Service manual
11-20
CONTROL SYSTEM
SM HADDCI 1-A.2 GB
For S/W 370V and higher (For 467300225R Controller)
Parameter Name
GC 7 RC DCI
(EEV)
GC 9 RC DCI
(EEV)
GC 12 RC DCI
(EEV)
GCD009
(Capillary)
GCD012
(Capillary)
Compressor Parameters
MinFreqC 20 20 20 20 20
MaxFreqC 52 70 75 65 78
MinFreqH 25 25 25 28 28
MaxFreqH 67 75 75 67 75
Step1Freq 37 37 37 37 37
Step2Freq 46 46 46 46 46
Step3Freq 60 60 65 60 65
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC 52 70 75 65 78
MaxFreqAsOAT1H 60 65 65 60 65
MaxFreqAsOAT2H 40 40 40 40 40
Compressor Over Heating Protection
CTTOH1 94 94 94 94 94
CTTOH2 98 98 98 98 98
CTTOH3 102 102 102 102 102
CTTOH4 105 105 105 105 105
Compressor Over Current Protection [A]
CCR01 28 35 40 36 36
CCR02 30 37 42 39 39
CCR03 32 39 44 42 42
CCR04 35 42 47 46 46
Outdoor Fan Speed (RPM)
OFC 700 760 760 830 830