Instructions

Appendix E. Calibration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
38
Fig. E.6
2. Connect the device to the PC.
3. Switch on the device power supply.
4. Start ALP and select the menu item Device > Calibration to start the calibration tool.
5. Select the device model in the open dialog window.
6. Select Analog outputs as calibration target (Fig. E.2).
7. Enter the measured output voltage in the input field (Fig. E.5).
8. Click Next to continue and follow the instructions.