Service manual
13-12
CONTROL SYSTEM > GC 18/GC 21
SM HADDCI 1-A.2 GB
13.12.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor FAN Speed Setting Unit Setting
Low Minimum Capacity Setting
High Nominal Capacity Setting
Auto Maximum Capacity Setting
13.13
SW Parameters
13.13.1 Imdoor Units SW Parameters
Model Depended Parameters:
Name
HAD/WNG018 HAD/WNG022
ICTSTSpeed 25 25
ICTVLSpeed 28 28
ICTLSpeed 30 30
ICTHSpeed 32 32
ICTTSpeed 40 40
MaxNLOADIFIC 45 50
MaxNLOADIF2C 62 85
MaxNLOADIF3C 120 120
MaxNLOADIF4C 127 127
MaxNLOADIF5C 127 127
NomLoadC 63 85
NomLoadH 76 82
IFVLOWC 700 800
IFLOWC 900 1000
IFMEDC 1050 1100
IFHIGHC 1200 1250
IFTURBOC 1250 1300
IFVLOWH 700 800
IFLOWH 900 950
IFMEDH 1100 1150
IFHIGHH 1250 1250
IFTURBOH 1300 1300