Service manual

11-6
CONTROL SYSTEM
SM HADDCI 1-A.2 GB
11.4.1 Temperature Compensation
4 degrees are reduced from RT sensor temperature reading (excluding I-Feel mode), to
compensate for temperature difference between high and low areas in the heated room, and due
to coil heat radiation on RT sensor.
11.4.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
11.5 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (ΔT).
Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by Down1 Hz/min.
HzDown2 (D2) – Compressor frequency is reduced by Down2 Hz/min.
Stop Compressor (SC) – Compressor is stopped.