Instructions

PR100.24.2.1_3-EN-73313-1.5
© All rights reserved. Subject to technical changes and misprints.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
PR100.24.2.1
Programmable relay
WARNING
Before working on the device, power it off as well as all connected
equipment.
WARNING
The device must be powered off before connecting to peripheral
devices or PC. Switch on the power supply only after the wiring has
been completed.
CAUTION
The program runs after transferring it to the relay. It is recommended
to transfer the program before wiring the relay.
Otherwise ensure that all peripheral devices are disconnected from
relay outputs before transferring the program.
1. Specification
Table 1 General specification
Power supply 24 (9…30) V DC
Power consumption, max. 4 W
Galvanic isolation 1500 V / 1 s
Inputs
Digital 8
Analog 4
Outputs
Digital 8
Analog
Network interface RS-485
Protocol
Modbus-RTU, Modbus-ASCII
Mode Master/Slave
Baud rate 9.6…115.2 kbit/s
Galvanic
isolation
1500 V / 1 s
Extension modules
none
Real-time clock accuracy ± 3 s/day
Dimensions (with terminal
blocks)
88 × 108 × 58 mm
Mounting DIN-rail (35 mm)
Weight approx. 250 g
Table 2 Digital inputs
Logical 1
8.5…30 V / 2…5 mA
Logical 0
-3…+5 V / 0…15 mA
Pulse length, min.
2 ms
Response time, max.
30 ms
Galvanic isolation
in groups of 4 (1-4, 5-8)
between inputs groups
1780 V / 1 s
against other circuits
2830 V / 1 s
Table 3 Analog inputs
Galvanic isolation
no
ADC resolution 12 bit
Analog mode
Input signal
0-10 V, 4-20 mA
Input voltage, max.
30 V
Input resistance for 0-10 V input
61
Basic error ±0.5 %
Temperature influence
±0.5 % / 10 °C
Digital mode
Nominal input voltage
24 V DC
Logical 1/0 switching threshold (adjustable in
ALP)
2.5…10 V
Logical 0/1 switching threshold (adjustable in
ALP)
3…10.5 V
Pulse length, min.
5 s
Signal frequency, max.
100 Hz
Table 4 Digital outputs
Type relay (NO)
Galvanic isolation individual
between outputs
1780 V
against other circuits
2830 V
Switching capacity AC
5 A, 250 V AC
(resistive load)
Switching capacity DC
3 A, 30 V DC
Load current at 5 V DC, min.
10 mA
Service life,
electrical
3 A, 30 V DC
100 000 switching cycles
5 A, 250 V AC (resistive load) 200 000 switching cycles
Table 5 Programming
Software ALP
Interface Micro-USB
Memory
ROM 128 kB
RAM 16 kB
Retain 1 kB
Network
variables
128 Byte
Program execution cycle, min.
1 ms
2. Operating conditions
The device is designed for natural convection cooling.
The following environmental conditions must be observed:
clean, dry and controlled environment, low dust level
closed non-hazardous areas, free of corrosive or flammable gases
Table 6 Operating conditions
Condition
Permissible range
Operating temperature
-40…+55 °C
Relative humidity up to 80 % (at +25 °C, non-condencing)
Attitude
up to 2000 m above sea level
Appliance class
II
IP code IP20
EMC immunity
conforms to IEC 61000-6-2
EMC emission conforms to IEC 61000-6-4
3. Installation
Fig. 1 Dimensions
Installation:
Fig. 2
1. Place the device on a DIN rail as shown in Fig. 2.
2. Press the device firmly against the DIN rail in the direction of arrow 2
until the latch locks.
3. Wire the device using the supplied terminal blocks.
Removing:
1. Take off the terminal blocks without disconnecting wires.
2. Insert a screwdriver into the eyelet of the slide interlock.
3. Loosen the slide interlock and then remove the relay from the DIN rail.
PR100 is equipped with plug-in terminal blocks which enable quick
replacement of the device without disconnecting the existing wiring.
4. Digital inputs wiring
Fig. 3 Switch contacts Fig. 4 3-wire sensors with PNP
transistor outputs