Overview of the Flexent‚ Modular Cell 4.0B cabinet
installation
1- 49
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
............................................................................................................................................................................................................................................................
.............................................................................................................................................................................................................................................................
Minimum installation temperatures
General
Power wire insulation tends to crack while being handled during
installation at extremely cold temperatures. For this reason minimum
temperatures have been established for the installation.
Affected installations
The following installations are affected by the minimum working
temperatures:
• All Modular Cell 4.0radio cabinets that do not have integrated
power being installed with PowerHouse 24 or WNG24-K power
cabinets or non-Lucent power
• The WNG24-BC or 60ECv2 battery cabinets, and the EZBFo
battery frame
Affected wire sizes
The following are the affected wire sizes:
• 2 AWG and larger
Affected wire insulation
type
The following are the affected wire insulation types:
• THHN
Minimum temperatures
The following are the minimum working and storage temperatures:
• Working (Installation): -25 degrees C (-13 degrees F)
• If installation has to proceed at -25 deg. C or below, see
"Storage prior to installation" on the next page.