Modular Cell 4.0B and WNG24-BC cabinet handling,
placement, anchoring and grounding
2- 3
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
............................................................................................................................................................................................................................................................
.............................................................................................................................................................................................................................................................
How to determine the anchoring requirements
Overview
Cabinet anchoring must meet all requirements of the local codes, taking
into consideration the seismic zone of the installation site.
Anchoring options
Use the following table to determine how many anchors are required.
If installation is: Then:
Zone 0, 1, 2, 3, or 4 Install 4 anchors.
Customer-supplied raised floor or
platform
Zone 0, 1, 2, 3, or 4
Customer shall supply anchor hardware.
(1/2" bolt size, corrosion resistant)
Zone 3 or 4 (EZBFo battery base module
only)
Install 8 anchors.