10. Are all ground connections in compliance
with Alcatel-Lucent requirements
(exothermic weld, compression type with
2-hole lugs; properly secured;
anti-oxidant used on contact surface
area)?
Y N N/A
11. Are all grounding conductors routed as
straight as possible with no loops or sharp
bends?
Y N N/A
12. Is cabinet support structure grounded? Y N N/A
13. Are metallic conduits bonded at both ends
and 7.62 meter (25 foot) intervals?
Y N N/A
14. Are all fence corner posts and gate posts
properly grounded (including fence fabric
and barbed wire, as applicable)?
Y N N/A
15. Are all metallic objects within 1.8 meters
(6 feet) bonded to the grounding system?
Y N N/A
16. Is AC / DC power supply equipped with a
surge protection device and is the device
properly connected to the ground system?
Y N N/A
17. Is tower light system (if installed)
equipped with a surge protection device
and is the device properly connected to
the ground system?
Y N N/A
18. Are the RF surge protection devices
properly connected to the ground system?
Y N N/A
Notes:
1. Completed by: ______________________
2. Date: _______
Site preparation checklists for RRHs SP-3 Site preparation grounding checklist
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................