Instructions

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
10
3.2.2 Outputs
Fig. 3.5 Relay outputs
Fig. 3.6 Analog outputs 4-20 mA (x.2.x)
Fig. 3.7 Analog outputs 0-10 V (x.4.x)
NOTICE
The output voltage of an external voltage source may not exceed 30 V. Higher
voltage can damage the device.
For voltage supply of analog outputs 4-20 mA or 0-10 V, the integrated voltage source can
be used.
3.2.3 Terminal assignment
For terminal layouts see App. B.
Table 3.1 Terminal assignment
No.
Marking
Description
1
AC230V L / DC24V-
AC / DC power supply *
2
AC230V N / DC24V+
AC / DC power supply *
3
COM1
DI1...DI4 common contact
4
DI1
DI1 digital input
5
DI2
DI2 digital input
6
DI3
DI3 digital input
7
DI4
DI4 digital input
8
COM2
DI5...DI8 common contact
9
DI5
DI5 digital input
10
DI6
DI6 digital input
11
DI7
DI7 digital input
12
DI8
DI8 digital input
13
OUT 24V+
24 VDC integrated voltage source **
14
OUT 24V-
24 VDC integrated voltage source **
15
DO1
DO1 digital output
16
-
DO1...DO2 common contact
17
DO2
DO2 digital output