Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Safety Ordering information
DANGER
Installation may only be performed when the
module and all connected devices are
powered off.
Voltage on the terminals can be dangerous!
PRM-X.1
Supply voltage
I/O
Supply voltage
230 - 230 (90…264) V AC
24 - 24 (19…30) V DC
CAUTION
It is necessary to observe the polarity while
connecting 24V DC power supply! Voltage
reversal can damage the device.
I/O
1 8 DI, 8 DO
►
NOTICE
Installation and maintenance may only be
carried out by specialist personnel using the
correct tools!
Specifications
Table 1 General specification
Device
PRM-230.1
PRM-24.1
Power supply
230 (90…264) V AC; 50 (47…63) Hz
24 (19…30) V DC
Power consumption, max.
8 VA
4 W
Galvanic isolation
2830 V
1780 V
Inputs
Digital
8
Analog
-
Outputs
Digital
8
Analog
-
IP Code
IP20
Appliance class
II
Operation temperature
-20…+55°C
Relative humidity
up to 80% (at +25°C, non-condensing)
Dimensions (with terminals blocks)
88 x 108 x 58 mm
Mounting
DIN rail (35 mm)
Weight
approx. 250 g
Table 2 Digital inputs Table 3 Digital outputs
Device
PRM-230.1
PRM-24.1
Device
PRM-230.1
PRM-24.1
Input voltage
230 V AC
24 V DC
Type
Relay (NO)
Input voltage, max.
264 V AC
30 V DC
Galvanic isolation
in groups of 2 (1-2, 3-4, 5-6, 7-8)
Galvanic isolation
in groups of 4 (1-4, 5-8)
Test voltage between output groups
1780 V
Test voltage between input groups
1780 V
Test voltage against other circuits
2830 V
Test voltage against other circuits
2830 V
88 58
90
PRM-230.1
POWER
ERROR
1 21 2
- +
3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
DC 24V AC 230V
L N
COM 1 COM 2
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
DI
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DO
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Digital inputsPower supply
Digital outputs
Fig 1 Dimensions Fig 2 Terminal blocks
Electrical connections
Wire external connections in accordance with Fig. 2-5 and tables 3 using plug-in terminal blocks (included).
WARNINNG
Switch on the power supply only after the wiring of the device has been completely performed