012 Heating -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL GCD012 Cooling Hz, BAND CENTER FREQUENCIES -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC Hz, BAND CENTER FREQUENCIES GC 18 Cooling SM HADDCI 1-A.
SOUND LEVEL CHARACTERISTICS 6-6 GC 21 Cooling GC 21 Heating GC 24 Cooling GC 24 Heating CONTENTS SM HADDCI 1-A.
ELECTRICAL DATA 7. ELECTRICAL DATA 7.1 Single Phase Units MODEL HAD007 HAD009 HAD012 Power Supply To indoor 1PH,220-240V,50Hz To indoor 1PH,220-240V,50Hz To indoor 1PH,220-240V,50Hz Max Current, A 5.2 6.3 7.5 Circuit Breaker,A 10 10 15 3x1.0 mm2 3x1.0 mm2 3x1.5 mm2 4x1.0 mm2 4x1.0 mm2 5x1.5 mm2 HAD018/GC 18 HAD022/GC 21 HAD024/GC 24 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz Indoor Unit Indoor Unit Outdoor Unit Max Current(A) 10.5 10.5 15 Start Current(A) 10.5 10.
WIRING DIAGRAMS 8. WIRING DIAGRAMS 8.1 HAD007, HAD009, HAD012 / GC 7, 9, 12 RC / GCD009, GCD012 SM HADDCI 1-A.
WIRING DIAGRAMS 8.2 HAD018, HAD022 ~230V/50Hz 8.3 8-2 HAD024 CONTENTS SM HADDCI 1-A.
WIRING DIAGRAMS 8.4 GC 18, GC 21 OUTDOOR UNIT CIRCUIT DIAGRAM OAT OCT CTT Blue P4 P1 P6 Blue 2 1 Yellow 1 2 P14 Black Orange 1 2 3 4 5 6 Red U V W P3 P9 P11 P13 Base heater Vdc Choke coil White Red Brown Black Reverse valve EARTH Vcc Vsp FG OFAN COMP 1 2 3 4 5 6 1 2 1 2 1 2 1 2 P19 P20 P8 P2 Outdoor unit controller PCB P10 L N COMN-COM P12 EARTH Jumper JP9 1 2 3 4 5 6 P7 6 5 4 3 2 1 Flash JP1 1 2 3 4 Y/G Y/G Black Red Blue Brown 8.
WIRING DIAGRAMS 8.6 8-4 Connection between indoor unit and outdoor unit CONTENTS SM HADDCI 1-A.
REFRIGERATION DIAGRAMS 9. REFRIGERATION DIAGRAMS 9.1 HAD009 Matching GCD009 9.2 HAD012 Matching GCD012 SM HADDCI 1-A.
REFRIGERATION DIAGRAMS 9.3 HAD007, HAD009, HAD012 Matching GC 7, GC 9, GC 12 RC DCI COOLING & DRY MODE EEV HEATING MODE EEV 9-2 CONTENTS SM HADDCI 1-A.
REFRIGERATION DIAGRAMS 9.4 HAD018, HAD022, HAD024 Matching GC 18, GC 21, GC 24 Cooling Heating SM HADDCI 1-A.
TUBING CONNECTIONS 10. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8.
CONTROL SYSTEM 11. CONTROL SYSTEM [HAD007, HAD009, HAD012] 11.1 Electronic Control 11.1.1 General Functions and Operating Rules The DCI software is fully parametric. The parameters values are given in the last section of this control logic chapter of the service manual. 11.1.2 System Operation Concept The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system ‘Master’, requesting the outdoor unit for cooling/heating capacity supply.
CONTROL SYSTEM 2. For S/W 370V and higher (For 467300225R Controller): NLOAD Target Frequency [Hz] 0 0 0MinFreq MaxFreq MinFreq {min (NLOAD, LoadDeadZone) MinFreq} MinFreq LoadDeadZone MinFreq Definitions MinFreq MaxFreq LoadDeadZone Cool MinFreqC MaxFreqC LoadDeadZoneC Heat MinFreqH MaxFreqH LoadDeadZoneH LoadDeadZone calculation Refer to the following diagram for the above description: 11.1.3.3 Frequency Changes Control Frequency change rate is 1 Hz/sec. 11.
CONTROL SYSTEM 11.1.3.5 Minimum On and Off Time 3 minutes. 11.1.4 Indoor Fan Control 10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds for heat mode. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load. 11.1.4.
CONTROL SYSTEM Notes: When OAT is faulty or disabled OFAN will follow ‘Normal cases’ rules (left column). 1. The table above can be overruled during protections. 2. OFLowFreq = OFLowFreqC in cool mode, and OFLowFreqH in heat mode. 3. OFMedFreq = OFMedFreqC in cool mode, and OFMedFreqH in heat mode. ● The OFAN will be off when the compressor is off. ● An exception for the following rule is when compressor was operating in cool mode before stopped.
CONTROL SYSTEM 11.1.7 EEV (electronic Expansion valve) Control 1. For S/W 37V3 and lower ( For 453031000R Controller) EEV opening is defined as EEV = EEVOL + EEVCV ● EEVOL is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. ● EEVCV is a correction value for the EEV opening that is based on the compressor temperature. ● During the first 5 minutes of compressor operation EEVCV = 0.
CONTROL SYSTEM 11.4.1 Temperature Compensation 4 degrees are reduced from RT sensor temperature reading (excluding I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and due to coil heat radiation on RT sensor. 11.4.2 Indoor Fan Control in Heat Mode Indoor fan speed depends on the indoor coil temperature: ICTST ICTVL 11.
CONTROL SYSTEM 11.7.1 Indoor Coil Defrost Protection ICT Trend ICT ICT < -2 -2 ≤ ICT < 0 0 ≤ ICT < 2 2 ≤ ICT < 4 4 ≤ ICT < 6 6 ≤ ICT < 8 8 ≤ ICT 11.7.2 Fast Increasing SC D1 SR SR Norm Norm Increasing No change Decreasing SC D1 SR SR Norm Norm SC D2 D1 SR SR Norm Normal SC D2 D2 D1 SR SR Fast Decreasing SC D2 D2 D2 D1 SR Indoor Coil over Heating Protection ICT Trend ICT ICT > 55 53 < ICT ≤ 55 49 < ICT ≤ 53 47 < ICT ≤ 49 45 < ICT ≤ 47 43 < ICT ≤ 45 ICT ≤ 43 11.7.
CONTROL SYSTEM 11.7.4 Compressor over Current Protection CCR Stop-Compresor CCROC4 HzDown2 CCROC3 HzDown1 CCROC2 Stop-Rise CCROC1 Normal 11.7.5 Heat Sink Over Heating Protection HST HST > 90 85 < HST ≤ 90 82 < HST ≤ 85 80 < HST ≤ 82 78 < HST ≤ 80 HST ≤ 78 HST Trend Decreasing No Change Increasing SC D1 SR SR Norm SC D2 D1 SR Norm Normal SC D2 D2 D1 SR Outdoor Coil Overheating Protection CDTn is the current reading of CDT and CDTn-1 is the last reading of CDT.
CONTROL SYSTEM For cooling: Discharge super heat =CTT-CDT For heating: Discharge super heat =CTT-ICT (Where CDT=MAX(OCT,OMT .Normal – No protection status is ON .Stop-Decrease – System is in protection. Compressor frequency is not allowed to decrease HzUp – System is in protection. Compressor frequency is increased by 3 Hz/min 11.7.6 Outdoor Coil Deicing Protection 11.7.6.1 Deicing Starting Conditions 1.
CONTROL SYSTEM 2. For S/W 370V and higher (For 467300225R Controller) Deicing operation will start when either one of the following conditions exist: • Case 1: OCT < DST AND TLD > DI • Case 2: OCT < OATmax – 12 AND TLD > DI. • Case 3: OCT is Invalid AND TLD > DI • Case 4: Unit is just switched to STBY AND OCT < DST • Case 5: NLOAD = 0 AND OCT < DST • Case 6: OCT<-1 AND TLD>100min DST Definition: When OATmax>0, then DST=8 When OATmax<=0, then DST= -0.8 X OATmax+8 OATmax=Rolling/Moving Max.
CONTROL SYSTEM 11.7.7.1 3 Levels Logic (used in floor/ceiling models) P2 0 1 1 0 P3 0 0 1 1 Level L0 L1 L2&3 L4 Water Level LEVEL4 LEVEL2&3 LEVEL1 ON Pump OFF ANY NLOAD 0 BLINK OPER LED NORMAL 11.7.7.
CONTROL SYSTEM 11.8 Indoor Unit Dry Contact Indoor unit Dry contact has two alternative functions that are selected by J8. Function Contact = Open Contact = Short J8 = Open Presence Detector Connection No Limit Forced to STBY J8 = Short Power Shedding Function No Limit Limit NLOAD 11.
CONTROL SYSTEM Operation Indication 1. Cool ICON Lights up during Cool, Dry or Auto modes (not Fan). Even though the mode can be changed automatically from Auto Cool to Auto Heat, the Cool will light on. 2. Heat ICON Lights up in Red color during heat mode. It will not light up during Auto Heat mode. Blinks continuously during Indoor/Outdoor protections (according to the relevant spec section). During heating the Heat Icon blinks. In Cool, Dry, Or Auto modes the Cool Icon blinks. 3.
CONTROL SYSTEM Family selection Jumper – J2 HW Model J2 (Default) Compensation Use Jumper WNG/WNG18/WNG30/ 0 Activated Use Model Plug PXD/AC/NPXD 1 Deactivated Use Model Plug/ DIP switch LS/K/KS /AD/DNG/KN/CNA/CNB/ ‘EMD 4-5 hp/DS 4-5 hp’ DNG 4-5 hp / KN 4-5-6 hp / CD 5-6 hp LSNA/LSNB/TOP DCI/NKN HADA/HADB/DeltaA/DeltaB 1 Activated Model selection Jumper – J3, J4 Model A B C D 11.11.1.
CONTROL SYSTEM ODU MODEL SELECTION ODU3 ODU2 OFF OFF OFF OFF OFF OFF OFF OFF ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ON (PIN7 & PIN8) ODU1 OFF OFF OFF OFF ON (PIN5 & PIN6) ON (PIN5 & PIN6) ON (PIN5 & PIN6) ON (PIN5 & PIN6) OFF OFF OFF OFF ON (PIN5 & PIN6) ON (PIN5 & PIN6) ON (PIN5 & PIN6) ON (PIN5 & PIN6) ODU0 OFF OFF ON (PIN3 & PIN4) ON (PIN3 & PIN4) OFF OFF ON (PIN3 & PIN4) ON (PIN3 & PIN4) OFF OFF ON (PIN3 & PIN4) ON (P
CONTROL SYSTEM ODU MODEL SELECTION ODU3 ODU2 ODU1 ODU0 ODU Model Compressor Type OFF OFF OFF OFF Reserved OFF OFF OFF ON A (Single DCR 22- Use Capillary) Toshiba-DA89 (4 Poles) OFF OFF ON OFF B (Single DCR 25- Use Capillary) Toshiba-DA89 (4 Poles) OFF OFF ON ON C (Single DCR 35- Use Capillary) Toshiba- DA108 (4 Poles) OFF ON OFF OFF D (Reserved) OFF ON OFF ON E (Single DCR 22- Use EEV) Panasonic-5RS092 (6 Poles) OFF ON ON OFF F (Single DCR 25- Use EEV) Panasonic-5R
CONTROL SYSTEM 11.12 Test Mode 11.12.1 Entering Test Mode System can enter Test mode in two ways: Automatically when the following conditions exists for 30 minutes continuously: o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature = 35±1 Or o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1 Manually when entering diagnostics with the following settings: o Mode = Cool, Set point = 16 o Mode = Heat, Set point = 30 11.12.
CONTROL SYSTEM 11.13.1.
CONTROL SYSTEM 11.13.
CONTROL SYSTEM For S/W 370V and higher (For 467300225R Controller) Parameter Name GC 7 RC DCI GC 9 RC DCI GC 12 RC DCI (EEV) (EEV) (EEV) GCD009 (Capillary) GCD012 (Capillary) Compressor Parameters MinFreqC 20 20 20 20 20 MaxFreqC 52 70 75 65 78 MinFreqH 25 25 25 28 28 MaxFreqH 67 75 75 67 75 Step1Freq 37 37 37 37 37 Step2Freq 46 46 46 46 46 Step3Freq 60 60 65 60 65 Frequency limits as a function of outdoor air temperature MaxFreqAsOATC 52 70 75 65 78 MaxFr
CONTROL SYSTEM 11.13.3 Remote Control DIP Switch Settings DEFINITION SETTING SWITCH STATUS SW. NO. 4 SW. NO. 3 SW. NO. 2 SW. NO. 1 RC-ALL MODES OF OPERATION -- -- OFF OFF STD-COOL, FAN, DRY, ACTIVE -- -- OFF ON HEAT-COOL, FAN, DRY, ACTIVE -- -- ON OFF AUTO FAN (AF) -- -- ON ON RC4 RC3 VERTICAL SWING ONLY TEMP. DISPLAY IN °C DEGREES -- OFF -- -- HORIZONTAL & VERTICAL SWING FUNCTIONS TOGETHER TEMP.
TROUBLESHOOTING 12. TROUBLESHOOTING [HAD007, HAD009, HAD012] 12.1 ELECTRICAL & CONTROL TROUBLESHOOTING WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 4 Min. to discharge the system.
TROUBLESHOOTING No SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION 8 Compressor is on but outdoor fan does not work Problem with outdoor Check outdoor fan motor according electronics or outdoor to the procedure in section 15.1.5.3 fan below, if not OK replace controller 9 Unit works in wrong mode (cool instead of heat or heat instead of cool) Electronics or power connection to RV Check RV power connections, if OK, Check RV operation with direct 230VAC power supply, if OK, Replace outdoor controller.
TROUBLESHOOTING If no fault occurred in the system, no fault code will be displayed during normal operation mode. The last fault code will be displayed even if the system has recovered from that fault. The last fault will be deleted from the EEPROM after the system has exit diagnostics mode. In diagnostics mode, system fault / status will be indicated by blinking of Filter & Timer LEDs.
TROUBLESHOOTING 15.1.3.2 No. Indoor unit diagnosis and corrective actions Fault Probable Cause Corrective Action 1 Sensor failures of all types 2 Communication mismatch Indoor and Outdoor controllers are with different versions Replace Indoor controller 3 No Communication Communication or grounding wiring is not good. Check Indoor to Outdoor wiring and grounding 4 No Encoder Indoor electronics or motor Check motor wiring, if ok, replace motor, if still not ok, replace Indoor controller.
TROUBLESHOOTING 15.1.3.
TROUBLESHOOTING For S/W 370V and higher (For 467300225R Controller) No Problem 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20 21 22 23 24 25 26 27 28 29 30 31 OCT shorted/disconnected CTT shorted/disconnected HST shorted/disconnected OAT shorted/disconnected OMT shorted/disconnected Reserved (for Multi Split RGT shorted/disconnected) Reserved (for Multi Split RLT shorted/disconnected) Reserved Reserved Reserved IPM Fault Reserved DC under voltage Reserved Zero Crossing detection fault Mismatch between I
TROUBLESHOOTING 12.1.5 Simple procedures for checking the Main Parts 12.1.5.1 Checking Mains Voltage. Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s). 12.1.5.2 Checking Power Input. If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit.
CONTROL SYSTEM > GC 18/GC 21 13. CONTROL SYSTEM [HAD018, HAD022] 13.1 General Functions and Operating Rules The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual. 13.1.1 System Operation Concept The control function is divided between indoor and outdoor unit controllers.
CONTROL SYSTEM > GC 18/GC 21 Target frequency limits as a function of outdoor air temperature (OAT): OAT Range Cool mode limits OAT < 6 No limit 6 ≤ OAT < 15 MaxFreqAsOATC 15 ≤ OAT < 28 28 ≤ OAT 13.1.4 Heat mode limits No limit MaxFreqAsOAT1H MaxFreqAsOAT2H Frequency Changes Control Frequency change rate is 1 Hz/sec. 13.1.5 Compressor Starting Control Step3 Step2 Step1 1 Minute 13.1.6 1 Minute Time Min 10 Minutes Minimum On and Off Time 3 minutes. 13.1.
CONTROL SYSTEM > GC 18/GC 21 13.1.8 Heating Element Control Heating element can be started if LOAD > 0.8 * MaximumNLOAD AND Indoor Coil temperature < 45. The heating element will be stopped when LOAD < 0.5 * MaximumNLOAD OR if Indoor Coil temperature > 50. 13.1.9 Outdoor Fan Control 7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3 speeds for heat mode, and a very low speed.
CONTROL SYSTEM > GC 18/GC 21 13.1.11 Reversing Valve (RV) Control Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes. 13.1.12 ionizer Control Ionizer is on when unit is on AND indoor fan is on AND Ionizer power switch (on Ionizer) is on. 13.2 Fan Mode In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
CONTROL SYSTEM > GC 18/GC 21 13.4.2 Indoor Fan Control in Heat Mode Indoor fan speed depends on the indoor coil temperature: 13.5 Auto Cool/Heat Mode When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (ΔT). Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
CONTROL SYSTEM > GC 18/GC 21 13.7.2 Indoor Coil over Heating Protection ICT Trend ICT ICT > 55 53 < ICT ≤ 55 49 < ICT ≤ 53 47 < ICT ≤ 49 45 < ICT ≤ 47 43 < ICT ≤ 45 ICT ≤ 43 13.7.
CONTROL SYSTEM > GC 18/GC 21 13.7.4 Compressor over Current Protection CCR Stop-Compresor CCROC4 HzDown2 CCROC3 HzDown1 CCROC2 Stop-Rise CCROC1 Normal 13.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35) HST HST > 90 85 < HST ≤ 90 82 < HST ≤ 85 80 < HST ≤ 82 78 < HST ≤ 80 HST Trend No Change SC D2 D1 SR Norm Decreasing SC D1 SR SR Norm HST ≤ 78 Increasing SC D2 D2 D1 SR Normal 13.7.6 Outdoor Coil Deicing Protection 13.7.6.
CONTROL SYSTEM > GC 18/GC 21 13.7.6.2 Deicing Protection Procedure OCT 12 0 T h re s h o ld COMP ON T1 T1 T2 DT m a x. 1 2 m in u te s D e ic e F re q C h R V HEAT RV T3 COOL O FAN T3 ON OFF EEV E E V D e ic e rO p e n Any T1 =60 seconds, T2 = 36 seconds, T3 = 6 seconds 13.8 Indoor Unit from Dry Contact Indoor unit Dry contact has two alternative functions that are selected by J9.
CONTROL SYSTEM > GC 18/GC 21 13.10 On Unit Controls and Indicators 13.10.1 Indoor Unit controller Controls and Indicators STAND BY INDICATOR 1. Lights up when the Air Conditioner is connected to power and the mode is STBY. 2. Blinks for 3 times at 600 msec each cycle, when the system is switched to Heat Mode by using the Mode/Reset Switch on the unit (the operation indicator will be off during this blinking time). OPERATION INDICATOR 1.
CONTROL SYSTEM > GC 18/GC 21 13.10.2 Indoor Unit controller Controls and Indicatiors The following is schematic drawing for the display: Infra Red Receiver Mode/Reset Button Filter STBY/OPER ESF/Ionizer 13.10.3 Timer Outdoor Unit Controller Indicators Unit has three LED’s. SB LED, STATUS LED, FAULT LED. SB LED is ON when power is ON (230 VAC), STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs.
CONTROL SYSTEM > GC 18/GC 21 Jumper - J10 OPERATION With Ionizer Without Ionizer J10 0 1 Jumper - J14 OPERATION LEX Display HAD Display 13.11.
CONTROL SYSTEM > GC 18/GC 21 13.12.2 Unit Operation in Test Mode In test mode, the unit will operate in fixed settings according to the indoor fan speed setting: Indoor FAN Speed Setting Unit Setting Low High Auto Minimum Capacity Setting Nominal Capacity Setting Maximum Capacity Setting 13.13 SW Parameters 13.13.
CONTROL SYSTEM > GC 18/GC 21 13.13.2 Outdoor Units SW Parameters Name MinFreqC MaxFreqC MinFreqH MaxFreqH Step1 Freq Step2Freq Step3Freq MaxFreqAsOATC MaxFreqAsOAT1 H MaxFreqAsOAT2H CCROC1 CCROC2 CCROC3 CCROC4 OFVL OFLOWC OFMEDC OFMAXC OFLOWH OFMEDH OFMAXH SM HADDCI 1-A.2 GB GC 18 GC 21 20 85 20 95 60 70 90 64 85 60 10 10.5 10.8 11.2 20 60 76 92 60 83 100 20 95 26 94 60 70 90 85 80 60 11.4 11.8 12.2 12.
TROUBLESHOOTING > GC 18/GC 21 14. TROUBLESHOOTING Troubleshooting for GC 18/GC 21 DCI WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 3 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! 14.
TROUBLESHOOTING > GC 18/GC 21 No Symptom 9 Unit works in wrong mode (cool instead of heat or heat instead of cool) Electronics or power connection to RV Check RV power connections, if OK, check RV operation with direct 230VAC power supply, if OK, replace outdoor controller. 10 All components are operating properly but no cooling or no heating Refrigerant leak Check refrigeration system. 11 Compressor is over heated and unit does not generate capacity EEV problem Check EEV.
TROUBLESHOOTING > GC 18/GC 21 14.3 Judgment by Indoor/Outdoor Unit Diagnostics Enter diagnostics mode - press for five seconds Mode button in any operation mode. Acknowledgment is by 3 short beeps and lights of COOL and HEAT LED’s. Then, every short pressing of Mode button will scroll between Indoor and Outdoor unit diagnostic modes by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LED’s.
TROUBLESHOOTING > GC 18/GC 21 14.3.2 No. Indoor Unit Diagnostics and Corrective Actions Fault Probable Cause Corrective Action 1 Sensor failures of all types 2 Communication mismatch Indoor and Outdoor controllers are with different versions Replace Indoor controller 3 No Communication Communication or grounding wiring is not good.
TROUBLESHOOTING > GC 18/GC 21 14.3.
TROUBLESHOOTING > GC 18/GC 21 14.4 Judgment by MegaTool MegaTool is a special tool to monitor the system states. Using MegaTool requires: • A computer with RS232C port. • A connection wire for MegaTool. • A special MegaTool software. Use MegaTool according to following procedure: • Setup MegaTool software: copy the software to the computer. • Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by the connection wire.
TROUBLESHOOTING > GC 18/GC 21 14.6 Precaution, Advise and Notice Items 14.6.1 High voltage in Outdoor unit controller. Whole controller, including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shock. Advise: Don’t touch the naked lead wire and don’t insert finger, conductor or anything else into the controller when power is on. 14.6.
CONTROL SYSTEM > GC 24 15. CONTROL SYSTEM [HAD024] 15.
Switching Power Drivers, A/D Application Control PFC Drivers IPM Comp. 15.2.2 OFAN RV Base Heater EEV’s Alarm LED’s 1 t o 4 IDU’s Input Filter Control Communication Power Communication EEMP Block Diagram Dry Contac ts 15.2.1 Temperature Sensors Product Overview 1ph/ 230V / 50Hz 15.2 Configuration Jumpers CONTROL SYSTEM > GC 24 HMI Compressor DC brush less and sensor less 2.5/3 horsepower motor inverter driven compressor. 15.2.3 Outdoor Fan DC brush less motor. 15.2.
CONTROL SYSTEM > GC 24 15.2.8 Temperature Sensors CTT - Compressor Top Temperature OAT - Outdoor Air Temperature OMT - Outdoor Middle Temperature OCT - Outdoor Coil (heat exchanger) Temperature HST - Heat Sink Temperature 15.2.9 Base Heater Heating element designed to melt any ice that is accumulated on the outdoor unit base during low heating operation. 15.3 General Operating Rules 15.3.1 Initialization Initialization process is the first operation done each time power is up.
CONTROL SYSTEM > GC 24 15.3.2 Communication with Indoor Units 15.3.2.1 Communication Failures Definition Two types of communication failures are diagnosed. The communication failures are checked separately for IDU channel. 15.3.2.1.1 ‘Bad Communication’ fault The system keeps a balance of a good/bad communication packet ratio for communication channel. When the ratio getting high , system enters ‘Bad Communication’ fault. 15.3.2.1.
CONTROL SYSTEM > GC 24 15.4.1.1 Turbo Speed The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is selected and under the following conditions: Difference between set point and actual room temperature is higher than 3 degrees. Room temperature is higher than 22°C for cooling or less than 25°C for heating. 15.4.2 Cool Mode NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control.
CONTROL SYSTEM > GC 24 15.4.4 Auto Cool/Heat Mode When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (ΔT). Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3. 15.4.
CONTROL SYSTEM > GC 24 15.4.11 On Unit Controls and Indicators 15.4.11.1 All models Expect for Floor/Ceiling model STAND BY INDICATOR OPERATION INDICATOR 1. Lights up when the Air Conditioner is connected to power and the mode is STBY. 2. Blinks for 3 times at 600 msec each cycle, when the system is switched to Heat Mode by using the Mode/Reset Switch on the unit (the operation indicator will be off during this blinking time). 1.
CONTROL SYSTEM > GC 24 15.4.12 Mode Setting Mode defines the ODU operation mode. There are three possible operation modes: 1. STBY - standby mode 2. COOL - the unit operating at cooling cycle 3. HEAT - the unit operating at heat pump cycle The ODU define the system operation mode according to three methods set by the display key board: 1. First request priority The first IDU which requests different mode than STBY mode will set the new operation mode.
CONTROL SYSTEM > GC 24 NLOAD limits as a function of indoor fan speed: Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating Low Max NLOADIF1C 127 Medium Max NLOADIF2C 127 High Max NLOADIF3C 127 Turbo Max NLOADIF4C 127 Auto Max NLOADIF5C 127 NLOAD limits as a function of power shedding: Mode Power Shedding OFF Power Shedding ON Cool No limit Nominal Cooling Heat No limit Nominal Heating 15.4.13.
CONTROL SYSTEM > GC 24 15.4.13.5.2 Step 3 limit The speed cannot go higher than Step3RPS unless it was operating for more than 1 continuous minute between Step3RPS - 5 and Step3RPS. 15.4.14 EEV Control 15.4.15.1 Operation Range The EEV operation range is defined according to the operation mode as following ODU Mode Normal operation SB IDU inactive Compressor off 200 COOL 80 to 350 0 HEAT 70 to 400 60 to 140 200 15.4.15.
CONTROL SYSTEM > GC 24 15.4.15.6 Balance time During the first 6 minutes after SB the correction is not calculated. After that the correction value is updated every 30 seconds. 15.4.15.7 EEV corrections The corrections in cool mode will keep the compressor in the proper operation temperature and will balance between the indoor units by controlling CTT-OMT. 15.4.15.8 Accumulative correction value storage The accumulated EEV correction value will be stored in the memory.
CONTROL SYSTEM > GC 24 15.4.15.3 Protection Behavior • When in total IDU protection level is different than normal, the OFAN will reduce OFSpdReducePrtC and OFSpdReducePrtH RPM for cool and heat respectively. • In cool mode the OFAN will operate according to CTT or HST protection level: Protection level SR, D1 or D2 Stop-Compressor 15.4.15.4 Action OFAN will add 100 RPM to the target speed continue to operate for maximum 2 minutes at it last speed or until normal level is achieved.
CONTROL SYSTEM > GC 24 15.4.18.3 IDU Protections 15.4.18.3.1 Indoor Cooil Defrost Protection Fast Increasing Increasing ICT Trend No change Decreasing Fast Decreasing ICT < -2 -2 < ICT < 0 SC D1 SC D1 SC D2 SC D2 SC D2 0 < ICT < 2 SR SR D1 D2 D2 ICT 2 < ICT < 4 SR SR SR D1 D2 4 < ICT < 6 Norm Norm SR SR D1 6 < ICT < 8 8 < ICT Norm Norm SR SR 15.4.18.3.
CONTROL SYSTEM > GC 24 15.4.19 Deicing 15.4.19.1 Deicing Starting Conditions Deicing operation will start when either one of the following conditions exist: Case 1: OCT < OAT - DST AND TLD > DI Case 2: OCT < OAT - 12 AND TLD > 30 minutes.
CONTROL SYSTEM > GC 24 15.5 Technician Test Mode This test is aimed for the technicians to check the system under a preset compressor and outdoor fan values while the expansion valves will function according to the normal running mode. 15.5.1 Entering technician mode o This mode is entered through the outdoor unit using the HMI (refer to user interface section). o It can be selected either for cool or heat. o Technician test is not possible to enter during deicer. 15.5.
CONTROL SYSTEM > GC 24 No Problem 5 4 3 2 1 1 OCT bad 0 0 0 0 1 2 CTT bad 0 0 0 1 0 3 HST bad 0 0 0 1 1 4 OAT bad 0 0 1 0 0 5 OMT bad 0 0 1 0 1 6 RGT bad 0 0 1 1 0 7 OFAN/Compressor Feedback Loss 0 0 1 1 1 8 OFAN- IPM fault 0 1 0 0 0 9 OFAN Lock 0 1 0 0 1 10 OFAN- Vospd exceeded 0 1 0 1 0 11 Compressor- IPM Fault 0 1 0 1 1 12 Compressor Lock 0 1 1 0 0 13 Compressor- Vospd exceeded 0 1 1 0 1 14 Compressor- Fold
CONTROL SYSTEM > GC 24 15.7 Jumper settings 0 = open (disconnected) 1 = closed (shorted) 15.5.
CONTROL SYSTEM > GC 24 15.8.2 Protection Parameters Deicer Parameters Parameter DST DSTF DIF (min) CTMR (min) TimeD (min) DIT (min) DTmin (min) DImin (min) DImax (min) DeicSPChRV EEVDeicerOpen DEICT1 (sec) DEICT2 (sec) DEICT3 (sec) OptimDeicSP 15.8.3 Default 8 12 30 15 1 10 3 30 120 0 180 50 36 6 90 Compressor Parameters Compressor Parameters MinOFFTime MinOnTime MaxSpeedC MaxSpeedH Step1RPS Step2RPS Step3RPS 15.8.
CONTROL SYSTEM > GC 24 15.8.5.1.2 Parameters for indoor coil over heating protection: ICTOH1 ICTOH2 ICTOH3 ICTOH4 ICTOH5 ICTOH6 15.8.5.
TROUBLESHOOTING > GC 24 16. TROUBLESHOOTING [GC 24] WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 1 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! 16.
TROUBLESHOOTING > GC 24 No 7 Symptom Corrective Action No power supply Check the connections and the wiring on the main terminal - Repair if needed.
TROUBLESHOOTING > GC 24 No Symptom Probable Cause Corrective Action 21 Other home appliances operation EMC interference by is faulty such as noise appears the A/C unit in the television picture, or the picture is distorted or static occurs in the radio sound Check for EMC problems 22 All others Check diagnostics 16.
TROUBLESHOOTING > GC 24 No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Problem OCT bad CTT bad HST bad OAT bad OMT bad RGT bad OFAN/Compressor Feedback Loss OFAN- IPM fault OFAN Lock OFAN- Vospd exceeded Compressor- IPM Fault Compressor Lock Compressor- Vospd exceeded Compressor- Foldback DC under voltage DC over voltage AC under voltage No communication A reserved reserved reserved Compressor- Ilegal Speed System Configuration Changed System Configuration Problem He
TROUBLESHOOTING > GC 24 16.3.2 No Outdoor fault corrective actions Fault Name 1 OCT bad 2 CTT bad 3 HST bad 4 OAT bad 5 TSUC bad 6 RGT bad 7 Probable Cause Corrective Action Thermistor not connected or damaged Check Thermistor OFAN/Compressor Feedback Loss OFAN halls or wires bad.
TROUBLESHOOTING > GC 24 No 18 Fault Name Corrective Action No signals in line A Check communication 19 Compressor- Ilegal Speed Exceeds speed low limit See # 13 20 System Configuration Changed Communication lines changed from last operation No problem just an announcement 21 System Configuration Problem Miss-match between the IDUs Change configuration if needed.
TROUBLESHOOTING > GC 24 No Fault Name 5 4 3 2 1 1 RT-1 is disconnected 0 0 0 0 1 2 RT-1 is shorted 0 0 0 1 0 3 RT-2 is disconnected 0 0 0 1 1 4 RT-2 is shorted 0 0 1 0 0 … Reserved 0 0 1 0 1 7 Communication mismatch 0 0 1 1 1 8 No Communication 0 1 0 0 0 9 No Encoder 0 1 0 0 1 10 Reserved 0 1 0 1 0 11 Outdoor Unit Fault 0 1 0 1 1 … Reserved 17 Defrost protection 1 0 0 0 1 18 Deicing Protection 1 0 0 1 0 19 Outdoor
TROUBLESHOOTING > GC 24 16.3.4 Indoor unit diagnostics and corrective actions No.
TROUBLESHOOTING > GC 24 16.4.4 Checking the Outdoor Fan Motor Check FAN-Power and FAN-Halls connections - Repair if needed. Rotate the fan slowly by hand. If the fan does not rotate easily, check whether something is obstructing the fan, or if the fan itself is coming into contact with the outer case, preventing it from rotating. Correct if necessary - otherwise, the fan motor bearings have seized. Replace the motor.
TROUBLESHOOTING > GC 24 16.4.10 Checking for electromagnetic interferance (EMC problems) 16.4.10.1 EMC troubles to the A/C unit EMC troubles to the A/C unit Locations most susceptible to noise : 1. Locations near broadcast stations where there are strong electromagnetic waves. 2. Locations near amateur radio (short wave) stations. 3. Locations near electronic sewing machines and arc-welding machines. Trouble : Either of the following trouble may occur: 1. The unit may stop suddenly during operation. 2.
TROUBLESHOOTING > GC 24 Advise: • Open the Outdoor unit controller cover only after one minute from power off. • Measure the electrolytic capacitors voltage before farther checking controller. Additional advises • When disassemble the controller or the front panel, turn off the power supply. • When connecting or disconnecting the connectors on the PCB, hold the whole housing, don’t pull the wire. • There are sharp fringes and sting on shell. Use gloves when disassemble the A/C units. SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17. EXPLODED VIEWS AND SPARE PARTS LISTS 17.1 Indoor Unit: HAD007 / HAD009 / HAD012 SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.2 Intdoor Unit: HAD007 / HAD009 Drawing NO. 17-2 Component Item Description Quantity 1 465720334 Front frame & Front Plate Assy.Electra 1 1 465720338 Front frame & Front Plate Assy.Airwell 1 1 465720342 Front frame & Front Plate Assy.Johnson 1 1 465720327 Front frame & Front Plate Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.3 Intdoor Unit: HAD012 Drawing NO. Component Item Description Quantity 1 465720335 Front frame & Front Plate Assy.Electra 1 1 465720339 Front frame & Front Plate Assy.Airwell 1 1 465720343 Front frame & Front Plate Assy.Johnson 1 1 465720328 Front frame & Front Plate Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.4 17-4 Outdoor Unit: GC 7 RC / GC 9 RC / GC 12 RC DCI CONTENTS SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.5 No. Outdoor Unit: GC 7 RC DCI Part No. Name Quan. 1 4522551 Grille A of GCN 1 2 4523441 Front panel A Painting assy 1 3 4519251 Axial Fan OD=400 1 4 453238900 Sensor/OAT 1 5 4526775 Compressor top thermistor(CTT) 1 6 4526776 Outdoor coil thermistor(OCT) 1 7 453170100 Compressor Assy. MATSUSHIBA 5RS092XDJ01 1 8 453052500 PAINTING BASE ASSY.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.6 No. Outdoor Unit: GC 9 RC DCI Part No. Name Quan. 1 4522551 Grille A of GCN 1 2 4523441 Front panel A Painting assy 1 3 4519251 Axial Fan OD=400 1 4 453238900 Sensor/OAT 1 5 4526775 Compressor top thermistor(CTT) 1 6 4526776 Outdoor coil thermistor(OCT) 1 7 453170100 Compressor: Rotary, Panasonic 5RS092XDJ01 1 8 453052500 PAINTING BASE ASSY.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.7 No. Outdoor Unit: GC 12 RC DCI Part No. Name Quan. 1 4522551 Grille A of GCN 1 2 4523441 Front panel A Painting assy 1 3 4519251 Axial Fan OD=400 1 4 453238900 Sensor/OAT 1 5 4526775 Compressor top thermistor(CTT) 1 6 4526776 Outdoor coil thermistor(OCT) 1 7 4526204 Compressor Assy. Rotary, Panasonic 5RS102XAB01 1 8 453052500 PAINTING BASE ASSY.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.8 17-8 Outdoor Unit: GCD009 / GCD012 CONTENTS SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.9 No. Outdoor Unit: GCD009 Part No. Name Quan. 1 4522551 Grille A of GCN 1 2 4523441 Front panel A Painting assy 1 3 4519251 Axial Fan OD=400 1 4 467400040 Sensor/OAT & OMT 1 5 467400200 Compressor top thermistor(CTT) 1 6 467400023 Outdoor coil thermistor(OCT) 1 7 460000032R Compressor Assy. Toshiba DA89X1C-20FZ3 1 8 453052500 PAINTING BASE ASSY.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.10 No. Outdoor Unit: GCD012 Part No. Name Quan. 1 4522551 Grille A of GCN 1 2 4523441 Front panel A Painting assy 1 3 4519251 Axial Fan OD=400 1 4 467400040 Sensor/OAT & OMT 1 5 467400200 Compressor top thermistor(CTT) 1 6 467400023 Outdoor coil thermistor(OCT) 1 7 460000033R Compressor Assy. Toshiba DA108X1C-20FZ3 1 8 453052500 PAINTING BASE ASSY.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.11 Indoor Unit: HAD018 / HAD022 / HAD024 SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.12 No. Indoor Unit: HAD018 / HAD022 Part No.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.13 No. Indoor Unit: HAD024 Part No. Item Description Quantity 1 465720378 Front panel Assy./Black/Airwell 1 1 465720379 Front panel Assy./Black/electra 1 1 465720380 Front panel Assy./Black/electra Inverter 1 1 465720381 Front panel Assy./Black/Johnson 1 1 465720382 Front panel Assy./Silver-white/Airwell 1 1 465720383 Front panel Assy./Silver-white/electra 1 1 465720384 Front panel Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.14 17-14 Outdoor Unit: GC 18 DCI CONTENTS SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.15 No. Outdoor Unit: GC 18 DCI Item Description Quantity 1 433218 Front Panel A 1 2 4526340 Air inlet ring 1 3 464860054 Painting Insulation Plate Assy 1 4 4526476 Axial fan 1 5 452889600R DC Resin Motor 1 6 4526457 Motor Support 1 7 4527363 Base Painting Assy. 1 8 4526456 Partition 1 9 467300025R Controller/Outdoor Unit DCI 2.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.16 17-16 Outdoor Unit: GC 21 DCI CONTENTS SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.17 No. Outdoor Unit: GC 21 DCI Item Description Quantity 1 4517144 FAN COVER/GRILL A 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 4521642 Painted Right Cabinet and Isolation Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 17-18 Outdoor Unit: GC 24 DCI 17.18 CONTENTS SM HADDCI 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 17.19 No. Outdoor Unit: GC 24 DCI Item Description 1 465100000 Grill 1 2 4523652 Painted Left Cabinet ASSY. 1 3 4523758 Nut/left 1 4 452960400 Outdoor Axial Fan 1 5 461600023 4-Way Valve Assy. 1 6 4522509 4-Way valve coil 1 7 4526522 4-WAY VALVE/R410A 1 8 466130002R DC Resin Motor 1 9 4522601 Right Handle 1 10 4523653 Painted Right Cabinet ASSY.
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► OPERATING MANUAL HAD007/009/012/018/022/024 ► INSTALLATION MANUAL HAD007/009/012/018/022/024 SM HADDCI 1-A.