User's Manual

Modular Cell 4.0B and WNG24-BC cabinet handling,
placement, anchoring and grounding
2- 65
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
............................................................................................................................................................................................................................................................
.............................................................................................................................................................................................................................................................
Post placement and anchoring procedures
Install the cabinet
grounding cables
All Lucent cabinets at a Modular Cell site require two grounding cables
that connect the cabinet to the grounding system. Lugs with installation
hardware are shipped with the cabinet. Refer to the figure on Page 2-
66, or those following, as applicable, which show the grounding lug
locations on the rear of the cabinet. Use the following procedure to
install cabinet grounding cables.
Important! Two bare solid or stranded #2 AWG grounding
cables should already be connected to the grounding electrode
system as part of site preparation.
................................................................................................................................
............................................
1 Locate the two #2 AWG grounding cables that are connected to the
grounding electrode system.
................................................................................................................................
............................................
2 Remove the double-hole grounding lug from the bottom rear of the
cabinet, or from the loose parts bag shipped with the cabinet. Refer to
the figure on Page 2-66, or those following, as applicable.
................................................................................................................................
............................................
3 Cut each cable to the proper length.
Important! When performing the next step, double crimp the
lug if the wire is stranded.
................................................................................................................................
............................................
4 Crimp a double-hole terminal lug onto the end of each cable.
................................................................................................................................
............................................
5 Verify that the cabinet grounding lug location is free of paint and polish,
if required.