Component installation in the Modular Cell 4.0B and the
WNG24-BC battery cabinets
Attach the interconnecting
bus bars
Perform the following steps to connect the interconnecting bus bars. Do
the bottom shelf first.
................................................................................................................................
............................................
1 Remove the series bus bar from the kit provided with the batteries.
................................................................................................................................
............................................
2 Apply antioxidant compound to the interconnecting bus bar, the positive
(+) terminal of battery 3, and the negative (-) terminal of battery 4. Refer
to the figure below.
................................................................................................................................
............................................
3 Place the interconnecting bus bar between the positive terminal of
battery 3 and the negative terminal of battery 4.
................................................................................................................................
............................................
4 Connect the interconnecting bus bar using the flat washers, lock washers
and nuts. Refer to the figure below for a top view (for mounting order).
Refer to the figure on Page 5-77 for a front view.
+
+
+
_
PARALLEL BUS BARS AND CABLES NOT SHOWN FOR CLARITY
FLAT WASHER
FLAT WASHER
LOCK WASHER
LOCK WASHER
NUT
NUT
BATTERY 4
BATTERY 3
BATTERY 2
TOP VIEW
SERIES BUS BAR
SERIES BUS BAR
+
_
BATTERY 5
_
_