User's Manual

15
Triple-End-of-Line (TEOL) Resistor Wiring
The triple-end-of-line (TEOL) resistor shall be installed near the wired device at the end of a
zone loop to supervise the wiring conditions for NC or NO devices, so the panel can detect
alarm, tamper and anti-masking for corresponding devices via the open, secure or shorted
circuits.
9.
10.
AUX Power Wiring
The Control Panel can provide a maximum total of 2A current for hardwired zones,
auxiliary output, keypad (KPT-35-COMBO), wired expansion module (WEZC-8, WEZ
Series), output expander (WEPC-1), and PGM/Bell ports.
Min/Max operating voltages for devices/detectors is 10 VDC -14VDC.
Please note that the total current should not exceed 2A, otherwise, an additional power
supply is required.