Note: The user can connect +48 V or -48 V to ground.
Stages (Figure 92 – DBS sub-rack power connection)
1. Connect the switch at the top of the DBS sub-rack to the external DC power source. You are
recommended to pass the power supply cable via the top of the rack.
2. Ground the DBS sub-rack.
Note: a ground strip is fixed to the backplane and ensures its grounding. The rack and subrack ground
are screwed together, thus no special grounding is required for the rack.
Figure 91 – DBS sub-rack ground connection
Earthing must be done very carefully in order to assure good operation of the DBS.
3. Make sure that the fuses are inserted in the fuse-holder. Before changing fuse, make sure that the
switch is set to OFF.
Figure 92 – DBS sub-rack power connection
ATTENTION: DO NOT CONNECT THE GROUNDING CABLE TO THE SWITCH
BUT TO THE YELLOW/GREEN TERMINAL BLOCK
Fuse-holderPower supply cables
ON - OFF
Switch
Winding cassette for fiber optic
cables