Anchor and torque requirements
Anchor and torque
requirements
The following table provides torque requirements for the installation of
the Modular Cell 4.0B cabinet and WNG battery cabinet anchor bolts.
Seismic
Zone(s)
Anchor Type Wrench Torque
Newton
Meters
Foot
pounds
0, 1, 2 (4) 1/2" drop in 3/4" 24 Nm 18 ft-lb
3, 4 (4) 12-mm expansion
stud
19-mm 79 Nm 58 ft-lb