Component installation in the Modular Cell 4.0B and the
WNG24-BC battery cabinets
Connect the negative
battery cables to the
batteries
Perform the following steps to connect the negative battery cables to
the batteries.
................................................................................................................................
............................................
1 Separate two of the battery cables. The negative cables from each of the
two battery cables will be connected to the batteries in the next step.
Important! When performing the next step, note that the two
negative battery cables being connected come from two separate
battery connectors. Refer to the figure on Page 5-80.
................................................................................................................................
............................................
2 Apply antioxidant compound to the two negative (-) battery terminals of
batteries 1 and 2. Refer to the figure on Page 5-79.
................................................................................................................................
............................................
3 Connect the two negative (-) battery cables (from separate connectors)
to the negative (-) terminal of batteries 1 and 2, using the flat washers,
lock washers and nuts. Refer to the figure below.