User's Manual

2-48
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
...........................................................................................................................................................................................................................................................
Modular Cell 4.0B and WNG24-BC cabinet handling,
placement, anchoring and grounding
Complete the installation of
the AC feed-through
coupling and tighten the
anchor bolts or nuts
Refer to the figure below and perform the following steps to complete
the installation of the AC feed-through coupling and tighten the anchor
bolts or nuts.
................................................................................................................................
............................................
1 Remove the temporary locknut from the AC coupling inside of the
existing cabinet and fully install a sealing washer ("BOX SIDE" facing
the cabinet wall) onto the AC coupling.
................................................................................................................................
............................................
2 Replace and tighten the locknut and install a 2-inch plastic bushing on
the end of the coupling.
Important! If installing a second battery cabinet, skip the next
step.
................................................................................................................................
............................................
3 If installing a first battery cabinet, tighten the locknut and assemble the
2-inch to 1/2-inch reducer on the coupling inside of the first WNG24-
BC battery cabinet, as shown in the figure below.
BOTTOM FRONT VIEW
SEALING WASHER*
AREA BETWEEN
CABINETS
LOCK NUT
2-inch
FEED-THROUGH COUPLING
2-inch
P
LASTIC BUSHING
SEALING WASHER
LOCK NUT
MODULAR CELL 4.0/4.0B
PRIMARY CABINET
FIRST WNG24-BC
BATTERY CABINET
2-inch TO 1/2-inch
REDUCER WITH SEA
L
*(”BOX SIDE” FACING
CABINET WALL)