Service manual

7-1
ELECTRICAL DATA
SM HADDCI 1-A.2 GB
7. ELECTRICAL DATA
7.1 Single Phase Units
MODEL HAD007 HAD009 HAD012
Power Supply
To indoor To indoor To indoor
1PH,220-240V,50Hz 1PH,220-240V,50Hz 1PH,220-240V,50Hz
Max Current, A
5.2 6.3 7.5
Circuit Breaker,A
10 10 15
Power Supply Wiring No. X Cross
Section mm
2
3x1.0 mm
2
3x1.0 mm
2
3x1.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
4x1.0 mm
2
4x1.0 mm
2
5x1.5 mm
2
MODEL HAD018/GC 18 HAD022/GC 21 HAD024/GC 24
Power Supply 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz
Power Supply From Indoor Unit Indoor Unit Outdoor Unit
Max Current(A) 10.5 10.5 15
Start Current(A) 10.5 10.5 15
Inrush Current(A) 45
Circuit Breaker(A) 20 20 20
Power Supply Cord No.×Cross
section mm
2
3×2.5mm
2
3×2.5mm
2
3×2.5mm
2
Interconnecting Cable
No.×Cross section mm
2
4×2.5mm
2
4×2.5mm
2
4×2.5mm
2
Inrush current is the current when power is up (charging the DC capacitors at outdoor
unit controller).
Starting current is the current when starting the compressor.
NOTE
Power wiring cord should comply with local lows and electrical regulations
requirements.