Component installation in the Modular Cell 4.0B and the
WNG24-BC battery cabinets
Route the thermal probe
cable from the 4.0B primary
cabinet and mount the
thermal probe in the
battery cabinet
Important! If currently installing a second battery cabinet with
a 4.0B primary cabinet, skip to Step 2 for routing and positioning
of thermal probe cable and thermal probe.
Perform the following steps to route the thermal probe cable and mount
the thermal probe in the battery cabinet. A plastic mounting bracket
with double sided tape and a wire tie is supplied with each thermal
probe.
.....
......................................................................................................................................
1 For installations with a 4.0B primary cabinet, route the thermal probe
cable and mount the thermal probe on the battery retaining bracket as
listed in the following instructions.
• If the cabinet is fully populated with 10 strings (20 batteries):
• Route the thermal probe cable to the top shelf battery
retaining bracket and mount the thermal probe on the center
of the bracket. Refer to the figure on Page 5-82, item 1.
• If the cabinet is not fully populated with batteries:
• Route the thermal probe cable to the top populated shelf
battery retaining bracket and mount the thermal probe on the
center of the bracket. Refer to the figure on Page 5-82, item
2.
................................................................................................................................
............................................
2 If installing a second battery cabinet, refer to the figure and instructions
on Page 5 - 82.
................................................................................................................................
............................................
3 Remove the thermal probe from the retaining bracket in the first battery
cabinet and unplug it from the thermal probe cable. Refer to the figure
below, item 3.
................................................................................................................................
............................................
4 Relocate the removed thermal probe on the shelf 5 battery retaining
bracket (or highest populated shelf location) in the second battery
cabinet. Refer to the figure below, item 4 or 5.
................................................................................................................................
............................................
5 Locate the thermal probe cable supplied with the second battery cabinet.
Refer to the figure below, item 6. Plug this cable into the cable from the