Instructions

PR200
Programmable relay
PR200_0029_EN
© All rights reserved. Subject to technical changes and misprints.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel: +49 (0) 511 16 59 6720 · www.akytec.de
DANGER
Installation may only be performed when the relay and all connected devices are powered off.
Voltage on the terminals can be dangerous!
CAUTION
It is necessary to observe the polarity while connecting 24V DC power supply! Voltage reversal can damage the device.
NOTICE
Installation and maintenance may only be carried out by specialist personnel using the correct tools!
Ordering information
Supply voltage
-
230 (94…264) V AC
-
24 (19…30) V DC
I/O
-
8 DI, 6 DO
-
8 DI, 4 AI, 8 DO, 2 AO (4-20 mA)
-
8 DI, 4 AI, 8 DO, 2 AO (0-10 V)
Interfaces
-
none
-
RS485
-
2x RS485
Specifications
Table 1 General specification
Device PR200-230.1
PR200-230.2
PR200-230.4
PR200-24.1
PR200-24.2
PR200-24.4
Power supply
230 (94…264) V AC; 50 (47…63) Hz
24 (19…30) V DC
Power consumption, max
10 VA
17 VA
10 W
10 W
Galvanic isolation
2830 V
1780 V
Integrated voltage source
-
24±3 V DC, 100 mA
-
-
Galvanic isolation
-
1780 V
-
-
Inputs
Digital
8
Analog *
-
4
-
4
Outputs
Digital (relay)
6
8
6
8
Analog
-
2
-
2
IP Code
IP20
Dimensions
123 x 108 x 58 mm
Mounting
DIN rail (35 mm)
Weight
approx. 600 g
* Analog inputs AI1…AI4 can also be configured as digital inputs.
Table 2 Digital inputs
Device PR200-230.1
PR200-230.2
PR200-230.4
PR200-24.1
PR200-24.2
PR200-24.4
Input voltage
230 V AC
24 V DC
Input voltage, max
264 V AC
30 V DC
Galvanic isolation
in groups of 4 (1-4, 5-8)
Test voltage between input groups
1780 V
Test voltage against other circuits
2830 V
Table 3 Digital outputs
Device PR200-230.1
PR200-230.2
PR200-230.4
PR200-24.1
PR200-24.2
PR200-24.4
Type
relay (NO)
Galvanic isolation
in groups of 2 (1-2, 3-4, 5-6, 7-8)
Test voltage between output groups
1780 V
Test voltage against other circuits
2830 V
Table 4 Analog inputs
Device
only PR200-230(24).2, PR200-230(24).4
Galvanic isolation
none
Mode
Analog
Input signal
0-10 V, 4-20 mA, 0-4 kohm
Input voltage *
-36…+36 V
Input resistance (0-10 V)
61 kohm
Input resistance (4-20 mA)
121 ohm
Mode
Digital
Logical 1 **
0…10 V, adjustable
Logical 0 **
0…10 V, adjustable
Current at input voltage 15…30 V, max
5 mA
* If the voltage at one input is below -0.5 V, the accuracy for all inputs cannot be guaranteed
** Parameter can be set in ALP Property Box using the option ‘Input mode’ = ‘digital’.
Table 5 Analog outputs
Device
PR200-230(24).2
PR200-230(24).4
Auxiliary voltage
12…30 V DC
Quantity
2
Output signal
4-20 mA
0-10 V
Output load, max
1 kohm
2 kohm
Basic error, max
±0.5%
Temperature influence
±0.05%/10 °C
Inductive load, max
50 µH
-
Signal conversion time
100 ms
DAC resolution
10 bit
Galvanic isolation
2830 V, individual
2830 V, in groups
Fig. 1 Dimensions
Fig. 2
a)
b)
Fig. 3
Installation
1. Align the upper slide of the DIN rail mounting groove with the DIN rail (arrow 1) and posh it onto the rail (arrow 2).
2. Wire external connections in accordance with Fig. 5-9 and tables 67 using plug-in terminal blocks (included).
NOTICE
The device should be configured via PC before mounting and wiring.
When wiring the device the terminal blocks with the same number of contacts can be encoded using coding elements from the package to prevent
swapping. If the coding tab is inserted into the recess in the header (Fig. 3a), and the coding profile is inserted into the slot on the plug (Fig. 3b), it is
impossible to connect them.
WARNING
Switch on the power supply only after the wiring of the device has been completely performed.

Summary of content (2 pages)