User's Manual

3-52
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
...........................................................................................................................................................................................................................................................
Cable connections in the Modular Cell 4.0B cabinets
................................................................................................................................
............................................
4 Route the cable into the EFIT and to J3 on the EFIM in the primary
cabinet as shown in the figure below.
................................................................................................................................
............................................
5 Connect the dual band cabinet integrated power alarm wire pairs to J3
as shown in the following table. Refer to the figure on Page 3-53, Note
1, and the table on Page 3 - 54.
POD B (4.0B With URCIIs
Only)
EFIM
EFIT
USER AND POWER
ALARM PUNCHDOWNS
USER AND POWER
ALARM PROTECTORS
Alarm Terminal Block
Pair (J3)
Wire Color Function
0+
B
lue - White User 0
Alarm
0- White - Blue
Power Major (PMJ)
1+
O
range - White User 1
Alarm
1- White -
Orange
Power Minor (PMN)
2+ Green - White User 2
Alarm
2- White - Green
AC Fail (ACF)
3+
N
/A User 3
Alarm
3- N/A
NOT USED
4+ Brown - White User 4
Alarm
4- White - Brown
B
atteries on Discharge
(BD)